ABB 1SDA071175R1 Emax 2 E4.2V 3200 Ekip Touch LSI three-pole fixed air circuit breaker with a 3200 A rated uninterrupted current, 690 V AC operational voltage, 150 kA breaking capacity at 380–440 V AC and LSI electronic protection for demanding low-voltage power distribution systems.
£14,719.56
The ABB E4.2V 3200 Ekip Touch LSI 3p FHR, order code 1SDA071175R1, is a high-performance air circuit breaker (ACB) designed for protection, switching and isolation in demanding high-current low-voltage power distribution systems. Part of the ABB Emax 2 air circuit breaker series, it combines a 3200 A rated uninterrupted current with the advanced Ekip Touch LSI electronic trip unit for industrial, commercial, infrastructure and critical-power installations.
The E4.2V performance level delivers exceptional short-circuit capability, with a rated ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC and 100 kA at 500–690 V AC. Its Ekip Touch LSI electronic release provides adjustable long-time overload, selective short-time short-circuit and instantaneous short-circuit protection, enabling precise protection coordination across complex electrical distribution networks.
With a rated operational voltage of 690 V AC, three-pole construction and fixed installation with rear flat horizontal terminals, the 1SDA071175R1 is engineered for integration into high-capacity low-voltage switchboards and power distribution assemblies. Its rated short-time withstand current of 100 kA for 1 s further supports selective protection strategies in installations with substantial prospective fault currents.
Air circuit breakers such as the ABB Emax 2 E4.2V provide switching, isolation and overcurrent protection for high-current low-voltage distribution systems. With an ultimate short-circuit breaking capacity reaching 150 kA, the E4.2V is engineered to interrupt substantial prospective fault currents while helping protect switchboards, busbars, cables, transformers and downstream electrical equipment.
The Ekip Touch LSI electronic trip unit combines adjustable long-time overload, selective short-time and instantaneous short-circuit protection. The short-time protection function enables greater coordination between upstream and downstream protective devices than an LI configuration, helping localise faults while maintaining continuity of supply to unaffected sections of the electrical installation.
| Product group | Emax 2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E4.2 |
| Performance level | V |
| Order code / SKU | 1SDA071175R1 |
| EAN | 8015644750251 |
| Product type | Air circuit breaker (ACB) |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50/60 Hz |
| Number of poles | 3 |
| Trip unit | Ekip Touch LSI electronic release |
| Release type | Electronic (EL) |
| Protection functions | Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) |
| Overload protection adjustment range | 1280–3200 A |
| Overload protection setting | 0.4–1 × In |
| Instantaneous protection setting | 1.5–15 × In |
| Ultimate short-circuit breaking capacity (Icu) at 380 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 400 / 415 / 440 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 / 525 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 75 kA |
| Installation | Fixed |
| Main terminal position | Rear |
| Terminal configuration | Rear flat horizontal |
| Terminal type | Bolt |
| Auxiliary contacts | 4 change-over contacts |
| Open/closed position indication | Yes |
| Power loss | 425 W |
| Standard | IEC 60947-2 |
The ABB 1SDA071175R1 is an Emax 2 air circuit breaker designed for switching, isolation and selective overcurrent protection in demanding high-current low-voltage power distribution systems.
The breaker has a rated uninterrupted current of 3200 A, making it suitable for high-current switchboards, main incomers, feeders and power distribution installations.
The E4.2V provides a rated ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC and 100 kA at 500–690 V AC. Its rated short-time withstand current is 100 kA for 1 s.
The Ekip Touch LSI electronic trip unit provides long-time overload, selective short-time short-circuit and instantaneous short-circuit protection. This LSI configuration enables more flexible protection coordination than an LI-only trip unit.
The 1SDA071175R1 is a fixed three-pole air circuit breaker with rear flat horizontal main terminals for integration into low-voltage switchboards and power distribution assemblies.
ABB Emax 2 air circuit breakers are engineered for advanced protection and control of high-current low-voltage electrical distribution systems, combining exceptional short-circuit performance with intelligent Ekip electronic protection technology.