1SDA071173R1 ABB E4.2V 3200 Ekip Dip LSIG 3p F HR Air Circuit Breaker

1SDA071173R1 ABB E4.2V 3200 Ekip Dip LSIG 3p F HR Air Circuit Breaker

ABB 1SDA071173R1 E4.2V 3200 Ekip Dip LSIG 3p F HR is a fixed three-pole 3200 A SACE Emax 2 air circuit breaker with 150 kA ultimate short-circuit breaking capacity at 440 V AC and Ekip Dip LSIG electronic protection including earth-fault protection.

SKU: 1SDA071173R1MPN: 1SDA071173R1
Price
List Price £20,327.70 ex VAT
Your Price (ex VAT) Save 25%
£15,245.78 25% OFF
You save £5,081.93 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £15,245.78
Trade pricing is personalised to your account

Manufacturer Lead Time

£15,245.78

Why Choose the ABB E4.2V 3200 Ekip Dip LSIG 3p F HR Air Circuit Breaker?

The ABB E4.2V 3200 Ekip Dip LSIG 3p F HR, order code 1SDA071173R1, is a high-performance air circuit breaker (ACB) designed for protection, control and isolation in demanding high-current low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 series, this fixed three-pole circuit breaker combines a 3200 A rated uninterrupted current with the Ekip Dip LSIG solid-state electronic trip unit.

The Ekip Dip LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. This comprehensive LSIG configuration supports selective coordination with other protective devices while providing integrated protection against overloads, short circuits and earth faults.

The E4.2V performance level combines a 150 kA ultimate short-circuit breaking capacity at 440 V AC with a 100 kA short-time withstand current for 1 s, making the breaker suitable for systems with exceptionally high prospective fault currents. This version features a fixed three-pole construction with rear horizontal terminals, four auxiliary contacts and circuit-breaker open/closed position indication.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 3200 A rated uninterrupted current for high-current electrical installations.
  • 150 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 100 kA short-time withstand current for 1 s for high fault-level applications.
  • Ekip Dip LSIG solid-state electronic trip unit for comprehensive circuit protection.
  • Integrated earth-fault protection alongside overload and short-circuit protection.
  • LSIG protection supports effective coordination and selective fault isolation.
  • Fixed three-pole construction with rear horizontal terminals.

Key Features

  • ABB SACE Emax 2 E4.2V series.
  • 3200 A rated uninterrupted current.
  • Three-pole fixed air circuit breaker.
  • Ekip Dip LSIG solid-state electronic protection release.
  • Long-time overload (L), short-time delayed (S), instantaneous short-circuit (I) and earth-fault (G) protection.
  • 150 kA Icu at 440 V AC.
  • 100 kA Icw for 1 s.
  • 690 V rated voltage.
  • Adjustable overload and short-circuit protection thresholds.
  • Integrated earth-fault protection.
  • Rear horizontal main circuit terminals.
  • Four auxiliary contacts with open/closed circuit-breaker position indication.

High-Fault-Level Circuit Protection with Earth-Fault Protection

Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical distribution systems against overloads, short circuits and earth faults while providing dependable switching and isolation. The E4.2V frame combines a substantial 3200 A current capability with 150 kA short-circuit breaking performance at 440 V AC and 100 kA short-time withstand capability, making it particularly suitable for installations with exceptionally high prospective fault currents.

The Ekip Dip LSIG electronic trip unit combines long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection. Its adjustable protection functions support coordination with downstream protective devices, helping engineers isolate faults selectively while protecting conductors, switchgear and connected equipment across the electrical distribution system.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution and manufacturing facilities.
  • Very high fault-level electrical distribution systems.
  • High-current main incomer applications.
  • Transformer secondary circuit protection.
  • Systems requiring integrated earth-fault protection.
  • Commercial buildings and infrastructure electrical systems.
  • Data centres and critical power distribution installations.
  • OEM switchgear and electrical panel building.

Technical Specifications

Series SACE Emax 2
ABB product group Emax2 Air Circuit Breaker
Frame E4.2V
ABB order code / MPN 1SDA071173R1
Product type Air circuit breaker
Rated uninterrupted current (Iu) 3200 A
Rated voltage 690 V
Ultimate short-circuit breaking capacity (Icu) 150 kA at 440 V AC
Short-time withstand current (Icw) 100 kA for 1 s
Number of poles 3
Current type AC
Trip unit Ekip Dip LSIG
Release type Solid-state electronic
Protection functions LSIG
Overload release adjustment range 1280–3200 A
Short-time delayed short-circuit adjustment range 1920–32000 A
Long-time protection Overload protection
Short-time protection Delayed short-circuit protection
Instantaneous protection Short-circuit protection
Earth-fault protection Integrated
Short-circuit performance level V
Installation version Fixed
Main terminal position Rear
Main terminal orientation Rear horizontal
Auxiliary contacts 4
Open/closed position indication Yes
Dimensions 384 × 371 mm
Standard IEC
Country of origin Italy
EAN / GTIN 8015644750237

Frequently Asked Questions

What is the ABB 1SDA071173R1 used for?

The ABB 1SDA071173R1 is an Emax 2 air circuit breaker designed to protect, control and isolate high-current low-voltage electrical distribution circuits, particularly in installations requiring very high short-circuit performance and integrated earth-fault protection.

What is the current rating of the ABB E4.2V 3200?

The circuit breaker has a rated uninterrupted current of 3200 A, making it suitable for substantial industrial, commercial and infrastructure power distribution circuits.

What breaking capacity does the ABB 1SDA071173R1 provide?

The E4.2V 3200 provides an ultimate short-circuit breaking capacity of 150 kA at 440 V AC together with a short-time withstand current of 100 kA for 1 s.

What protection functions are provided by the Ekip Dip LSIG trip unit?

The Ekip Dip LSIG trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.

Is the ABB 1SDA071173R1 a fixed or withdrawable circuit breaker?

The 1SDA071173R1 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals for integration into low-voltage switchboards.

Trusted by Electrical Distribution Professionals Worldwide

ABB SACE Emax 2 air circuit breakers are designed for reliable protection, control and monitoring of low-voltage power distribution systems, combining high short-circuit performance with advanced electronic protection for demanding industrial and commercial installations.