Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071165R1 SACE Emax 2 E4.2H fixed three-pole air circuit breaker with Ekip Touch LSI electronic protection, 3200 A rated current, 690 V AC rating and 100 kA breaking capacity at 440 V AC.
£12,263.87
The ABB E4.2H 3200 Ekip Touch LSI 3p FHR, order code 1SDA071165R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in demanding low-voltage power distribution systems. This fixed three-pole E4.2 breaker combines a 3200 A rated uninterrupted current with ABB's advanced Ekip Touch LSI solid-state electronic trip unit.
The Ekip Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Its adjustable electronic protection functions support selective coordination within complex distribution systems, while the Ekip Touch interface provides an intuitive platform for configuring protection settings and accessing operating information.
The E4.2H performance level provides an ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 85 kA for 1 s. Rated for operation at 690 V AC and supplied with rear horizontal terminals, four change-over auxiliary contacts and open/closed position indication, the 1SDA071165R1 is engineered for high-current industrial and infrastructure switchboards.
The ABB SACE Emax 2 E4.2H is engineered for major low-voltage distribution points where high continuous currents and substantial prospective fault levels demand robust interruption and withstand performance. Its combination of a 3200 A rated current, 100 kA breaking capacity at 440 V AC and 85 kA short-time withstand capability provides dependable protection for switchboards, feeders, busbars, transformers and connected equipment.
The Ekip Touch LSI trip unit adds adjustable short-time protection between the long-time overload and instantaneous functions. This allows improved coordination with downstream protective devices, helping isolate the circuit affected by a fault while maintaining continuity elsewhere in the installation where the overall protection design permits.
| Series | SACE Emax 2 E4.2 |
|---|---|
| ABB order code | 1SDA071165R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Frame | E4.2 |
| Performance level | H |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated voltage | 690 V AC |
| Current type | AC |
| Number of poles | 3 |
| Installation | Fixed |
| Trip unit | Ekip Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Integrated earth-fault protection | No |
| Overload release setting range | 1280–3200 A |
| Short-time delayed short-circuit setting range | 1920–32,000 A |
| Instantaneous short-circuit setting range | 4800–48,000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Rated short-time withstand current (Icw), 1 s | 85 kA |
| Main terminal position | Rear |
| Terminal orientation | Horizontal |
| Main-circuit connection | Bolt connection |
| Auxiliary contacts | 4 change-over contacts |
| Trip contact | Yes |
| Position indication | Circuit breaker open / closed |
| Degree of protection | IP30 |
| Operating element | Push button |
| Complete device including protection unit | Yes |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Integrated undervoltage release | No |
| DIN rail mounting | No |
| Power loss | 425 W |
| Net weight | 56 kg |
| EAN / GTIN | 8015644750152 |
| Country of manufacture | Italy |
| Standard / approval | IEC |
The ABB 1SDA071165R1 is a SACE Emax 2 E4.2H fixed three-pole air circuit breaker rated at 3200 A and equipped with an Ekip Touch LSI solid-state electronic trip unit.
The Ekip Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The E4.2H 3200 provides an ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 85 kA for 1 s.
No. This model uses an LSI protection configuration, providing long-time, short-time and instantaneous protection without integrated earth-fault protection.
It is designed for high-current low-voltage distribution applications including industrial switchboards, main distribution panels, transformer secondary systems, critical-power installations, infrastructure networks and OEM switchgear assemblies.
ABB SACE Emax 2 air circuit breakers combine high-current switching, substantial short-circuit performance and advanced electronic protection for dependable low-voltage power distribution in demanding industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.