1SDA071126R1 ABB E4.2V 2500 Ekip Touch LSIG 3p FHR Air Circuit Breaker

1SDA071126R1 ABB E4.2V 2500 Ekip Touch LSIG 3p FHR Air Circuit Breaker

ABB 1SDA071126R1 Emax 2 E4.2V 2500 fixed three-pole air circuit breaker with Ekip Touch LSIG electronic protection, 2500 A rated current, 690 V AC rating and 150 kA breaking capacity at 415 V AC.

SKU: 1SDA071126R1MPN: 1SDA071126R1
Price
List Price £16,780.58 ex VAT
Your Price (ex VAT) Save 25%
£12,585.44 25% OFF
You save £4,195.15 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £12,585.44
Trade pricing is personalised to your account

Manufacturer Lead Time

£12,585.44

Why Choose the ABB E4.2V 2500 Ekip Touch LSIG 3p FHR Air Circuit Breaker?

The ABB E4.2V 2500 Ekip Touch LSIG 3p FHR, order code 1SDA071126R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection, switching and management of demanding low-voltage power distribution systems. Part of the ABB Emax 2 E4.2 series, this fixed three-pole breaker combines a 2500 A rated current with the advanced Ekip Touch LSIG solid-state electronic trip unit.

The Ekip Touch LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Its touchscreen-based electronic platform provides flexible protection configuration and supports the wider Emax 2 ecosystem for measurement, communication and power-management functions, making it well suited to sophisticated industrial and infrastructure distribution systems.

The E4.2V performance level delivers an ultimate short-circuit breaking capacity of 150 kA at 415 V AC together with a rated short-time withstand current of 100 kA for 1 s. With a rated operational voltage of 690 V AC, fixed three-pole construction and rear flat horizontal terminals, the 1SDA071126R1 is engineered for critical high-current switchboards where exceptional fault interruption capability is required.

Key Advantages

  • High-performance ABB SACE Emax 2 E4.2V air circuit breaker.
  • 2500 A rated current for high-current low-voltage distribution.
  • Exceptional 150 kA ultimate short-circuit breaking capacity at 415 V AC.
  • 100 kA rated short-time withstand current for 1 s.
  • Advanced Ekip Touch LSIG electronic trip unit.
  • LSIG protection covers overload, short-time, instantaneous and earth-fault conditions.
  • Touchscreen-based protection interface supports intuitive configuration and monitoring.
  • Fixed three-pole construction for permanent switchboard installation.
  • Rear flat horizontal terminals support integration with high-current busbar systems.

Key Features

  • ABB SACE Emax 2 E4.2V series.
  • 2500 A rated current.
  • Three-pole configuration.
  • Fixed installation version.
  • Ekip Touch LSIG solid-state electronic release.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • Touchscreen interface for protection configuration and system information.
  • Rated operational voltage of 690 V AC.
  • 150 kA Icu at 415 V AC.
  • 100 kA Icw for 1 s.
  • Rear flat horizontal main terminals.
  • Four auxiliary contacts fitted.
  • Circuit-breaker open/closed position indication.

Advanced LSIG Protection for High-Fault-Level Power Distribution

The ABB SACE Emax 2 E4.2V is designed for critical low-voltage installations where high continuous currents and exceptionally high prospective fault levels require substantial interruption and withstand performance. Its combination of a 2500 A current rating, 150 kA breaking capacity at 415 V AC and 100 kA short-time withstand capability makes it suitable for major distribution points in industrial, infrastructure and critical-power networks.

The Ekip Touch LSIG electronic trip unit provides comprehensive protection against overloads, short circuits and earth faults while offering a modern touchscreen interface for configuration and system supervision. Short-time protection supports selective coordination with downstream protective devices, while integrated earth-fault protection provides an additional layer of protection for the distribution network.

Typical Applications

  • High-fault-level low-voltage main switchboards.
  • Industrial power distribution systems.
  • High-current incomer and feeder protection.
  • Manufacturing and process plant switchgear.
  • Large commercial and infrastructure installations.
  • Power distribution centres and substations.
  • Transformer secondary distribution systems.
  • Data centre and critical-power switchboards.
  • Utility and heavy-industry low-voltage distribution.
  • Installations requiring integrated earth-fault protection.
  • OEM low-voltage switchboards and switchgear assemblies.

Technical Specifications

Series SACE Emax 2 E4.2
ABB order code 1SDA071126R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Frame E4.2
Performance level V
Rated current 2500 A
Rated uninterrupted current (Iu) 2500 A
Current type AC
Number of poles 3
Installation Fixed
Trip unit Ekip Touch LSIG
Release type Solid-state electronic
Protection functions Long-time, short-time, instantaneous and earth fault (LSIG)
Earth-fault protection Yes
Rated operational voltage (Ue) 690 V AC
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 150 kA
Rated short-time withstand current (Icw), 1 s 100 kA
Main terminal position Rear
Terminal configuration Rear flat horizontal
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Power loss 425 W
Width 384 mm
Depth 270 mm
EAN 8015644749767
Country of origin Italy
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA071126R1?

The ABB 1SDA071126R1 is an Emax 2 E4.2V fixed three-pole air circuit breaker rated at 2500 A and equipped with an Ekip Touch LSIG solid-state electronic trip unit.

What protection functions does the Ekip Touch LSIG trip unit provide?

The Ekip Touch LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection.

What is the breaking capacity of the ABB E4.2V 2500?

The E4.2V 2500 provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC and a rated short-time withstand current of 100 kA for 1 s.

Is the ABB 1SDA071126R1 fixed or withdrawable?

This model is a fixed three-pole air circuit breaker equipped with rear flat horizontal main terminals.

Where is the ABB E4.2V 2500 Ekip Touch LSIG typically used?

It is designed for demanding low-voltage distribution applications including industrial switchboards, high-fault-level main distribution panels, transformer secondary systems, data centres, critical-power installations, infrastructure networks and OEM switchgear assemblies.

Trusted Protection from ABB

ABB SACE Emax 2 air circuit breakers combine exceptional short-circuit performance, advanced electronic protection and flexible power-management capabilities for dependable low-voltage distribution in demanding industrial, commercial and infrastructure installations.