Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071105R1 E4.2V 2000 Ekip Touch LSI 3p F HR is a fixed three-pole 2000 A SACE Emax 2 air circuit breaker with 150 kA ultimate short-circuit breaking capacity at 415 V AC and Ekip Touch LSI electronic protection.
£9,325.82
The ABB E4.2V 2000 Ekip Touch LSI 3p F HR, order code 1SDA071105R1, is a high-performance air circuit breaker (ACB) designed for protection, control and isolation in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 series, this fixed three-pole circuit breaker combines a 2000 A rated current with the Ekip Touch LSI solid-state electronic trip unit.
The Ekip Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This combination enables adjustable electronic protection and effective system coordination, while the Ekip Touch platform provides an intuitive interface for configuring and supervising the circuit breaker's protection functions.
The E4.2V performance level combines a 150 kA ultimate short-circuit breaking capacity at 415 V AC with a 100 kA short-time withstand current for 1 s, making the breaker suitable for systems with very high prospective fault currents. This version features a fixed three-pole construction with rear horizontal terminals, four auxiliary contacts and circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical distribution systems against overloads and short circuits while providing dependable switching and isolation. The E4.2V frame combines a 2000 A current rating with exceptional short-circuit interruption and withstand capability, making it particularly suitable for installations where very high prospective fault currents are present.
The Ekip Touch LSI electronic trip unit combines long-time overload, short-time delayed and instantaneous short-circuit protection. The inclusion of short-time protection enables improved coordination with other protective devices compared with an LI-only configuration, helping engineers achieve selective fault isolation while protecting conductors, switchgear and connected electrical equipment.
| Series | SACE Emax 2 |
|---|---|
| ABB product group | Emax2 Air Circuit Breaker |
| Frame | E4.2V |
| ABB order code / MPN | 1SDA071105R1 |
| Product type | Air circuit breaker |
| Rated current | 2000 A |
| Rated operational voltage | 690 V AC |
| Ultimate short-circuit breaking capacity (Icu) | 150 kA at 415 V AC |
| Short-time withstand current (Icw) | 100 kA for 1 s |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | LSI |
| Long-time protection | Overload protection |
| Short-time protection | Delayed short-circuit protection |
| Instantaneous protection | Short-circuit protection |
| Earth-fault protection | Not included in LSI configuration |
| Short-circuit performance level | V |
| Installation version | Fixed |
| Main terminal position | Rear |
| Main terminal orientation | Rear horizontal |
| Auxiliary contacts | 4 |
| Open/closed position indication | Yes |
| Dimensions | 270 × 371 × 270 mm |
| Standard | IEC |
| EAN / GTIN | 8015644749552 |
The ABB 1SDA071105R1 is an Emax 2 air circuit breaker designed to protect, control and isolate high-current low-voltage electrical distribution circuits, particularly in installations requiring very high short-circuit breaking performance.
The circuit breaker has a rated current of 2000 A, making it suitable for substantial industrial, commercial and infrastructure power distribution circuits.
The E4.2V 2000 provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC and a short-time withstand current of 100 kA for 1 s.
The Ekip Touch LSI trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection. The LSI configuration does not include the earth-fault protection function provided by LSIG variants.
The 1SDA071105R1 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals for integration into low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers are engineered for reliable protection and control of demanding low-voltage power distribution systems, combining high short-circuit performance with advanced electronic protection for industrial, commercial and infrastructure installations.