Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071089R1 Emax 2 E2.2H 2500 air circuit breaker, a 2500 A three-pole fixed ACB with Ekip Hi-Touch LSIG electronic protection, 690 V AC rated operational voltage and up to 100 kA short-circuit breaking capacity.
£13,228.61
The ABB E2.2H 2500 Ekip Hi-Touch LSIG 3p F HR, order code 1SDA071089R1, is a high-performance Emax 2 air circuit breaker (ACB) designed for protection, switching and advanced management of demanding low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, it combines a 2500 A current rating with high short-circuit performance and sophisticated electronic protection for industrial, infrastructure and commercial power installations.
This fixed three-pole circuit breaker incorporates the Ekip Hi-Touch LSIG electronic trip unit, providing long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection. The Hi-Touch platform provides advanced protection and monitoring capabilities, making the breaker suitable for sophisticated electrical networks where selectivity, system visibility and reliable fault protection are essential.
With a rated uninterrupted current of 2500 A and a rated operational voltage of 690 V AC, the E2.2H provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC. Its fixed three-pole configuration and rear flat horizontal terminals provide straightforward integration into high-current low-voltage switchboards and distribution assemblies.
Air circuit breakers such as the ABB Emax 2 E2.2H protect high-current low-voltage distribution systems against overload, short-circuit and earth-fault conditions while providing controlled switching and isolation. The E2.2H performance level is particularly suited to installations with high prospective fault currents, delivering substantial interruption and short-time withstand capability for demanding electrical networks.
The Ekip Hi-Touch LSIG electronic trip unit combines long-time, selective short-time and instantaneous overcurrent protection with earth-fault protection. This comprehensive protection package supports selective system coordination while helping protect conductors, switchgear and connected equipment against a wide range of electrical fault conditions.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA071089R1 |
| EAN | 8015644749392 |
| Product type | Air circuit breaker (ACB) |
| Frame | E2.2 |
| Short-circuit performance level | H |
| Rated current (In) | 2500 A |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 400 / 415 / 440 V AC |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 85 kA for 1 s; 66 kA for 3 s |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time overload, selective short-time, instantaneous short circuit and earth fault |
| Mounting type | Fixed |
| Terminal connection | Rear flat horizontal |
| Terminal type | Bolt |
| Connecting capacity | 1800 mm² |
| Recommended terminal screw | M12 |
| Terminal tightening torque | 70 N·m |
| Auxiliary contacts | 4 |
| Power loss | 267 W |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 8,000 cycles at Ue ≤ 440 V; 7,000 cycles at Ue 500–690 V |
| Dimensions (H × W × D) | 371 × 276 × 270 mm |
| Net weight | 41 kg |
| Suitable for IT networks | Yes, up to 690 V |
| Standard | IEC 60947-2 |
The ABB 1SDA071089R1 is an Emax 2 air circuit breaker designed for protection and switching of high-current low-voltage electrical distribution systems, particularly installations requiring high short-circuit performance and comprehensive LSIG protection.
The circuit breaker has a rated uninterrupted current of 2500 A, making it suitable for high-current industrial, infrastructure and commercial electrical distribution systems.
The E2.2H 2500 provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC.
The Ekip Hi-Touch LSIG electronic trip unit provides long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection for comprehensive protection of low-voltage electrical systems.
The 1SDA071089R1 is a fixed three-pole air circuit breaker equipped with rear flat horizontal terminals for integration into low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic LSIG protection and robust construction for demanding industrial, commercial and infrastructure electrical distribution systems.
We use cookies