Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071077R1 E2.2S 2500 Ekip G Touch LSIG is a fixed three-pole 2500 A SACE Emax 2 air circuit breaker with rear horizontal terminals, 85 kA breaking capacity at 400/415 V AC and advanced LSIG generator protection.
£12,366.18
The ABB E2.2S 2500 Ekip G Touch LSIG 3p F HR, order code 1SDA071077R1, is a high-performance 2500 A three-pole air circuit breaker (ACB) designed for advanced generator and low-voltage power distribution protection. As part of the ABB SACE Emax 2 series, it combines the E2.2S high-breaking-capacity platform with an Ekip G Touch LSIG electronic trip unit, fixed installation and rear horizontal terminals.
This breaker provides a rated uninterrupted current of 2500 A and an ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC. The Ekip G Touch LSIG release provides adjustable long-time, short-time, instantaneous and earth-fault protection together with generator-specific protection functionality and advanced electrical measurement capabilities.
The 1SDA071077R1 is supplied as a fixed three-pole breaker with rear horizontal terminals. Its combination of high fault-breaking performance, configurable electronic protection and generator-oriented functionality makes it suitable for generator switchboards, industrial power systems, critical infrastructure and other demanding high-current installations.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and protection for high-current low-voltage electrical systems. The E2.2S platform combines high short-circuit performance with advanced electronic protection, helping safeguard generators, cables, switchgear and connected equipment against overloads and electrical faults.
The Ekip G Touch LSIG release is specifically suited to generator protection while also providing comprehensive LSIG protection for distribution circuits. Its configurable electronic functions and measurement capabilities enable engineers to coordinate protection and monitor electrical conditions within modern generation and power-distribution systems.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA071077R1 |
| Product type | Air circuit breaker (ACB) |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated operational voltage (Ue) | up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Number of poles | 3 |
| Mounting | Fixed |
| Main terminal arrangement | Rear horizontal |
| Trip unit | Ekip G Touch LSIG |
| Protection functions | Long-time, short-time, instantaneous and earth fault |
| Long-time protection adjustment | 0.4–1 × In |
| Short-time protection adjustment | 0.6–10 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Earth-fault protection adjustment | 0.1–1 × In |
| Auxiliary change-over contacts | 4 |
| Power loss | 267 W |
| Protection rating | IP30 |
| Applicable standard | IEC 60947-2 |
| Net weight | approx. 41 kg |
The ABB 1SDA071077R1 is a 2500 A air circuit breaker designed for advanced generator protection and high-current low-voltage power distribution applications.
The breaker is fitted with an ABB Ekip G Touch LSIG electronic trip unit, providing long-time, short-time, instantaneous and earth-fault protection together with generator-specific protection functionality.
The breaker has a rated uninterrupted current of 2500 A.
This model is a fixed three-pole air circuit breaker equipped with rear horizontal main terminals.
The E2.2S 2500 has an ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC and 66 kA at 500/525–690 V AC, providing high fault-current protection for demanding electrical systems.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, generator-specific functionality, high short-circuit performance and flexible system integration for dependable protection of modern generation and low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.