Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071066R1 E2.2N 2500 Ekip Touch LSIG 3p F HR is a fixed three-pole 2500 A SACE Emax 2 air circuit breaker with 66 kA short-circuit breaking capacity at 400 V AC and adjustable LSIG electronic protection including earth-fault protection.
£8,185.66
The ABB E2.2N 2500 Ekip Touch LSIG 3p F HR, order code 1SDA071066R1, is a high-performance air circuit breaker (ACB) designed for protection, control and isolation in demanding low-voltage electrical distribution systems. As part of the advanced ABB SACE Emax 2 series, this fixed three-pole circuit breaker combines a 2500 A current rating with the Ekip Touch LSIG electronic trip unit for comprehensive protection of high-current electrical installations.
The breaker incorporates LSIG protection functions, providing long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. The Ekip Touch electronic release provides configurable protection and monitoring capabilities, supporting effective selectivity and coordination across industrial, commercial and infrastructure power distribution systems.
With a rated uninterrupted current of 2500 A, a rated operational voltage of 690 V AC and a short-circuit breaking capacity of 66 kA at 400 V AC, the E2.2N 2500 provides robust protection for substantial low-voltage networks. This version features a fixed three-pole construction with rear horizontal terminals, four auxiliary change-over contacts and circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical distribution systems against overloads, short circuits and earth faults while providing reliable switching and isolation. The E2.2N performance level combines a substantial 2500 A current rating with high short-circuit capability, making the breaker suitable for main distribution boards, industrial switchboards and other critical high-current electrical installations.
The Ekip Touch LSIG electronic trip unit combines long-time overload, short-time delayed, instantaneous short-circuit and ground-fault protection. Its adjustable protection thresholds enable effective coordination with other protective devices, helping engineers achieve system selectivity while protecting conductors, switchgear and connected equipment.
| Series | SACE Emax 2 |
|---|---|
| ABB product group | Emax2 Air Circuit Breaker |
| Frame | E2.2N |
| ABB order code / MPN | 1SDA071066R1 |
| Product type | Air circuit breaker |
| Rated current (In) | 2500 A |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Short-circuit breaking capacity (Icu) | 66 kA at 400 V AC, 50 Hz |
| Service short-circuit breaking capacity (Ics) | 100% of Icu |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | LSIG |
| Overload release adjustment range | 1000–2500 A |
| Short-time delayed short-circuit release adjustment range | 1500–25000 A |
| Instantaneous short-circuit release adjustment range | 3750–37500 A |
| Earth-fault protection | Integrated |
| Installation version | Fixed |
| Main terminal orientation | Rear horizontal |
| Connecting capacity | 1800 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Open/closed position indication | Yes |
| Integrated undervoltage release | No |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 8,000 cycles at Ue ≤ 440 V; 7,000 cycles at Ue 500–690 V |
| Power loss | 267 W |
| Dimensions (H × W × D) | 371 × 276 × 270 mm |
| Weight | 41 kg |
| Country of origin | Italy |
| EAN / GTIN | 8015644749163 |
The ABB 1SDA071066R1 is an Emax 2 air circuit breaker designed to protect, control and isolate high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications.
The circuit breaker has a rated uninterrupted current of 2500 A, making it suitable for substantial low-voltage power distribution circuits.
The E2.2N 2500 provides a short-circuit breaking capacity of 66 kA at 400 V AC, 50 Hz.
The Ekip Touch LSIG trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The 1SDA071066R1 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals for integration into low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers are designed for reliable protection, control and isolation of low-voltage power distribution systems, combining high-current switching performance with advanced electronic protection for demanding industrial and commercial installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.