Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071045R1 is a SACE Emax 2 E2.2S 2000 A fixed three-pole air circuit breaker with rear horizontal terminals, 85 kA breaking capacity at 400/415 V AC and an Ekip Touch LSI electronic trip unit.
£7,381.69
The ABB E2.2S 2000 Ekip Touch LSI 3p FHR, order code 1SDA071045R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and control of demanding low-voltage electrical distribution systems. Rated at 2000 A, this three-pole fixed circuit breaker combines the E2.2S frame with ABB's advanced Ekip Touch LSI electronic trip unit.
The Ekip Touch LSI release provides electronic long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. This combination supports effective protection and selective coordination within industrial and commercial distribution networks, while the touchscreen-based Ekip Touch platform provides an intuitive interface for configuring and supervising the protection functions.
This configuration is a fixed three-pole breaker equipped with rear horizontal (HR) terminals. The E2.2S version provides an ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC, a rated short-time withstand current of 66 kA for 1 s and a rated operational voltage up to 690 V AC, making it suitable for high-current switchboards, main distribution panels and critical power systems.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage distribution systems against overloads and short circuits while providing controlled switching and isolation of major electrical circuits. The E2.2S frame combines high interruption capability with the flexibility required for main incomers, feeders and other important circuits within industrial and commercial switchboards.
The Ekip Touch LSI trip unit provides configurable electronic long-time, short-time and instantaneous protection, enabling the breaker to respond appropriately to different overcurrent and short-circuit conditions. Short-time protection is particularly useful where selective coordination between upstream and downstream protection devices is required, helping isolate faults while maintaining continuity elsewhere in the electrical distribution system.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2S |
| ABB order code | 1SDA071045R1 |
| EAN | 8015644748951 |
| Product type | Air circuit breaker |
| Rated current | 2000 A |
| Number of poles | 3 |
| Trip unit | Ekip Touch LSI |
| Protection functions | L, S and I |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 400/415 V AC | 85 kA |
| Rated short-time withstand current (Icw, 1 s) | 66 kA |
| Rated short-time withstand current (Icw, 3 s) | 50 kA |
| Current type | AC |
| Installation | Fixed |
| Terminal configuration | Rear horizontal (HR) |
| Auxiliary contacts | 4 change-over contacts |
| Electrical durability at ≤440 V | 10000 cycles |
| Mechanical durability | 25000 cycles |
| Power loss | 212 W |
| Product dimensions | 371 × 276 × 270 mm |
| Product net weight | approx. 41 kg |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071045R1 is a SACE Emax 2 E2.2S fixed three-pole air circuit breaker rated at 2000 A and fitted with an Ekip Touch LSI electronic trip unit.
The Ekip Touch LSI release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
The circuit breaker has a rated current of 2000 A.
This E2.2S configuration provides an ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC.
The E2.2S has a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.
The 1SDA071045R1 is a fixed-version circuit breaker designed for permanent installation within a low-voltage switchboard.
In this configuration, the breaker is fixed and equipped with rear horizontal terminals, providing rear-facing main connections for integration with switchboard conductors and busbars.
It is typically used in high-current low-voltage distribution systems such as industrial switchboards, main incomers, feeder circuits, commercial infrastructure and installations requiring electronic LSI protection and selective coordination.
ABB SACE Emax 2 air circuit breakers are engineered for reliable protection, control and management of low-voltage electrical distribution systems, supporting demanding industrial, commercial and infrastructure applications worldwide.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.