Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071042R1 E2.2S 2000 Ekip Dip LSI three-pole fixed air circuit breaker with rear horizontal terminals, 2000 A rated current, 690 V AC rated operational voltage and up to 85 kA short-circuit breaking capacity for selective low-voltage power distribution protection.
£7,323.22
The ABB E2.2S 2000 Ekip Dip LSI 3p F HR, order code 1SDA071042R1, is a 2000 A air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for switching, isolation and protection in demanding low-voltage power distribution systems. Its E2.2 frame combines high current capacity with the S short-circuit performance class for industrial, commercial and infrastructure switchboards.
This model is equipped with an Ekip Dip LSI electronic trip unit, providing long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The combination provides essential electronic protection while the short-time function supports selective coordination between upstream and downstream protective devices.
The E2.2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC. The 1SDA071042R1 is a three-pole fixed circuit breaker with rear horizontal terminals and includes four auxiliary change-over contacts plus open/closed circuit-breaker position indication for integration into compatible low-voltage switchgear.
Air circuit breakers such as the ABB SACE Emax 2 E2.2S provide switching, isolation and protection for high-current low-voltage electrical networks. With a rated uninterrupted current of 2000 A and an ultimate short-circuit breaking capacity reaching 85 kA at 400–440 V AC, the E2.2S is suited to installations where substantial load currents and prospective fault levels must be safely managed.
The Ekip Dip LSI trip unit provides three complementary electronic protection functions. Long-time protection responds to sustained overload conditions, short-time protection permits controlled fault-clearing delays to improve selectivity with downstream devices, and instantaneous protection rapidly interrupts severe short circuits. This combination makes the 1SDA071042R1 particularly suitable for coordinated industrial and commercial distribution networks.
| Series | SACE Emax 2 |
|---|---|
| Frame / sub-type | E2.2S |
| Order code / MPN | 1SDA071042R1 |
| EAN / GTIN | 8015644748920 |
| Product type | Air circuit breaker (ACB) |
| Current type | AC |
| Rated current | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) | 85 kA at 400–440 V AC |
| Number of poles | 3 |
| Protection release | Ekip Dip LSI |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time) and I (instantaneous) |
| Integrated ground-fault protection | No |
| Short-circuit performance level | S |
| Mounting configuration | Fixed |
| Connection position | Rear |
| Terminal arrangement | Rear horizontal |
| Auxiliary contacts | 4 change-over contacts |
| Trip indication | Yes |
| Circuit-breaker position indication | Open / closed |
| Motor operator | Optional |
| Integrated motor operator | No |
| Degree of protection | IP30 |
| Product classification | Air circuit breaker for transformer, generator and installation protection |
| Standard | IEC 60947-2 |
The ABB 1SDA071042R1 is an Emax 2 air circuit breaker designed for switching, isolation and protection of high-current low-voltage circuits, including transformer, generator, main incomer, feeder and general installation protection applications.
The ABB E2.2S 2000 has a rated uninterrupted current of 2000 A and a rated operational voltage of 690 V AC, making it suitable for demanding high-current distribution applications.
The E2.2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC.
The Ekip Dip LSI electronic trip unit provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The short-time function supports selective coordination between upstream and downstream protective devices.
The F HR configuration identifies the 1SDA071042R1 as a fixed circuit breaker with rear horizontal terminals, intended for permanent installation and rear connection within compatible low-voltage switchgear.
ABB SACE Emax 2 air circuit breakers are engineered for reliable switching, isolation and protection of modern low-voltage electrical systems, combining high short-circuit performance with configurable electronic protection and flexible integration into industrial and commercial switchgear.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.