Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071041R1 Emax 2 E2.2S 2000 fixed three-pole air circuit breaker with Ekip Dip LI electronic protection, 2000 A rated current and 85 kA breaking capacity at 400 V AC.
£7,016.29
The ABB E2.2S 2000 Ekip Dip LI 3p FHR, order code 1SDA071041R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in demanding low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, this fixed three-pole breaker combines a 2000 A rated current with an Ekip Dip LI electronic trip unit.
The Ekip Dip LI release provides long-time overload and instantaneous short-circuit protection, with settings made through DIP switches. This straightforward electronic protection platform provides dependable circuit protection while avoiding unnecessary complexity, making the breaker well suited to industrial switchboards, commercial distribution systems and infrastructure applications.
With a rated operational voltage of up to 690 V AC, the E2.2S 2000 provides an ultimate short-circuit breaking capacity of 85 kA at 400 V AC and 66 kA at 690 V AC. Its fixed three-pole configuration and rear horizontal terminals enable practical integration into high-current low-voltage switchboards and distribution assemblies.
Air circuit breakers such as the ABB SACE Emax 2 provide essential switching and fault protection at key points within low-voltage distribution networks. The E2.2S 2000 combines a high continuous-current capability with substantial short-circuit interruption performance, helping protect cables, busbars and connected equipment against damaging overload and fault currents.
The Ekip Dip LI electronic trip unit provides long-time overload and instantaneous short-circuit protection with adjustable thresholds configured through DIP switches. This makes the 1SDA071041R1 a practical solution for installations requiring reliable high-current protection without the additional short-time or earth-fault functions associated with LSI and LSIG releases.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA071041R1 |
| Product type | Air circuit breaker |
| Performance level | S |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Current type | AC |
| Number of poles | 3 |
| Installation | Fixed |
| Trip unit | Ekip Dip LI |
| Release type | Electronic |
| Protection functions | Long-time overload and instantaneous short circuit (LI) |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Earth-fault protection | No |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50 / 60 Hz |
| Ultimate short-circuit breaking capacity (Icu) at 380–440 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Main terminal position | Rear |
| Terminal orientation | Horizontal |
| Main circuit connection | Bolt connection |
| Auxiliary contacts | 4 change-over contacts |
| Motor operator | Optional |
| Protection rating | IP30 |
| Power loss | 212 W |
| Electrical durability | 10,000 cycles at ≤440 V AC; 8,000 cycles at 500–690 V AC |
| Mechanical durability | 25,000 cycles |
| Standard | IEC 60947-2 |
| EAN | 8015644748913 |
The ABB 1SDA071041R1 is an Emax 2 E2.2S fixed three-pole air circuit breaker rated at 2000 A and equipped with an Ekip Dip LI electronic trip unit.
The Ekip Dip LI release provides long-time overload and instantaneous short-circuit protection, with protection thresholds configured using DIP switches.
The E2.2S 2000 provides an ultimate short-circuit breaking capacity of 85 kA at 400 V AC and 66 kA at 690 V AC.
No. This model uses an LI protection configuration, providing long-time overload and instantaneous short-circuit protection without integrated earth-fault protection.
It is designed for high-current low-voltage distribution applications including industrial switchboards, main distribution panels, infrastructure systems, transformer distribution and OEM switchgear assemblies.
ABB SACE Emax 2 air circuit breakers combine dependable high-current switching, electronic fault protection and flexible switchboard integration for reliable low-voltage power distribution in industrial, commercial and infrastructure installations.