ABB 1SDA071039R1 Emax 2 E2.2N 2000 fixed three-pole air circuit breaker with horizontal rear terminals, Ekip Hi-Touch LSIG electronic protection, 2000 A rated uninterrupted current, 690 V AC operational voltage and 66 kA short-circuit breaking capacity.

SKU: 1SDA071039R1MPN: 1SDA071039R1
Price
List Price £13,175.00 ex VAT
Your Price (ex VAT) Save 25%
£9,881.25 25% OFF
You save £3,293.75 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,881.25
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,881.25

Why Choose the ABB E2.2N 2000 Ekip Hi-Touch LSIG 3p F HR Air Circuit Breaker?

The ABB 1SDA071039R1, designated E2.2N 2000 Ekip Hi-Touch LSIG 3p F HR, is a high-performance three-pole air circuit breaker (ACB) designed for advanced protection, measurement and control in demanding low-voltage power distribution systems. As part of the ABB SACE Emax 2 series, it combines a 2000 A rated uninterrupted current with the advanced Ekip Hi-Touch LSIG electronic trip unit.

The E2.2N configuration is suited to industrial, commercial, infrastructure and critical-power installations requiring high-current switching, selective protection and sophisticated electrical monitoring. Its Ekip Hi-Touch LSIG release provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, together with advanced measurement and Network Analyzer functionality.

With a rated operational voltage of 690 V AC, rated ultimate short-circuit breaking capacity of 66 kA and rated short-time withstand current of 66 kA for 1 s, the 1SDA071039R1 provides robust protection for high-current electrical networks. This version is a fixed, three-pole circuit breaker with horizontal rear terminals and is fitted with four auxiliary change-over contacts and circuit-breaker open/closed position indication.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding low-voltage distribution systems.
  • 2000 A rated uninterrupted current for high-current industrial, commercial and infrastructure applications.
  • 66 kA Icu across key AC operating voltages up to 690 V AC provides robust short-circuit interruption capability.
  • 66 kA short-time withstand current for 1 s supports selective protection strategies.
  • Ekip Hi-Touch LSIG electronic trip unit provides comprehensive overload, short-circuit and earth-fault protection.
  • Integrated earth-fault protection supports comprehensive distribution-system protection.
  • Ekip Measuring Pro and Network Analyzer functionality provide advanced electrical measurement and power-quality analysis.
  • Touch-sensitive interface provides convenient access to protection settings and operating information.
  • Supports compatible optional Ekip communication and signalling modules for integration with automation and power-management systems.
  • Fixed three-pole construction with horizontal rear terminals for permanent switchboard installation.

Key Features

  • ABB SACE Emax 2 E2.2N series.
  • 2000 A rated uninterrupted current (Iu).
  • Three-pole configuration.
  • 690 V AC rated operational voltage (Ue).
  • 1000 V AC rated insulation voltage (Ui).
  • 12 kV rated impulse withstand voltage (Uimp).
  • 66 kA rated ultimate short-circuit breaking capacity (Icu).
  • 66 kA rated service short-circuit breaking capacity (Ics).
  • Ics equal to 100% of Icu.
  • 66 kA rated short-time withstand current (Icw) for 1 s.
  • 50 kA rated short-time withstand current (Icw) for 3 s.
  • Ekip Hi-Touch LSIG electronic protection release.
  • Long-time overload (L) protection.
  • Short-time selective short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • Integrated earth-fault (G) protection.
  • Ekip Measuring Pro measurement functionality.
  • Integrated Network Analyzer functionality.
  • Four auxiliary change-over contacts.
  • Circuit-breaker open/closed position indication.

Advanced Selective and Earth-Fault Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E2.2N provide switching, isolation and protection for high-current low-voltage electrical systems. With a 2000 A rated uninterrupted current, 66 kA ultimate breaking capacity and 66 kA short-time withstand current for 1 s, this configuration is suited to main distribution, transformer secondary and feeder circuits where dependable fault interruption and selective coordination are required.

The Ekip Hi-Touch LSIG electronic trip unit combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection with advanced measurement capabilities. Integrated Ekip Measuring Pro and Network Analyzer functionality provides enhanced visibility of electrical-system performance and power quality, while the wider ABB Ekip platform supports compatible optional communication, signalling and power-management modules.

Typical Applications

  • Main low-voltage electrical distribution boards.
  • Industrial switchboards and switchgear assemblies.
  • Manufacturing and process plants.
  • Commercial building power distribution.
  • Data centres and critical power installations.
  • Infrastructure electrical systems.
  • Transformer secondary distribution.
  • High-current incoming and feeder protection.
  • Distribution systems requiring selective and earth-fault protection.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA071039R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker (ACB)
Frame E2.2N
Short-circuit performance level N
Rated uninterrupted current (Iu) 2000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 3
Installation Fixed
Terminal configuration Horizontal rear flat terminals
Main terminal connection Bolted
Trip unit Ekip Hi-Touch LSIG
Trip unit type Electronic solid-state protection release
Protection functions L, S, I, G
Overload protection adjustment 0.4–1 × In
Short-time selective protection adjustment 0.6–10 × In
Instantaneous short-circuit protection adjustment 1.5–15 × In
Earth-fault protection adjustment 0.1–1 × In
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 66 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw), 1 s 66 kA
Rated short-time withstand current (Icw), 3 s 50 kA
Integrated earth-fault protection Yes
Auxiliary change-over contacts 4
Position indication Circuit breaker open / closed
Motor operator Optional
Degree of protection IP30
Suitable for IT networks Yes, up to 690 V
Product dimensions (W × H × D) 276 × 371 × 270 mm
Product net weight 41 kg
EAN 8015644748890
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071039R1 used for?

The ABB 1SDA071039R1 is an Emax 2 air circuit breaker designed for switching, protecting and monitoring high-current low-voltage electrical distribution circuits in industrial, commercial, infrastructure and critical-power applications.

What is the current rating of the ABB E2.2N 2000?

The circuit breaker has a rated uninterrupted current of 2000 A, making it suitable for high-current low-voltage distribution applications.

What protection does the Ekip Hi-Touch LSIG trip unit provide?

The Ekip Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, together with advanced measurement and monitoring functionality.

What are the short-circuit ratings of the ABB 1SDA071039R1?

The E2.2N 2000 has a rated ultimate short-circuit breaking capacity of 66 kA at key operating voltages up to 690 V AC, together with a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.

What terminal configuration does the ABB 1SDA071039R1 use?

This version is a fixed three-pole air circuit breaker with horizontal rear flat terminals, designed for permanent installation within a suitable low-voltage switchboard or switchgear assembly.

Trusted Low-Voltage Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance with advanced electronic protection, measurement, power-quality analysis and expandable connectivity capabilities to provide dependable protection and intelligent power management for demanding low-voltage electrical distribution systems.