ABB 1SDA071028R1 Emax 2 E2.2B 2000 A three-pole fixed air circuit breaker with rear horizontal terminals, Ekip Hi-Touch LSI electronic protection and 42 kA ultimate breaking capacity at 400 V AC for high-current low-voltage power distribution systems.
£8,931.14
The ABB E2.2B 2000 Ekip Hi-Touch LSI 3p F HR, order code 1SDA071028R1, is a high-current air circuit breaker (ACB) from the ABB SACE Emax 2 range, engineered for protection, switching and isolation in low-voltage electrical distribution systems. Rated at 2000 A, this three-pole fixed breaker combines the E2.2B frame with ABB's advanced Ekip Hi-Touch electronic protection platform.
The breaker incorporates an Ekip Hi-Touch LSI solid-state electronic release, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Adjustable protection settings enable coordination with cables, busbars, transformers and downstream protective devices, while the Hi-Touch platform provides advanced protection, measurement and power-management capabilities for sophisticated electrical networks.
The 3p F HR configuration identifies a three-pole fixed breaker with rear horizontal terminals. The E2.2B 2000 provides a rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC and is rated for operation up to 690 V AC, making the 1SDA071028R1 a robust solution for high-current main distribution and feeder applications.
Air circuit breakers such as the ABB SACE Emax 2 E2.2B provide switching, isolation and electronic protection for high-current low-voltage installations. The Ekip Hi-Touch platform combines configurable protection with advanced measurement and power-management functionality, supporting effective coordination and management of modern electrical distribution networks.
The Ekip Hi-Touch LSI release combines long-time, short-time delayed and instantaneous protection within a single electronic protection unit. Together with its 2000 A rated current, 42 kA ultimate breaking capacity at 400 V AC and 42 kA short-time withstand current for 1 s, the 1SDA071028R1 provides dependable protection for main switchboards, transformer distribution circuits and high-current feeders.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2B |
| ABB order code | 1SDA071028R1 |
| Product type | Air circuit breaker (ACB) |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Frequency | 50/60 Hz |
| Rated ultimate short-circuit breaking capacity at 400 V AC | 42 kA |
| Rated short-time withstand current | 42 kA for 1 s |
| Number of poles | 3 |
| Protection trip unit | Ekip Hi-Touch LSI |
| Release technology | Solid-state electronic release |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload release adjustment range | 800–2000 A |
| Short-time delayed short-circuit release adjustment range | 1200–20000 A |
| Instantaneous short-circuit release adjustment range | 3000–30000 A |
| Integrated ground-fault protection | No |
| Current type | AC |
| Installation | Fixed |
| Main-circuit terminals | Rear horizontal (HR) |
| Main-circuit connection | Bolt connection |
| Connecting capacity | 1800 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Open/closed position indication | Yes |
| Integrated undervoltage release | No |
| Integrated motor drive | No |
| Motor drive | Optional |
| Electrical durability at ≤440 V | 10,000 operating cycles |
| Electrical durability at 500–690 V | 8,000 operating cycles |
| Mechanical durability | 25,000 operating cycles |
| Power loss | 212 W |
| Dimensions (W × H × D) | 276 × 371 × 270 mm |
| Net weight | 41 kg |
| EAN | 8015644748784 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071028R1 is a SACE Emax 2 E2.2B 2000 Ekip Hi-Touch LSI 3p F HR air circuit breaker rated at 2000 A, with three-pole fixed construction, rear horizontal terminals and an Ekip Hi-Touch LSI electronic release.
The breaker has a rated current of 2000 A, making it suitable for high-current low-voltage electrical distribution applications.
The Ekip Hi-Touch LSI release provides long-time overload protection (L), short-time delayed short-circuit protection (S) and instantaneous short-circuit protection (I).
The E2.2B 2000 provides a rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC, together with a rated short-time withstand current of 42 kA for 1 s.
No. This configuration uses an Ekip Hi-Touch LSI release providing long-time, short-time and instantaneous protection; integrated ground-fault protection is not included in the LSI configuration.
The F HR designation identifies a fixed-version breaker with rear horizontal terminals, providing a rear connection arrangement for integration into compatible low-voltage switchboards.
The 1SDA071028R1 is a fixed-version air circuit breaker, intended for permanent installation within a compatible low-voltage switchboard or distribution assembly.
ABB SACE Emax 2 air circuit breakers are engineered for reliable protection, switching and power management in low-voltage electrical distribution systems, supporting demanding industrial, commercial and infrastructure installations.