Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071023R1 E2.2B 2000 Ekip Dip LSIG 3p F HR is a fixed three-pole 2000 A SACE Emax 2 air circuit breaker with 42 kA breaking capacity and adjustable LSIG electronic protection including earth-fault protection.
£6,680.09
The ABB E2.2B 2000 Ekip Dip LSIG 3p F HR, order code 1SDA071023R1, is a high-performance air circuit breaker (ACB) designed for protection, control and isolation in low-voltage electrical distribution systems. As part of the advanced ABB SACE Emax 2 series, this fixed three-pole circuit breaker combines a 2000 A current rating with the Ekip Dip LSIG solid-state electronic trip unit for comprehensive circuit protection.
The breaker incorporates LSIG protection functions, providing long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. The Ekip Dip electronic release provides adjustable protection settings for effective coordination within industrial and commercial distribution systems while maintaining a straightforward interface for configuration and operation.
With a rated uninterrupted current of 2000 A and an ultimate short-circuit breaking capacity of 42 kA across common low-voltage operating levels up to 690 V AC, the E2.2B 2000 is suitable for substantial electrical distribution systems. This version features a fixed three-pole construction with rear horizontal terminals, four auxiliary change-over contacts and circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical distribution systems against overloads, short circuits and earth faults while providing reliable switching and isolation. Their high current and fault-breaking capabilities make them particularly suitable for main distribution boards, industrial switchboards and other high-current electrical installations.
The Ekip Dip LSIG electronic trip unit combines long-time overload, short-time delayed, instantaneous short-circuit and ground-fault protection. These adjustable protection functions allow the breaker to protect conductors and downstream equipment while supporting selective coordination and dependable operation within properly engineered electrical distribution systems.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2B |
| ABB order code / MPN | 1SDA071023R1 |
| Product type | Air circuit breaker |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50 / 60 Hz |
| Ultimate short-circuit breaking capacity (Icu) | 42 kA at 380–415 V AC; 42 kA at 440 V AC; 42 kA at 500–525 V AC; 42 kA at 690 V AC |
| Service short-circuit breaking capacity (Ics) | 42 kA at 415 V AC |
| Short-time withstand current (Icw) | 42 kA for 1 s |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LSIG |
| Release type | Solid-state electronic |
| Protection functions | LSIG |
| Overload protection adjustment | 0.4–1 × In (800–2000 A) |
| Instantaneous short-circuit protection adjustment | 1.5–15 × In (3000–30000 A) |
| Earth-fault protection | Integrated |
| Earth-fault protection adjustment | 0.1–1 × In |
| Installation version | Fixed |
| Main terminal orientation | Rear horizontal |
| Main circuit connection | Bolt connection |
| Connecting capacity | 1800 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Open/closed position indication | Yes |
| Integrated undervoltage release | No |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Mechanical durability | 25,000 cycles |
| Electrical durability | 10,000 cycles at Ue ≤ 440 V; 8,000 cycles at Ue 500–690 V |
| Power loss | 212 W |
| Protection rating | IP30 |
| Weight | 41 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644748739 |
The ABB 1SDA071023R1 is an Emax 2 air circuit breaker designed to protect, control and isolate high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure installations.
This circuit breaker has a rated uninterrupted current of 2000 A.
The E2.2B version provides an ultimate short-circuit breaking capacity of 42 kA at 415 V AC, with a 42 kA rating also specified at 690 V AC.
The Ekip Dip LSIG trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The 1SDA071023R1 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals.
ABB SACE Emax 2 air circuit breakers are designed for reliable protection and control of low-voltage power distribution systems, combining high-current switching performance with advanced electronic protection for demanding industrial and commercial installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.