1SDA071020R1 ABB E2.2H 1600 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker

1SDA071020R1 ABB E2.2H 1600 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker

ABB 1SDA071020R1 Emax 2 E2.2H 1600 fixed three-pole air circuit breaker with horizontal rear terminals, Ekip G Hi-Touch LSIG electronic protection, 1600 A rated uninterrupted current, 690 V AC operational voltage and 100 kA breaking capacity at 380–440 V AC.

SKU: 1SDA071020R1MPN: 1SDA071020R1
Price
List Price £12,707.26 ex VAT
Your Price (ex VAT) Save 25%
£9,530.45 25% OFF
You save £3,176.82 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,530.45
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,530.45

Why Choose the ABB E2.2H 1600 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker?

The ABB 1SDA071020R1, designated E2.2H 1600 Ekip G Hi-Touch LSIG 3p F HR, is a high-performance three-pole air circuit breaker (ACB) designed for advanced protection, monitoring and control in demanding low-voltage power distribution and generator applications. As part of the ABB SACE Emax 2 series, it combines a 1600 A rated uninterrupted current with the sophisticated Ekip G Hi-Touch LSIG electronic trip unit.

The E2.2H is engineered for industrial, infrastructure, critical-power and generation installations where very high short-circuit performance and advanced generator-oriented protection are required. Its Ekip G Hi-Touch LSIG release provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, together with generator-specific protection, advanced measurement and power-quality analysis functionality.

With a rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 100 kA at 380–440 V AC, the 1SDA071020R1 provides robust protection for high-fault-level electrical networks. This version is a fixed, three-pole circuit breaker with horizontal rear terminals and is supplied with four auxiliary contacts and circuit-breaker open/closed position indication.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding distribution and generator systems.
  • 1600 A rated uninterrupted current for high-current industrial and infrastructure installations.
  • 100 kA Icu at 380–440 V AC provides exceptional short-circuit interruption capability.
  • 85 kA Icu at 500–690 V AC supports demanding higher-voltage low-voltage networks.
  • Ekip G Hi-Touch LSIG electronic trip unit combines comprehensive LSIG protection with generator-specific functionality.
  • Integrated advanced measurement and Network Analyzer functionality supports detailed electrical-system monitoring.
  • Touch-sensitive interface provides convenient access to protection settings and operating information.
  • Supports compatible optional Ekip communication and signalling modules for integration with automation and power-management systems.
  • Fixed three-pole construction with horizontal rear terminals for permanent switchboard installation.

Key Features

  • ABB SACE Emax 2 E2.2H series.
  • 1600 A rated uninterrupted current (Iu).
  • Three-pole configuration.
  • 690 V AC rated operational voltage (Ue).
  • 1000 V AC rated insulation voltage (Ui).
  • 50/60 Hz operating frequency.
  • 100 kA rated ultimate short-circuit breaking capacity (Icu) at 380–440 V AC.
  • 85 kA rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC.
  • 85 kA rated short-time withstand current (Icw) for 1 s.
  • Ekip G Hi-Touch LSIG electronic protection release.
  • Long-time overload (L) protection.
  • Short-time selective short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • Earth-fault (G) protection.
  • 640–1600 A overload protection setting range.
  • 960–16000 A short-time selective protection setting range.
  • 2400–24000 A instantaneous short-circuit protection setting range.
  • 160–1600 A earth-fault protection setting range.
  • Generator-specific protection functions.
  • Integrated advanced measurement and Network Analyzer functionality.
  • Four auxiliary contacts and open/closed position indication.

Advanced Generator and High-Fault-Level Power Protection

Air circuit breakers such as the ABB SACE Emax 2 E2.2H provide switching, isolation and protection for high-current low-voltage electrical systems. With a 1600 A current rating, 100 kA ultimate breaking capacity at 380–440 V AC and 85 kA short-time withstand current for 1 s, this high-performance configuration is particularly suited to electrical networks with substantial prospective fault currents and demanding selectivity requirements.

The Ekip G Hi-Touch LSIG electronic trip unit combines adjustable long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection with generator-specific functionality. Advanced measurement and Network Analyzer capabilities provide additional insight into electrical-system operation and power quality, while the modular Ekip architecture supports compatible communication and signalling options for integration into intelligent power-management and automation systems.

Typical Applications

  • Generator protection and generator switchboards.
  • Main low-voltage electrical distribution boards.
  • Industrial switchboards and switchgear assemblies.
  • Manufacturing and process plants.
  • Data centres and critical power infrastructure.
  • Commercial and infrastructure power distribution.
  • Transformer and generator distribution systems.
  • High-fault-level incoming and feeder protection.
  • Energy management and industrial automation systems.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA071020R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker (ACB)
Frame E2.2H
Performance level H
Rated uninterrupted current (Iu) 1600 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50/60 Hz
Number of poles 3
Installation Fixed
Terminal configuration Horizontal rear terminals
Trip unit Ekip G Hi-Touch LSIG
Trip unit type Solid-state electronic protection release
Protection functions L, S, I, G
Overload protection setting range 640–1600 A
Short-time selective protection setting range 960–16000 A
Instantaneous short-circuit protection setting range 2400–24000 A
Earth-fault protection setting range 160–1600 A
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 85 kA
Earth-fault protection Integrated
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Measurement Advanced Ekip measurement functionality
Power-quality analysis Network Analyzer
EAN 8015644748708
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071020R1 used for?

The ABB 1SDA071020R1 is an Emax 2 air circuit breaker designed for switching, protecting and monitoring high-current low-voltage power distribution and generator systems, particularly where high short-circuit performance is required.

What is the current rating of the ABB E2.2H 1600?

The circuit breaker has a rated uninterrupted current of 1600 A, with an adjustable long-time overload protection range of 640–1600 A.

What protection does the Ekip G Hi-Touch LSIG trip unit provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, together with generator-specific protection, advanced measurement and power-quality analysis functionality.

What is the breaking capacity of the ABB 1SDA071020R1?

The E2.2H 1600 has a rated ultimate short-circuit breaking capacity of 100 kA at 380–440 V AC and 85 kA at 500–690 V AC, with a rated short-time withstand current of 85 kA for 1 s.

What terminal configuration does the ABB 1SDA071020R1 use?

This version is a fixed three-pole air circuit breaker with horizontal rear terminals, designed for permanent installation within a suitable low-voltage switchboard or switchgear assembly.

Trusted Low-Voltage and Generator Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance with advanced electronic protection, generator-specific functionality, measurement and expandable connectivity capabilities to provide dependable protection and intelligent power management for demanding low-voltage electrical systems.