ABB 1SDA071019R1 Emax 2 E2.2H 1600 fixed three-pole air circuit breaker with Ekip Hi-Touch LSIG electronic protection, 1600 A rated current and 100 kA breaking capacity at 400 V AC.
£9,077.29
The ABB E2.2H 1600 Ekip Hi-Touch LSIG 3p FHR, order code 1SDA071019R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection, monitoring and control of demanding low-voltage AC power distribution systems. Part of the advanced ABB Emax 2 E2.2 series, this fixed three-pole breaker combines a 1600 A rated current with the sophisticated Ekip Hi-Touch electronic trip unit.
The breaker incorporates comprehensive LSIG protection functions, providing long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. The Ekip Hi-Touch electronic release supports advanced protection and monitoring functions, making this breaker well suited to industrial, commercial and infrastructure installations where dependable fault protection and power-system supervision are required.
With a rated operational voltage of up to 690 V AC and an ultimate short-circuit breaking capacity of 100 kA at 400 V AC, the E2.2H 1600 is engineered for systems with high prospective fault currents. This version has a fixed three-pole configuration with rear horizontal terminals and is supplied with four auxiliary change-over contacts for circuit-breaker open/closed position signalling.
Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical systems against abnormal current conditions while providing a dependable switching and isolation point within the distribution network. The E2.2H performance level provides substantial short-circuit interruption capability, making this breaker particularly suitable for switchboards where high prospective fault currents can occur.
The Ekip Hi-Touch LSIG trip unit extends protection beyond conventional overload and short-circuit functions by incorporating earth-fault protection. This combination enables comprehensive protection of conductors, equipment and distribution infrastructure while supporting selective coordination within sophisticated electrical networks.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA071019R1 |
| Product type | Air circuit breaker |
| Performance level | H |
| Rated current | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Current type | AC |
| Number of poles | 3 |
| Installation | Fixed |
| Trip unit | Ekip Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and earth fault (LSIG) |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 85 kA |
| Rated short-time withstand current (Icw), 3 s | 66 kA |
| Overload release setting range | 640–1600 A |
| Short-time short-circuit release adjustment range | 960–16000 A |
| Instantaneous short-circuit release adjustment range | 2400–24000 A |
| Main terminal position | Rear |
| Terminal orientation | Horizontal |
| Terminal connection type | Rear flat horizontal |
| Main terminal type | Bolt connection |
| Auxiliary contacts | 4 change-over contacts |
| Dimensions | 276 × 270 × 270 mm |
| EAN | 8015644748692 |
| Country of origin | Italy |
| Standard | IEC |
The ABB 1SDA071019R1 is an Emax 2 E2.2H fixed three-pole air circuit breaker rated at 1600 A and equipped with an Ekip Hi-Touch LSIG electronic trip unit.
The LSIG configuration provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection.
The E2.2H 1600 has an ultimate short-circuit breaking capacity of 100 kA at 400 V AC and 85 kA at 690 V AC.
This model is a fixed three-pole air circuit breaker with rear horizontal main terminals.
It is designed for high-current low-voltage distribution applications including industrial switchboards, main distribution panels, infrastructure systems, power distribution centres and OEM switchgear assemblies.
ABB SACE Emax 2 air circuit breakers combine high-performance fault interruption, advanced electronic protection and flexible system integration for dependable low-voltage power distribution in demanding industrial and commercial installations.