ABB 1SDA071011R1 Emax 2 E2.2H 1600 A three-pole fixed air circuit breaker with rear horizontal terminals, Ekip Dip LI electronic protection and 100 kA ultimate breaking capacity at 415 V AC for demanding low-voltage power distribution systems.
£5,423.02
The ABB E2.2H 1600 Ekip Dip LI 3p F HR, order code 1SDA071011R1, is a high-performance air circuit breaker (ACB) from the ABB SACE Emax 2 range, engineered for protection, switching and isolation in demanding low-voltage electrical distribution systems. Rated at 1600 A, this three-pole fixed breaker combines the high-breaking-capacity E2.2H frame with ABB's Ekip Dip electronic protection technology.
The breaker incorporates an Ekip Dip LI solid-state electronic release, providing long-time overload and instantaneous short-circuit protection. Its adjustable overload and instantaneous protection settings help safeguard cables, busbars, transformers and connected equipment while allowing the breaker to be configured for the requirements of the protected electrical network.
The 3p F HR configuration identifies a three-pole fixed breaker with rear horizontal terminals. With a rated ultimate short-circuit breaking capacity of 100 kA at 415 V AC and a rated operational voltage of 690 V AC, the 1SDA071011R1 is well suited to high-fault-level industrial, commercial and infrastructure power-distribution systems.
Air circuit breakers such as the ABB SACE Emax 2 E2.2H provide switching, isolation and electronic protection for high-current low-voltage installations. The Ekip Dip LI release monitors current and provides long-time overload and instantaneous short-circuit protection, helping protect electrical distribution equipment against sustained overcurrents and severe short-circuit faults.
With its 1600 A current rating, 100 kA ultimate breaking capacity at 415 V AC and adjustable LI protection, the 1SDA071011R1 provides a robust solution for high-fault-level main switchboards and distribution feeders. Its fixed three-pole construction and rear horizontal terminals make it particularly suitable for integration into permanent low-voltage switchgear assemblies.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2H |
| ABB order code | 1SDA071011R1 |
| Product type | Air circuit breaker (ACB) |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated impulse withstand voltage | 12 kV |
| Rated ultimate short-circuit breaking capacity at 415 V AC | 100 kA |
| Number of poles | 3 |
| Protection trip unit | Ekip Dip LI |
| Release technology | Solid-state electronic release |
| Protection functions | Long-time and instantaneous (LI) |
| Overload release adjustment range | 640–1600 A |
| Instantaneous short-circuit release adjustment range | 2400–24000 A |
| Short-time delayed short-circuit protection | No |
| Integrated ground-fault protection | No |
| Current type | AC |
| Installation | Fixed |
| Main-circuit terminal position | Rear |
| Terminal orientation | Horizontal (HR) |
| Connecting capacity | 1200 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Open/closed position indication | Yes |
| Integrated undervoltage release | No |
| Integrated motor drive | No |
| Motor drive | Optional |
| Electrical durability at ≤440 V | 12,000 operating cycles |
| Electrical durability at 500–690 V | 10,000 operating cycles |
| Mechanical durability | 25,000 operating cycles |
| Power loss | 136 W |
| Dimensions (W × H × D) | 276 × 371 × 270 mm |
| Net weight | 41 kg |
| EAN | 8015644748616 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071011R1 is a SACE Emax 2 E2.2H 1600 Ekip Dip LI 3p F HR air circuit breaker rated at 1600 A, with three-pole fixed construction, rear horizontal terminals and an Ekip Dip LI electronic release.
The breaker has a rated current of 1600 A, making it suitable for high-current low-voltage electrical distribution applications.
The Ekip Dip LI release provides long-time overload protection (L) and instantaneous short-circuit protection (I).
The E2.2H 1600 provides a rated ultimate short-circuit breaking capacity of 100 kA at 415 V AC, providing high fault-clearing capability for demanding low-voltage distribution systems.
No. This configuration uses an Ekip Dip LI release providing long-time overload and instantaneous short-circuit protection; integrated ground-fault protection is not included.
The F HR designation identifies a fixed-version breaker with rear horizontal terminals, providing a rear connection arrangement for integration into compatible low-voltage switchboards.
The 1SDA071011R1 is a fixed-version air circuit breaker, intended for permanent installation within a compatible low-voltage switchboard or distribution assembly.
ABB SACE Emax 2 air circuit breakers are engineered for reliable protection, switching and management of low-voltage electrical distribution systems, supporting demanding industrial, commercial and infrastructure installations.