ABB 1SDA071008R1 E2.2S 1600 Ekip Hi-Touch LSI three-pole fixed air circuit breaker with rear flat horizontal terminals, 1600 A rated current, 690 V AC rated operational voltage and 85 kA short-circuit breaking capacity at 400–440 V AC for advanced selective low-voltage power distribution protection.
£8,171.03
The ABB E2.2S 1600 Ekip Hi-Touch LSI 3p F HR, order code 1SDA071008R1, is a high-performance air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for switching, isolation and protection in demanding low-voltage power distribution systems. Its E2.2S frame provides a rated uninterrupted current of 1600 A and a rated operational voltage of 690 V AC, making it suitable for high-current industrial, commercial and infrastructure switchboards.
This model is equipped with an advanced Ekip Hi-Touch LSI electronic trip unit, providing long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The Hi-Touch platform combines sophisticated protection with enhanced measurement and monitoring capabilities, while short-time protection supports selective coordination between upstream and downstream protective devices.
The E2.2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC. The 1SDA071008R1 is a three-pole fixed circuit breaker with rear flat horizontal terminals, fitted with four auxiliary contacts and circuit-breaker open/closed position indication for integration into compatible low-voltage switchgear.
Air circuit breakers such as the ABB SACE Emax 2 E2.2S provide switching, isolation and protection for high-current low-voltage electrical networks. The E2.2S performance class combines a 1600 A current rating with 85 kA breaking capacity at 400–440 V AC and a 66 kA short-time withstand capability for 1 s, making it well suited to systems with substantial prospective fault currents.
The Ekip Hi-Touch LSI trip unit combines advanced electronic monitoring with three complementary protection functions. Long-time protection responds to sustained overloads, short-time protection permits controlled fault-clearing delays to improve selectivity with downstream devices, and instantaneous protection rapidly interrupts severe short circuits. This combination makes the 1SDA071008R1 particularly suitable for coordinated industrial and infrastructure distribution networks.
| Series | SACE Emax 2 |
|---|---|
| Frame / sub-type | E2.2S |
| Order code / MPN | 1SDA071008R1 |
| EAN / GTIN | 8015644748586 |
| Product type | Air circuit breaker (ACB) |
| Current type | AC |
| Rated current | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 85 kA at 400–440 V AC |
| Rated service short-circuit breaking capacity (Ics) | 85 kA at 400–440 V AC |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw) | 66 kA for 1 s |
| Number of poles | 3 |
| Protection release | Ekip Hi-Touch LSI |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time) and I (instantaneous) |
| Integrated ground-fault protection | No |
| Short-circuit performance level | S |
| Mounting configuration | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Terminal type | Bolt |
| Connecting capacity | 1200 mm² |
| Recommended terminal screw | M12 |
| Terminal tightening torque | 70 N·m |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Suitable for IT networks | Yes, up to 690 V |
| Power loss | 136 W |
| Electrical durability | 12,000 cycles at Ue ≤ 440 V AC |
| Mechanical durability | 25,000 cycles |
| Standard | IEC 60947-2 |
The ABB 1SDA071008R1 is an Emax 2 air circuit breaker designed for switching, isolation and protection of high-current low-voltage circuits, including main incomers, feeders, transformer secondary circuits and industrial power distribution systems.
The ABB E2.2S 1600 has a rated uninterrupted current of 1600 A and a rated operational voltage of 690 V AC.
The E2.2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC. Its rated short-time withstand current is 66 kA for 1 s and 50 kA for 3 s.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The short-time function supports selective coordination with downstream protective devices, while the Hi-Touch platform provides advanced measurement and monitoring capabilities.
The F HR configuration identifies this model as a fixed circuit breaker with rear horizontal terminals. ABB specifies rear flat horizontal terminals for the 1SDA071008R1, providing rear bolted connections for permanent installation within compatible low-voltage switchgear.
ABB SACE Emax 2 air circuit breakers are engineered for reliable switching, isolation and protection of modern low-voltage electrical systems, combining high short-circuit performance with advanced electronic protection, selective coordination and intelligent power monitoring capabilities.