1SDA071003R1 ABB E2.2S 1600 Ekip Dip LSIG 3p FHR Air Circuit Breaker

1SDA071003R1 ABB E2.2S 1600 Ekip Dip LSIG 3p FHR Air Circuit Breaker

ABB 1SDA071003R1 Emax 2 E2.2S 1600 air circuit breaker, a fixed three-pole 1600 A ACB with horizontal rear terminals, Ekip Dip LSIG electronic protection, 85 kA breaking capacity at 400–440 V AC and 66 kA short-time withstand capability.

SKU: 1SDA071003R1MPN: 1SDA071003R1
Price
List Price £7,912.81 ex VAT
Your Price (ex VAT) Save 25%
£5,934.61 25% OFF
You save £1,978.20 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,934.61
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,934.61

Why Choose the ABB E2.2S 1600 Ekip Dip LSIG 3p FHR Air Circuit Breaker?

The ABB E2.2S 1600 Ekip Dip LSIG 3p FHR, order code 1SDA071003R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in demanding low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, it combines a 1600 A current rating with the E2.2S short-circuit performance level and an Ekip Dip electronic trip unit.

This model is a fixed, three-pole circuit breaker with horizontal rear flat terminals equipped with an Ekip Dip LSIG solid-state electronic release. Its LSIG protection functions provide long-time overload, short-time delayed short-circuit, instantaneous short-circuit and integrated earth-fault protection, delivering comprehensive protection for cables, busbars, transformers and connected distribution equipment.

The E2.2S 1600 provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC, 66 kA at 500–690 V AC and a rated short-time withstand current of 66 kA for 1 s. Its combination of high fault performance, four auxiliary change-over contacts and horizontal rear connections makes the 1SDA071003R1 particularly suitable for industrial, infrastructure and high-capacity switchboard applications.

Key Advantages

  • High-performance ABB SACE Emax 2 E2.2S air circuit breaker.
  • 1600 A rated uninterrupted current for high-current low-voltage distribution.
  • Ekip Dip LSIG electronic trip unit provides comprehensive configurable protection.
  • LSIG functionality combines overload, short-time, instantaneous and earth-fault protection.
  • 85 kA Icu at 400–440 V AC provides substantial short-circuit interruption capability.
  • 66 kA Icw for 1 s supports selective coordination in demanding distribution networks.
  • Ics equal to 100% of Icu provides strong service short-circuit performance.
  • Fixed three-pole construction with horizontal rear terminals facilitates switchboard busbar integration.
  • Four auxiliary change-over contacts support status signalling, monitoring and control.

Key Features

  • ABB SACE Emax 2 E2.2S series.
  • 1600 A rated uninterrupted current.
  • 690 V AC rated operational voltage.
  • Three-pole configuration.
  • Fixed circuit-breaker construction.
  • Rear flat horizontal terminals.
  • Ekip Dip LSIG solid-state electronic release.
  • Long-time L overload protection.
  • Short-time delayed S short-circuit protection.
  • Instantaneous I short-circuit protection.
  • Integrated G earth-fault protection.
  • 85 kA Icu at 400/415/440 V AC.
  • 66 kA Icu at 500/525/690 V AC.
  • 66 kA Icw for 1 s and 50 kA Icw for 3 s.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Four auxiliary change-over contacts.
  • Circuit-breaker open/closed position indication.
  • Suitable for IT networks up to 690 V.

High-Performance Selective and Earth-Fault Protection

Air circuit breakers such as the ABB Emax 2 E2.2S protect low-voltage electrical networks by interrupting current when hazardous overload, short-circuit or earth-fault conditions occur. The Ekip Dip LSIG electronic release combines long-time, short-time delayed, instantaneous and earth-fault functions, enabling comprehensive circuit protection while supporting selective coordination with other protective devices throughout the distribution network.

The E2.2S performance class combines 85 kA Icu at 400–440 V AC with a 66 kA 1-second short-time withstand rating. Its fixed construction and horizontal rear terminals facilitate direct busbar integration, while the 1600 A rating, integrated earth-fault protection, auxiliary contacts and optional motor drive make the 1SDA071003R1 a robust solution for main incomers and high-current feeders.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Main incomer and high-current feeder protection.
  • Selective electrical distribution systems.
  • Applications requiring integrated earth-fault protection.
  • Installations with high prospective short-circuit currents.
  • Transformer secondary distribution switchboards.
  • Manufacturing and process plant switchgear.
  • Commercial and critical infrastructure power distribution.
  • IT network distribution systems up to 690 V.
  • OEM switchboards requiring horizontal rear busbar connections.

Technical Specifications

Series SACE Emax 2 E2.2
ABB order code 1SDA071003R1
EAN 8015644748531
Product type Air circuit breaker
Frame / performance class E2.2S
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Current type AC
Number of poles 3
Version Fixed
Terminal arrangement Rear flat horizontal
Main-circuit connection Bolt connection
Trip unit Ekip Dip LSIG
Release type Electronic (EL)
Protection functions L (long-time overload), S (short-time short circuit), I (instantaneous short circuit), G (earth fault)
Integrated earth-fault protection Yes
Overload release adjustment range 640–1600 A
Short-time delayed short-circuit adjustment range 960–16000 A
Instantaneous short-circuit adjustment range 2400–24000 A
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 66 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw), 1 s 66 kA
Rated short-time withstand current (Icw), 3 s 50 kA
Connecting capacity 1200 mm²
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Control element Push button
Complete device with protection unit Yes
Integrated motor drive No
Optional motor drive Yes
Integrated undervoltage release No
DIN rail mounting No
Degree of protection IP30
Electrical durability at Ue ≤ 440 V 12000 cycles
Electrical durability at 500–690 V 10000 cycles
Electrical operating frequency 30 cycles per hour
Mechanical durability 25000 cycles
Mechanical operating frequency 60 cycles per hour
Power loss 136 W
Product dimensions (W × H × D) 276 × 371 × 270 mm
Net weight 45 kg
Suitable for IT networks Yes, up to 690 V
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071003R1 used for?

The ABB 1SDA071003R1 is an Emax 2 E2.2S air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, particularly systems requiring substantial short-circuit performance and integrated earth-fault protection.

What are the rated current and voltage of the E2.2S 1600 Ekip Dip LSIG?

The circuit breaker has a rated uninterrupted current of 1600 A and a rated operational voltage of up to 690 V AC.

What protection does the Ekip Dip LSIG trip unit provide?

The Ekip Dip LSIG electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and integrated earth-fault (G) protection.

What is the short-circuit performance of the ABB E2.2S 1600?

The E2.2S 1600 provides 85 kA Icu at 400/415/440 V AC and 66 kA Icu at 500/525/690 V AC. Its rated short-time withstand current is 66 kA for 1 s.

What does FHR mean on the ABB 1SDA071003R1?

The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with busbars inside low-voltage switchboards.

Trusted ABB Protection for Demanding Power Systems

ABB SACE Emax 2 air circuit breakers combine configurable electronic protection, high short-circuit performance and flexible switchboard integration to provide dependable overcurrent and earth-fault protection for demanding low-voltage power distribution systems.