ABB 1SDA070988R1 Emax 2 E2.2B 1600 fixed three-pole air circuit breaker with rear horizontal terminals, a 1600 A rated uninterrupted current, Ekip Hi-Touch LSI electronic trip unit, 42 kA ultimate short-circuit breaking capacity at 440 V AC and 42 kA short-time withstand current for 1 s.
£7,337.84
The ABB E2.2B 1600 Ekip Hi-Touch LSI 3p FHR, order code 1SDA070988R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for switching, protection and advanced supervision in low-voltage electrical distribution systems. Part of the ABB Emax 2 E2.2 series, this fixed three-pole circuit breaker combines a 1600 A rated uninterrupted current with an Ekip Hi-Touch LSI electronic trip unit and rear horizontal terminals.
The Ekip Hi-Touch LSI electronic release provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. Its advanced protection and monitoring capabilities make this configuration particularly suitable for distribution systems where accurate protection settings, selective coordination and detailed supervision of electrical conditions are important.
The E2.2B 1600 provides a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s. Its fixed three-pole construction with rear horizontal terminals provides a practical connection arrangement for permanent integration into industrial, commercial and infrastructure switchboards.
The ABB SACE Emax 2 E2.2B is designed for high-current low-voltage distribution systems where dependable circuit protection and coordination are required. With a 1600 A current rating, 42 kA Icu at 440 V AC and 42 kA Icw for 1 s, the ABB 1SDA070988R1 is well suited to main distribution circuits, high-current feeders and switchboards serving substantial industrial and commercial loads.
The Ekip Hi-Touch LSI trip unit combines long-time overload, short-time selective and instantaneous short-circuit protection. Long-time protection safeguards conductors and equipment against sustained overloads, short-time protection supports selective coordination between protective devices, and instantaneous protection provides rapid interruption of severe short circuits. The LSI configuration does not include integrated earth-fault protection.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2B |
| Product ID / order code | 1SDA070988R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated voltage | 690 V AC |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Rear horizontal |
| Trip unit | Ekip Hi-Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | LSI |
| Overload release setting range | 640–1600 A |
| Short-time delayed short-circuit setting range | 960–16000 A |
| Instantaneous short-circuit setting range | 2400–24000 A |
| Integrated earth-fault protection | No |
| Rated ultimate short-circuit breaking capacity (Icu) | 42 kA at 440 V AC |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Auxiliary contacts | 4 change-over contacts |
| Breaker position indication | Open / closed |
| Integrated motor operator | No |
| Motor operator | Optional |
| EAN | 8015644748388 |
The ABB 1SDA070988R1 is an Emax 2 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution circuits, including main incomers, feeders and industrial or commercial distribution systems requiring advanced LSI protection.
The ABB E2.2B 1600 Ekip Hi-Touch LSI has a rated uninterrupted current of 1600 A, with its overload release adjustable from 640–1600 A.
The E2.2B 1600 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.
For the ABB 1SDA070988R1 configuration, FHR identifies a fixed air circuit breaker with rear horizontal terminals, providing a rear connection arrangement suitable for integration into compatible low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine dependable switching, robust short-circuit performance and advanced electronic protection, with Ekip Hi-Touch technology providing sophisticated protection and supervision capabilities for demanding industrial, commercial, infrastructure and critical low-voltage power distribution systems.