ABB 1SDA070987R1 Emax 2 E2.2B 1600 air circuit breaker, a fixed three-pole 1600 A ACB with horizontal rear terminals, Ekip G Touch LSIG generator-oriented electronic protection, 42 kA breaking capacity at 440 V AC and 42 kA short-time withstand capability.
£7,571.74
The ABB E2.2B 1600 Ekip G Touch LSIG 3p FHR, order code 1SDA070987R1, is a SACE Emax 2 air circuit breaker (ACB) designed for generator and low-voltage power distribution applications. Part of the ABB Emax 2 E2.2 series, it combines a 1600 A current rating with the E2.2B performance class and ABB's generator-oriented Ekip G Touch electronic protection platform.
This model is a fixed, three-pole circuit breaker with horizontal rear terminals and an Ekip G Touch LSIG solid-state electronic release. The LSIG functions provide long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, while the Ekip G platform is specifically suited to the protection and management requirements of generator-based electrical systems.
The E2.2B 1600 provides a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC together with a rated short-time withstand current of 42 kA for 1 s. Four auxiliary contacts and circuit-breaker open/closed position indication further support integration into generator switchboards, industrial distribution panels and control systems.
Generator circuits can present protection requirements that differ from conventional utility-fed distribution systems, particularly because available short-circuit current and operating conditions depend on generator characteristics. The Ekip G Touch LSIG platform combines ABB's generator-oriented functionality with long-time, short-time, instantaneous and earth-fault protection to support dependable generator and distribution-system protection.
The E2.2B frame provides 42 kA ultimate short-circuit breaking capacity at 440 V AC and 42 kA short-time withstand capability for 1 s. Together with fixed construction, horizontal rear terminals and integrated auxiliary contacts, this makes the 1SDA070987R1 suitable for generator switchboards, main distribution assemblies and other high-current power-management applications.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070987R1 |
| EAN | 8015644748371 |
| Product type | Air circuit breaker |
| Frame / performance class | E2.2B |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational voltage | 690 V AC |
| Current type | AC |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Trip unit | Ekip G Touch LSIG |
| Release technology | Solid-state electronic |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit), G (earth fault) |
| Integrated earth-fault protection | Yes |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated short-time withstand current (Icw), 1 s | 42 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Dimensions | 276 × 371 × 270 mm |
| Net weight | 41 kg |
| Standard / approval | IEC |
The ABB 1SDA070987R1 is an Emax 2 E2.2B air circuit breaker designed for generator and low-voltage power distribution applications requiring electronic overload, short-circuit and earth-fault protection.
The circuit breaker has a rated uninterrupted current of 1600 A and is specified for low-voltage AC applications with a rated operational voltage of 690 V AC.
The Ekip G Touch LSIG electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, with the Ekip G platform designed for generator-oriented applications.
The E2.2B 1600 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.
The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, an arrangement designed for connection to switchboard busbars from the rear of the breaker.