Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070986R1 Emax 2 E2.2B 1600 air circuit breaker, a fixed three-pole 1600 A ACB with horizontal rear terminals and Ekip Touch LSIG electronic overload, short-circuit and earth-fault protection.
£5,174.53
The ABB E2.2B 1600 Ekip Touch LSIG 3p FHR, order code 1SDA070986R1, is a SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, this configuration combines a 1600 A current rating with the E2.2B performance class and ABB's advanced Ekip Touch electronic trip unit.
This model is a fixed, three-pole circuit breaker with horizontal rear terminals equipped with an Ekip Touch LSIG solid-state electronic release. Its LSIG protection functions provide long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, providing comprehensive protection for cables, busbars, transformers and downstream distribution equipment.
The E2.2B 1600 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s. Supplied with four auxiliary contacts and circuit-breaker open/closed position indication, the 1SDA070986R1 provides a practical solution for main distribution and feeder applications requiring electronic protection and rear busbar connections.
Air circuit breakers such as the ABB Emax 2 E2.2B protect low-voltage electrical networks by interrupting current when hazardous overload, short-circuit or earth-fault conditions occur. The Ekip Touch LSIG electronic release combines long-time, short-time delayed, instantaneous and earth-fault functions, allowing protection settings to be coordinated with other protective devices throughout the distribution network.
The E2.2B performance class provides 42 kA Icu at 440 V AC together with a 42 kA 1-second short-time withstand rating. Its fixed construction and horizontal rear terminals facilitate integration with switchboard busbars, while the 1600 A rating and integrated electronic protection make the 1SDA070986R1 suitable for main incomers and high-current feeder circuits.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070986R1 |
| EAN | 8015644748364 |
| Product type | Air circuit breaker |
| Frame / performance class | E2.2B |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational voltage (Ue) | 690 V AC |
| Current type | AC |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Horizontal rear terminals |
| Trip unit | Ekip Touch LSIG electronic release |
| Release technology | Solid-state electronic |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit), G (earth fault) |
| Integrated earth-fault protection | Yes |
| Long-time protection adjustment | 0.4–1 × In |
| Short-time protection adjustment | 0.6–10 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated short-time withstand current (Icw), 1 s | 42 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Net weight | 41 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA070986R1 is an Emax 2 E2.2B air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, including main incomers and feeders requiring electronic overcurrent and earth-fault protection.
The circuit breaker has a rated uninterrupted current of 1600 A and is designed for low-voltage AC power-distribution applications with an operational voltage up to 690 V AC.
The Ekip Touch LSIG electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and integrated earth-fault (G) protection.
The E2.2B 1600 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.
The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with busbars inside low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine configurable electronic protection, proven short-circuit performance and flexible switchboard integration to provide dependable protection and selective control for modern low-voltage power distribution systems.
We use cookies