1SDA070986R1 ABB E2.2B 1600 Ekip Touch LSIG 3p FHR Air Circuit Breaker

1SDA070986R1 ABB E2.2B 1600 Ekip Touch LSIG 3p FHR Air Circuit Breaker

ABB 1SDA070986R1 Emax 2 E2.2B 1600 air circuit breaker, a fixed three-pole 1600 A ACB with horizontal rear terminals and Ekip Touch LSIG electronic overload, short-circuit and earth-fault protection.

SKU: 1SDA070986R1MPN: 1SDA070986R1
Price
List Price £6,899.37 ex VAT
Your Price (ex VAT) Save 25%
£5,174.53 25% OFF
You save £1,724.84 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,174.53
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,174.53

Why Choose the ABB E2.2B 1600 Ekip Touch LSIG 3p FHR Air Circuit Breaker?

The ABB E2.2B 1600 Ekip Touch LSIG 3p FHR, order code 1SDA070986R1, is a SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, this configuration combines a 1600 A current rating with the E2.2B performance class and ABB's advanced Ekip Touch electronic trip unit.

This model is a fixed, three-pole circuit breaker with horizontal rear terminals equipped with an Ekip Touch LSIG solid-state electronic release. Its LSIG protection functions provide long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, providing comprehensive protection for cables, busbars, transformers and downstream distribution equipment.

The E2.2B 1600 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s. Supplied with four auxiliary contacts and circuit-breaker open/closed position indication, the 1SDA070986R1 provides a practical solution for main distribution and feeder applications requiring electronic protection and rear busbar connections.

Key Advantages

  • ABB SACE Emax 2 E2.2B air circuit breaker for low-voltage power distribution.
  • 1600 A rated uninterrupted current for substantial distribution loads.
  • Ekip Touch LSIG electronic trip unit provides advanced configurable protection.
  • LSIG functionality combines overload, short-time, instantaneous and earth-fault protection.
  • 42 kA Icu at 440 V AC provides robust short-circuit interruption.
  • 42 kA Icw for 1 s supports selective coordination in distribution networks.
  • Fixed three-pole construction with horizontal rear terminals facilitates switchboard busbar integration.
  • Four auxiliary contacts and open/closed indication support monitoring, signalling and control.

Key Features

  • ABB SACE Emax 2 E2.2B series.
  • 1600 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed circuit-breaker construction.
  • Horizontal rear terminals.
  • Ekip Touch LSIG solid-state electronic release.
  • Long-time L overload protection.
  • Short-time delayed S short-circuit protection.
  • Instantaneous I short-circuit protection.
  • Integrated G earth-fault protection.
  • 42 kA rated ultimate short-circuit breaking capacity at 440 V AC.
  • 42 kA rated short-time withstand current for 1 s.
  • Four auxiliary contacts.
  • Circuit-breaker open/closed position indication.
  • Designed to IEC requirements for low-voltage circuit-breaker applications.

Advanced Overcurrent and Earth-Fault Protection for Distribution Systems

Air circuit breakers such as the ABB Emax 2 E2.2B protect low-voltage electrical networks by interrupting current when hazardous overload, short-circuit or earth-fault conditions occur. The Ekip Touch LSIG electronic release combines long-time, short-time delayed, instantaneous and earth-fault functions, allowing protection settings to be coordinated with other protective devices throughout the distribution network.

The E2.2B performance class provides 42 kA Icu at 440 V AC together with a 42 kA 1-second short-time withstand rating. Its fixed construction and horizontal rear terminals facilitate integration with switchboard busbars, while the 1600 A rating and integrated electronic protection make the 1SDA070986R1 suitable for main incomers and high-current feeder circuits.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Main incomer and high-current feeder protection.
  • Selective electrical distribution systems.
  • Applications requiring integrated earth-fault protection.
  • Transformer secondary distribution switchboards.
  • Manufacturing and process plant switchgear.
  • Commercial building power distribution.
  • Infrastructure electrical distribution systems.
  • OEM switchboards requiring horizontal rear busbar connections.

Technical Specifications

Series SACE Emax 2 E2.2
ABB order code 1SDA070986R1
EAN 8015644748364
Product type Air circuit breaker
Frame / performance class E2.2B
Rated uninterrupted current (Iu) 1600 A
Rated operational voltage (Ue) 690 V AC
Current type AC
Number of poles 3
Version Fixed
Terminal arrangement Horizontal rear terminals
Trip unit Ekip Touch LSIG electronic release
Release technology Solid-state electronic
Protection functions L (long-time overload), S (short-time short circuit), I (instantaneous short circuit), G (earth fault)
Integrated earth-fault protection Yes
Long-time protection adjustment 0.4–1 × In
Short-time protection adjustment 0.6–10 × In
Instantaneous protection adjustment 1.5–15 × In
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 42 kA
Rated short-time withstand current (Icw), 1 s 42 kA
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Net weight 41 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA070986R1 used for?

The ABB 1SDA070986R1 is an Emax 2 E2.2B air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, including main incomers and feeders requiring electronic overcurrent and earth-fault protection.

What is the rated current of the E2.2B 1600 Ekip Touch LSIG?

The circuit breaker has a rated uninterrupted current of 1600 A and is designed for low-voltage AC power-distribution applications with an operational voltage up to 690 V AC.

What protection does the Ekip Touch LSIG trip unit provide?

The Ekip Touch LSIG electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and integrated earth-fault (G) protection.

What is the short-circuit performance of the ABB E2.2B 1600?

The E2.2B 1600 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.

What does FHR mean on the ABB 1SDA070986R1?

The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with busbars inside low-voltage switchboards.

Trusted ABB Protection for Low-Voltage Power Systems

ABB SACE Emax 2 air circuit breakers combine configurable electronic protection, proven short-circuit performance and flexible switchboard integration to provide dependable protection and selective control for modern low-voltage power distribution systems.