Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070984R1 E2.2B 1600 Ekip Touch LI three-pole fixed SACE Emax 2 air circuit breaker rated at 1600 A with electronic long-time overload and instantaneous short-circuit protection.
£4,370.57
The ABB E2.2B 1600 Ekip Touch LI 3P, order code 1SDA070984R1, is a SACE Emax 2 air circuit breaker (ACB) designed for reliable protection and switching in low-voltage electrical distribution systems. This fixed three-pole E2.2B breaker combines a rated current of 1600 A with ABB's Ekip Touch LI solid-state electronic trip unit.
The Ekip Touch LI release provides long-time overload and instantaneous short-circuit protection. Its electronic protection architecture and touch interface allow accurate configuration of protection settings, helping safeguard cables, busbars, transformers and connected equipment against sustained overloads and severe short-circuit faults.
The E2.2B performance level provides an ultimate short-circuit breaking capacity of 42 kA at 415 V AC and 42 kA at 690 V AC. This configuration is a fixed three-pole breaker with rear horizontal terminals and is supplied with four auxiliary contacts plus circuit-breaker open/closed position indication.
ABB SACE Emax 2 air circuit breakers combine switching capability with electronic circuit protection for modern low-voltage electrical networks. The E2.2B 1600 is suitable for main distribution boards, transformer-fed systems and high-current feeders where dependable overload and short-circuit protection is required.
The Ekip Touch LI release combines long-time overload protection with instantaneous short-circuit protection. Long-time protection responds to sustained overcurrent conditions, while the instantaneous function provides rapid interruption of severe short circuits, helping reduce thermal and electrodynamic stress on conductors and connected equipment.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070984R1 |
| EAN | 8015644748340 |
| Product type | Air circuit breaker (ACB) |
| Performance level | B |
| Rated current | 1600 A |
| Rated operational voltage | up to 690 V AC |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Touch LI |
| Release type | Solid-state electronic |
| Protection functions | LI (Long-time, Instantaneous) |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Mounting | Fixed |
| Main terminals | Rear horizontal |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Net weight | approximately 46 kg |
| Standard | IEC |
The ABB 1SDA070984R1 is an Emax 2 air circuit breaker designed for switching and protecting low-voltage electrical distribution circuits against overload and short-circuit conditions.
The circuit breaker has a rated current of 1600 A.
The Ekip Touch LI electronic trip unit provides long-time overload and instantaneous short-circuit protection.
The E2.2B 1600 provides an ultimate short-circuit breaking capacity of 42 kA at 415 V AC and 42 kA at 690 V AC.
This fixed three-pole circuit breaker uses rear horizontal terminals for integration with low-voltage switchboard and busbar systems.
ABB SACE Emax 2 air circuit breakers combine dependable switching, electronic protection and flexible switchboard integration to safeguard industrial, commercial and infrastructure low-voltage power distribution systems.