ABB E2.2B 1600 Ekip Dip LSI 3p FHR air circuit breaker with 1600 A rated current and adjustable LSI electronic protection for low voltage power distribution systems.
£4,604.44
The ABB E2.2B 1600 Ekip Dip LSI 3p FHR is a robust low voltage air circuit breaker (ACB) designed for reliable switching and protection in industrial, commercial and infrastructure power distribution systems. As part of the advanced ABB SACE Emax 2 air circuit breaker series, it provides dependable circuit interruption performance with flexible electronic protection settings. :chatgpt-content-reference{index="0"}
This fixed three-pole circuit breaker is equipped with the Ekip Dip LSI electronic trip unit, providing accurate long-time overload, short-time short-circuit and instantaneous protection functions. The Emax 2 platform combines high electrical performance with compact switchgear integration, helping engineers achieve reliable protection coordination in modern low voltage installations. :chatgpt-content-reference{index="1"}
With a rated current of 1600 A, a three-pole fixed configuration and rear horizontal terminal connection, the E2.2B 1600 Ekip Dip LSI 3p FHR is suitable for main distribution boards, industrial switchgear assemblies and electrical systems requiring dependable high-capacity protection. :chatgpt-content-reference{index="2"}
Air circuit breakers such as the ABB E2.2B 1600 Ekip Dip LSI protect electrical infrastructure by automatically disconnecting circuits during overload and short-circuit conditions, helping safeguard switchgear, cables and connected equipment.
The Emax 2 platform delivers reliable protection, flexible configuration and efficient integration into modern electrical distribution systems. The Ekip Dip LSI release allows engineers to set protection parameters for improved selectivity and system reliability.
| Product family | SACE Emax 2 |
|---|---|
| Product type | Air Circuit Breaker |
| Order code | 1SDA070982R1 |
| Rated current | 1600 A |
| Number of poles | 3 poles |
| Release type | Ekip Dip LSI electronic trip unit |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Short-circuit performance level | B |
| Ultimate short-circuit breaking capacity | 42 kA |
| Rated service short-circuit breaking capacity | 42 kA |
| Short-time withstand current | 42 kA for 1 s / 42 kA for 3 s |
| Terminal connection | Rear flat horizontal |
| Mounting type | Fixed installation |
| Mechanical durability | 25,000 cycles |
| Electrical durability | 12,000 cycles at ≤440 V AC and 10,000 cycles at 500–690 V AC |
| Power loss | 136 W |
| Terminal tightening torque | 70 N·m |
This air circuit breaker is used for protecting and switching low voltage electrical distribution systems in industrial, commercial and infrastructure applications.
The ABB E2.2B 1600 Ekip Dip LSI 3p FHR has a rated current of 1600 A.
The integrated Ekip Dip LSI trip unit provides long-time overload, short-time short-circuit and instantaneous protection functions.
This model is a three-pole (3P) fixed air circuit breaker.
The breaker is typically installed inside low voltage switchboards and electrical distribution assemblies.
ABB Emax 2 air circuit breakers are widely selected by electrical engineers and system integrators for dependable protection, efficient switching and reliable operation in modern power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.