Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070976R1 Emax 2 E2.2H 1250 fixed three-pole air circuit breaker with horizontal rear terminals, Ekip Touch LSIG electronic protection, 1250 A rated uninterrupted current, 690 V AC operational voltage and 100 kA breaking capacity at 400–440 V AC.
£6,095.38
The ABB 1SDA070976R1, designated E2.2H 1250 Ekip Touch LSIG 3p F HR, is a high-performance three-pole air circuit breaker (ACB) designed for advanced switching, protection and monitoring in demanding low-voltage power distribution systems. As part of the ABB SACE Emax 2 series, it combines a 1250 A rated uninterrupted current with the Ekip Touch LSIG electronic trip unit for comprehensive overload, short-circuit and earth-fault protection.
The E2.2H is engineered for industrial, commercial, infrastructure and critical-power installations where very high breaking performance, selectivity and advanced electronic protection are required. Its Ekip Touch LSIG release provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, while the Ekip Touch interface provides convenient access to protection settings, measurements and operating information.
With a rated uninterrupted current of 1250 A, rated operational voltage up to 690 V AC and rated ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC, the 1SDA070976R1 provides robust protection for high-fault-level electrical networks. This version is a fixed, three-pole circuit breaker with horizontal rear terminals, making it suitable for permanent integration into low-voltage switchboards and switchgear assemblies.
Air circuit breakers such as the ABB SACE Emax 2 E2.2H provide switching, isolation and protection for high-current low-voltage electrical systems. The high-performance E2.2H frame is particularly suited to installations with substantial prospective fault currents, providing up to 100 kA short-circuit breaking capacity at 400–440 V AC while supporting selective coordination across complex electrical distribution networks.
The Ekip Touch LSIG electronic trip unit combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection with advanced configuration and monitoring capabilities. Adjustable protection thresholds allow the breaker to be coordinated with the requirements of the electrical installation, while the modular ABB Ekip platform supports compatible communication, signalling and power-management functionality.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA070976R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker (ACB) |
| Frame | E2.2H |
| Performance level | H |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Number of poles | 3 |
| Installation | Fixed |
| Terminal configuration | Horizontal rear terminals |
| Trip unit | Ekip Touch LSIG |
| Trip unit type | Electronic protection release |
| Protection functions | L, S, I, G |
| Long-time overload protection setting range | 500–1250 A |
| Short-time selective protection setting range | 750–12500 A |
| Instantaneous short-circuit protection setting range | 1875–18750 A |
| Earth-fault protection setting range | 125–1250 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Earth-fault protection | Integrated |
| Standard | IEC 60947-2 |
The ABB 1SDA070976R1 is an Emax 2 air circuit breaker designed for switching, protecting and monitoring high-current low-voltage electrical distribution systems against overloads, short circuits and earth faults.
The circuit breaker has a rated uninterrupted current of 1250 A, with a long-time overload protection setting range of 500–1250 A.
The Ekip Touch LSIG electronic trip unit provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, together with advanced configuration, measurement and monitoring capabilities.
The E2.2H 1250 has a rated ultimate short-circuit breaking capacity (Icu) of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC.
This version is a fixed three-pole air circuit breaker with horizontal rear terminals, designed for permanent installation within a suitable low-voltage switchboard or switchgear assembly.
ABB SACE Emax 2 air circuit breakers combine high short-circuit breaking performance, advanced electronic protection, measurement and expandable connectivity capabilities to provide dependable protection and intelligent power management for demanding low-voltage electrical distribution systems.