ABB 1SDA070973R1 Emax 2 E2.2H 1250 air circuit breaker, a fixed three-pole 1250 A ACB with horizontal rear terminals and Ekip Dip LSIG electronic overload, short-circuit and earth-fault protection.
£6,007.70
The ABB E2.2H 1250 Ekip Dip LSIG 3p FHR, order code 1SDA070973R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in demanding low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, it combines a 1250 A rating with the high-breaking-capacity E2.2H performance class and an Ekip Dip electronic trip unit.
This model is a fixed, three-pole circuit breaker with horizontal rear terminals equipped with an Ekip Dip LSIG solid-state electronic release. Its LSIG protection functions provide long-time overload, short-time delayed short-circuit, instantaneous short-circuit and integrated earth-fault protection, enabling comprehensive protection of cables, busbars, transformers and connected distribution equipment.
The E2.2H 1250 provides a rated ultimate short-circuit breaking capacity of 100 kA at 415 V AC and 85 kA at 690 V AC. Combined with its 1250 A rating, four auxiliary contacts, trip signalling and horizontal rear connections, the 1SDA070973R1 is particularly well suited to critical industrial, infrastructure and high-capacity switchboard applications.
Air circuit breakers such as the ABB Emax 2 E2.2H protect low-voltage electrical networks by interrupting current when hazardous overload, short-circuit or earth-fault conditions occur. The Ekip Dip LSIG electronic release combines long-time, short-time delayed, instantaneous and earth-fault protection functions, allowing the breaker to provide comprehensive protection while supporting selective coordination with other devices throughout the distribution system.
The E2.2H performance class is engineered for installations with substantial prospective fault currents, delivering 100 kA Icu at 415 V AC and 85 kA Icu at 690 V AC. Horizontal rear terminals facilitate switchboard busbar connections, while the fixed construction, auxiliary contacts and status signalling make the 1SDA070973R1 a robust solution for main incomers and high-current feeders.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070973R1 |
| EAN | 8015644748234 |
| Product type | Air circuit breaker |
| Frame / performance class | E2.2H |
| Rated current | 1250 A |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Horizontal rear terminals |
| Trip unit | Ekip Dip LSIG electronic release |
| Release technology | Solid-state electronic |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit), G (earth fault) |
| Integrated earth-fault protection | Yes |
| Overload release setting | 500–1250 A |
| Instantaneous short-circuit setting | 1875–18750 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Auxiliary contacts | 4 |
| Trip signalling contact | Yes |
| Position indication | Circuit breaker open / closed |
| Current type | AC |
| Standard | IEC |
The ABB 1SDA070973R1 is an Emax 2 E2.2H air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, particularly systems requiring high short-circuit performance and integrated earth-fault protection.
The ABB E2.2H 1250 Ekip Dip LSIG is rated at 1250 A, making it suitable for substantial main incomer and feeder duties in low-voltage distribution systems.
The Ekip Dip LSIG electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and integrated earth-fault (G) protection.
The E2.2H 1250 provides a rated ultimate short-circuit breaking capacity of 100 kA at 415 V AC and 85 kA at 690 V AC, making it suitable for demanding high-fault-current distribution systems.
The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with busbars inside low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high short-circuit performance and flexible switchboard integration to provide dependable protection and selective control for demanding low-voltage power distribution systems.