1SDA070960R1 ABB E2.2N 1250 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker 1250 A

1SDA070960R1 ABB E2.2N 1250 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker 1250 A

ABB 1SDA070960R1 E2.2N 1250 Ekip G Hi-Touch LSIG three-pole fixed air circuit breaker with rear horizontal terminals, 1250 A rated current and 66 kA short-circuit breaking capacity for advanced generator and low-voltage power distribution protection.

SKU: 1SDA070960R1MPN: 1SDA070960R1
Price
List Price £11,323.49 ex VAT
Your Price (ex VAT) Save 25%
£8,492.62 25% OFF
You save £2,830.87 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,492.62
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,492.62

Why Choose the ABB E2.2N 1250 Ekip G Hi-Touch LSIG 3p F HR Air Circuit Breaker?

The ABB E2.2N 1250 Ekip G Hi-Touch LSIG 3p F HR, order code 1SDA070960R1, is a high-performance air circuit breaker (ACB) designed for generator protection and demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, this E2.2 frame circuit breaker combines a rated uninterrupted current of 1250 A with advanced electronic protection, measurement and power-management functionality.

The breaker is equipped with an Ekip G Hi-Touch LSIG solid-state electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. The generator-oriented Ekip G Hi-Touch platform is designed for applications requiring sophisticated protection and monitoring of generator-fed networks while retaining the advanced capabilities of ABB's Ekip Hi-Touch architecture.

The E2.2N performance class provides a rated ultimate short-circuit breaking capacity of 66 kA at 415 V AC and 66 kA at 690 V AC. The 1SDA070960R1 is a three-pole fixed circuit breaker with rear horizontal terminals and is fitted with four auxiliary contacts plus circuit-breaker open/closed position indication for integration into compatible low-voltage switchgear.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for generator and low-voltage distribution protection.
  • 1250 A rated uninterrupted current for high-current electrical systems.
  • 66 kA ultimate short-circuit breaking capacity at 415 V AC.
  • 66 kA ultimate short-circuit breaking capacity at 690 V AC.
  • Advanced Ekip G Hi-Touch LSIG electronic trip unit with generator-oriented functionality.
  • Provides long-time, short-time, instantaneous and ground-fault protection.
  • Three-pole fixed configuration with rear horizontal terminals.
  • Advanced protection, measurement and monitoring capabilities for demanding electrical networks.

Key Features

  • ABB SACE Emax 2 E2.2N series.
  • 1250 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed mounting design.
  • Rear horizontal terminals.
  • Ekip G Hi-Touch LSIG solid-state electronic release.
  • Long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection functions.
  • 66 kA Icu at 415 V AC.
  • 66 kA Icu at 690 V AC.
  • Overload protection adjustment range of 500–1250 A.
  • Main circuit connection by bolted terminals.
  • Four auxiliary contacts fitted.
  • Trip indication contact for protection release operation.
  • Circuit-breaker open/closed position indication.
  • Generator-oriented protection functionality for demanding power-generation applications.

Advanced Generator and LSIG Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E2.2N provide switching, isolation and protection for high-current low-voltage electrical circuits. The E2.2N performance class combines 66 kA short-circuit breaking capability with the flexibility of the Emax 2 platform, making it suitable for generator switchboards, main distribution boards, industrial power systems and other demanding electrical installations.

The Ekip G Hi-Touch LSIG trip unit combines advanced generator-oriented functionality with comprehensive circuit protection. Long-time protection responds to sustained overloads, short-time protection supports selective fault coordination, instantaneous protection rapidly clears severe short circuits, and ground-fault protection detects potentially damaging earth faults. This combination makes the 1SDA070960R1 particularly suitable for generator-fed and critical low-voltage power networks.

Typical Applications

  • Generator protection and generator switchboards.
  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Transformer and installation protection.
  • Critical and standby power systems.
  • Manufacturing and process plant switchgear.
  • High-current feeder and incomer protection.
  • Electrical installations requiring advanced LSIG and ground-fault protection.

Technical Specifications

Series SACE Emax 2
Frame / sub-type E2.2N
Order code / MPN 1SDA070960R1
EAN 8015644748104
Product type Air circuit breaker (ACB)
Current type AC
Rated current 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated operational voltage up to 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) 66 kA at 415 V AC
Number of poles 3
Protection release Ekip G Hi-Touch LSIG
Release type Solid-state electronic
Protection functions L (long-time), S (short-time), I (instantaneous) and G (ground fault)
Overload protection adjustment range 500–1250 A
Short-circuit performance level N
Mounting configuration Fixed
Terminal arrangement Rear horizontal
Main circuit connection Bolted connection
Auxiliary contacts 4
Trip indication contact Fitted
Circuit-breaker position indication Open / closed
Approximate weight 41 kg
Country of origin Italy
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA070960R1 used for?

The ABB 1SDA070960R1 is an Emax 2 air circuit breaker designed for generator, transformer and installation protection in demanding high-current low-voltage electrical distribution systems.

What is the rated current of the ABB E2.2N 1250?

The ABB E2.2N 1250 has a rated uninterrupted current of 1250 A and is suitable for low-voltage electrical distribution systems operating at up to 690 V AC.

What breaking capacity does the 1SDA070960R1 provide?

The E2.2N performance class provides a rated ultimate short-circuit breaking capacity of 66 kA at 415 V AC and 66 kA at 690 V AC, providing robust protection for high-current distribution systems.

What protection functions does the Ekip G Hi-Touch LSIG trip unit provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection, together with advanced functionality intended for generator protection and power-management applications.

What does F HR mean on the ABB E2.2N 1250?

The F HR configuration identifies this model as a fixed circuit breaker with rear horizontal terminals, designed for permanent installation and rear connection within compatible low-voltage switchgear.

Trusted Power Distribution Technology from ABB

ABB SACE Emax 2 air circuit breakers are engineered for reliable protection, switching and management of modern low-voltage electrical systems, combining high short-circuit performance with advanced electronic protection, generator functionality and flexible switchboard integration.