ABB 1SDA070959R1 Emax 2 E2.2N 1250 air circuit breaker, a fixed three-pole 1250 A ACB with horizontal rear terminals and Ekip Hi-Touch LSIG electronic overload, short-circuit and earth-fault protection.
£8,039.48
The ABB E2.2N 1250 Ekip Hi-Touch LSIG 3p FHR, order code 1SDA070959R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection, switching and control in demanding low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, it combines a 1250 A rating with the E2.2N performance class and ABB's advanced Ekip Hi-Touch electronic protection platform.
This model is a fixed, three-pole circuit breaker with horizontal rear terminals equipped with an Ekip Hi-Touch LSIG solid-state electronic release. Its LSIG functions provide long-time overload, short-time delayed short-circuit, instantaneous short-circuit and integrated earth-fault protection, enabling comprehensive protection and selective coordination for cables, busbars, transformers and downstream distribution equipment.
The 1SDA070959R1 is rated for 1250 A at up to 690 V AC and provides a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC. Four auxiliary change-over contacts, open/closed position indication and provision for an optional motor drive make this Emax 2 configuration well suited to modern industrial, commercial and infrastructure switchboards.
Air circuit breakers such as the ABB Emax 2 E2.2N protect low-voltage electrical networks by interrupting current when hazardous overload, short-circuit or earth-fault conditions occur. The Ekip Hi-Touch LSIG electronic release combines long-time, short-time delayed, instantaneous and earth-fault protection functions, enabling protection settings to be coordinated with upstream and downstream devices throughout the distribution system.
The E2.2N platform combines 66 kA short-circuit breaking performance at 400 V AC with advanced electronic protection and robust Emax 2 construction. Horizontal rear terminals facilitate connection to switchboard busbars, while auxiliary contacts, status indication and optional motorised operation make the 1SDA070959R1 suitable for intelligent industrial and infrastructure power-distribution systems.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070959R1 |
| EAN | 8015644748098 |
| Product type | Air circuit breaker |
| Frame / performance class | E2.2N |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated voltage | 690 V AC |
| Current type | AC |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Horizontal rear terminals |
| Trip unit | Ekip Hi-Touch LSIG |
| Release technology | Solid-state electronic |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit), G (earth fault) |
| Integrated earth-fault protection | Yes |
| Overload release setting | 500–1250 A |
| Short-time delayed short-circuit release setting | 750–12500 A |
| Instantaneous short-circuit release setting | 1875–18750 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 66 kA |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Complete device with protection unit | Yes |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Integrated undervoltage release | No |
| DIN rail mounting | No |
| Electrical durability at Ue ≤ 440 V | 15000 cycles |
| Electrical durability at 500–690 V | 15000 cycles |
| Electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 25000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Product dimensions (W × H × D) | 276 × 371 × 270 mm |
| Net weight | 45 kg |
The ABB 1SDA070959R1 is an Emax 2 E2.2N air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, including systems requiring selective overcurrent and integrated earth-fault protection.
The circuit breaker has a rated uninterrupted current of 1250 A and a rated voltage of 690 V AC.
The Ekip Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and integrated earth-fault (G) protection.
The E2.2N 1250 has a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, 50 Hz, providing robust fault interruption for demanding low-voltage power-distribution systems.
The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with busbars inside low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, robust short-circuit performance and flexible switchboard integration to provide dependable protection and selective control for modern low-voltage power distribution systems.