Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070958R1 Emax 2 E2.2N 1250 air circuit breaker, a fixed three-pole 1250 A ACB with horizontal rear terminals, 66 kA breaking capacity and Ekip Hi-Touch LSI electronic overload and short-circuit protection.
£7,557.11
The ABB E2.2N 1250 Ekip Hi-Touch LSI 3p FHR, order code 1SDA070958R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in demanding low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, it combines a 1250 A current rating with the E2.2N performance class and ABB's advanced Ekip Hi-Touch electronic protection platform.
This model is a fixed, three-pole circuit breaker with horizontal rear terminals equipped with an Ekip Hi-Touch LSI solid-state electronic release. Its LSI protection functions provide long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, supporting selective coordination while protecting cables, busbars, transformers and downstream distribution equipment.
With a rated current of 1250 A, rated operational voltage of 690 V AC and breaking capacity of 66 kA, the E2.2N 1250 provides robust protection for high-current distribution systems. Four auxiliary contacts and circuit-breaker open/closed position indication support integration into modern switchboard monitoring, signalling and control systems.
Air circuit breakers such as the ABB Emax 2 E2.2N protect low-voltage electrical networks by interrupting current when hazardous overload or short-circuit conditions occur. The Ekip Hi-Touch LSI electronic release provides long-time, short-time delayed and instantaneous protection functions, allowing protection characteristics to be coordinated with other devices throughout the electrical distribution system.
The E2.2N platform combines 66 kA breaking capacity with advanced electronic protection and robust Emax 2 construction. Its horizontal rear terminals facilitate connection to switchboard busbars, while the 1250 A rating, auxiliary contacts and position indication make the 1SDA070958R1 particularly suitable for main incomers, high-current feeders and selective industrial power-distribution systems.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070958R1 |
| EAN | 8015644748081 |
| Product type | Air circuit breaker |
| Frame / performance class | E2.2N |
| Rated current (In) | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Breaking capacity | 66 kA |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Trip unit | Ekip Hi-Touch LSI electronic release |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit) |
| Current type | AC |
| Connecting capacity | 1200 mm² |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Electrical durability at Ue ≤ 440 V | 15000 cycles |
| Electrical durability at 500–690 V | 15000 cycles |
| Electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 25000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Power loss | 83 W |
| Product dimensions (W × H × D) | 276 × 371 × 270 mm |
| Net weight | 41 kg |
| Standard / approval | IEC |
The ABB 1SDA070958R1 is an Emax 2 E2.2N air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, including main incomers, feeders and industrial distribution systems requiring advanced electronic protection.
The circuit breaker has a rated current of 1250 A and a rated operational voltage of up to 690 V AC.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection for coordinated low-voltage power distribution.
The E2.2N 1250 has a 66 kA breaking capacity, providing robust fault interruption for demanding industrial and commercial low-voltage distribution systems.
The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with busbars inside low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, robust short-circuit performance and flexible switchboard integration to provide dependable protection and selective control for modern low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.