Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070948R1 Emax 2 E2.2H 1000 A three-pole fixed air circuit breaker with rear horizontal terminals, Ekip Hi-Touch LSI electronic protection and 100 kA ultimate breaking capacity at 400 V AC for demanding low-voltage power distribution systems.
£8,185.66
The ABB E2.2H 1000 Ekip Hi-Touch LSI 3p F HR, order code 1SDA070948R1, is a high-performance air circuit breaker (ACB) from the ABB SACE Emax 2 range, engineered for protection, switching and isolation in demanding low-voltage electrical distribution systems. Rated at 1000 A, this three-pole fixed breaker combines the high-breaking-capacity E2.2H frame with ABB's advanced Ekip Hi-Touch electronic protection platform.
The breaker incorporates an Ekip Hi-Touch LSI solid-state electronic trip unit, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection. The Hi-Touch platform combines advanced protection and measurement capabilities, making this configuration well suited to sophisticated industrial and infrastructure distribution networks where accurate protection and effective system coordination are required.
The 3p F HR configuration identifies a three-pole fixed breaker with rear horizontal terminals. The E2.2H 1000 provides a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC and a rated short-time withstand current of 85 kA, delivering robust fault-clearing performance for high-fault-level low-voltage switchboards.
Air circuit breakers such as the ABB SACE Emax 2 E2.2H protect high-current low-voltage installations against damaging overload and short-circuit currents while providing controlled switching and isolation. The Ekip Hi-Touch electronic platform combines advanced protection and measurement functionality, supporting effective coordination and management of sophisticated electrical distribution networks.
The Ekip Hi-Touch LSI release combines long-time, short-time and instantaneous protection within a single electronic trip unit. Together with its 1000 A current rating, 100 kA ultimate breaking capacity at 400 V AC and high 85 kA short-time withstand capability, the 1SDA070948R1 provides a robust solution for installations where high fault-current performance and advanced electronic protection are required.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2H |
| ABB order code | 1SDA070948R1 |
| Product type | Air circuit breaker (ACB) |
| Rated current | 1000 A |
| Rated voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Rated ultimate short-circuit breaking capacity at 400 V AC | 100 kA |
| Short-time withstand capability | 85 kA |
| Number of poles | 3 |
| Protection trip unit | Ekip Hi-Touch LSI |
| Trip-unit technology | Solid-state electronic release |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Integrated ground-fault protection | No |
| Current type | AC |
| Installation | Fixed |
| Main-circuit terminal position | Rear |
| Terminal orientation | Horizontal (HR) |
| Main-circuit connection | Bolt connection |
| Connecting capacity | 600 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Open/closed indication | Yes |
| Integrated undervoltage release | No |
| Motor drive | Optional |
| Protection rating | IP30 |
| Electrical durability | 15,000 operating cycles |
| Mechanical durability | 25,000 operating cycles |
| Power loss | 53 W |
| Dimensions (W × H × D) | 276 × 371 × 270 mm |
| Net weight | 41 kg |
| EAN | 8015644747985 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA070948R1 is a SACE Emax 2 E2.2H 1000 Ekip Hi-Touch LSI 3p F HR air circuit breaker rated at 1000 A, with three-pole fixed construction, rear horizontal terminals and an Ekip Hi-Touch LSI electronic trip unit.
The breaker has a rated current of 1000 A, making it suitable for high-current low-voltage electrical distribution applications.
The Ekip Hi-Touch LSI trip unit provides long-time overload protection (L), short-time short-circuit protection (S) and instantaneous short-circuit protection (I).
The E2.2H 1000 provides a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC, making it suitable for demanding high-fault-level low-voltage distribution systems.
The F HR designation identifies a fixed-version breaker with rear horizontal terminals, providing a rear connection arrangement for integration into compatible low-voltage switchboards.
The 1SDA070948R1 is a fixed-version air circuit breaker, intended for permanent installation within a compatible low-voltage switchboard or distribution assembly.
No. This configuration uses an Ekip Hi-Touch LSI trip unit providing long-time, short-time and instantaneous protection; integrated ground-fault protection is not included in the LSI configuration.
ABB SACE Emax 2 air circuit breakers are engineered for reliable protection, switching and management of low-voltage electrical distribution systems, supporting demanding industrial, commercial and infrastructure installations.