ABB 1SDA070946R1 E2.2H 1000 Ekip Touch LSIG three-pole fixed air circuit breaker with rear horizontal terminals, 1000 A rated current and 100 kA short-circuit breaking capacity at 400–440 V AC for demanding low-voltage power distribution protection.
£5,920.00
The ABB E2.2H 1000 Ekip Touch LSIG 3p F HR, order code 1SDA070946R1, is a high-performance air circuit breaker (ACB) designed for protection, switching and control in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, this E2.2 frame circuit breaker combines a 1000 A rated current with H-class short-circuit performance for industrial, commercial and infrastructure electrical installations.
The breaker is equipped with an Ekip Touch LSIG electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. This comprehensive LSIG protection package supports selective coordination and dependable protection of cables, transformers, feeders and other equipment, while the Ekip Touch interface provides advanced configuration, measurement and monitoring capabilities.
The E2.2H performance class provides a rated ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 690 V AC. The 1SDA070946R1 is a three-pole fixed circuit breaker with rear horizontal terminals, providing a robust installation arrangement for permanent integration into compatible low-voltage switchboards.
Air circuit breakers such as the ABB SACE Emax 2 E2.2H provide switching, isolation and protection for high-current low-voltage electrical circuits. The H-performance version of the E2.2 frame is designed for installations with particularly high prospective short-circuit currents, providing 100 kA breaking capacity at 400–440 V AC and making it well suited to main distribution boards and demanding industrial switchgear.
The Ekip Touch LSIG trip unit provides four principal electronic protection functions. Long-time protection responds to sustained overloads, short-time protection enables selective coordination during short-circuit conditions, instantaneous protection provides rapid interruption of severe faults, and ground-fault protection detects potentially damaging earth-fault currents. Together, these functions provide comprehensive protection for complex low-voltage distribution networks.
| Series | SACE Emax 2 |
|---|---|
| Frame / sub-type | E2.2H |
| Order code / MPN | 1SDA070946R1 |
| Product type | Air circuit breaker (ACB) |
| Current type | AC |
| Rated current | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational voltage | up to 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 400–440 V AC |
| Number of poles | 3 |
| Protection release | Ekip Touch LSIG |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time), I (instantaneous) and G (ground fault) |
| Long-time protection setting | 400–1000 A |
| Short-time protection setting | 0.6–10 × In |
| Instantaneous protection setting | 1.5–15 × In |
| Ground-fault protection setting | 0.1–1.0 × In |
| Short-circuit performance level | H |
| Mounting configuration | Fixed |
| Terminal arrangement | Rear horizontal |
| Approximate weight | 41 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA070946R1 is an Emax 2 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution circuits, particularly in installations requiring high short-circuit performance and comprehensive LSIG protection.
The ABB E2.2H 1000 has a rated uninterrupted current of 1000 A, making it suitable for demanding industrial, commercial and infrastructure power distribution systems.
The E2.2H performance class provides a rated ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 690 V AC.
The Ekip Touch LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection for comprehensive protection and coordination of low-voltage electrical systems.
The F HR configuration identifies this model as a fixed circuit breaker with rear horizontal terminals, designed for permanent installation and rear connection within compatible low-voltage switchgear.
ABB SACE Emax 2 air circuit breakers are engineered for reliable protection, switching and management of modern low-voltage electrical distribution systems, combining high short-circuit performance with advanced electronic protection and flexible switchboard integration.