1SDA070942R1 ABB E2.2H 1000 Ekip Dip LSI 3p FHR Air Circuit Breaker

1SDA070942R1 ABB E2.2H 1000 Ekip Dip LSI 3p FHR Air Circuit Breaker

ABB 1SDA070942R1 Emax 2 E2.2H 1000 air circuit breaker, a fixed three-pole 1000 A ACB with horizontal rear terminals, Ekip Dip LSI electronic protection, 100 kA breaking capacity at 400 V AC and 85 kA short-time withstand capability.

SKU: 1SDA070942R1MPN: 1SDA070942R1
Price
List Price £7,113.70 ex VAT
Your Price (ex VAT) Save 25%
£5,335.28 25% OFF
You save £1,778.43 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,335.28
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,335.28

Why Choose the ABB E2.2H 1000 Ekip Dip LSI 3p FHR Air Circuit Breaker?

The ABB E2.2H 1000 Ekip Dip LSI 3p FHR, order code 1SDA070942R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in demanding low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, it combines a 1000 A current rating with the high-breaking-capacity E2.2H performance class and an Ekip Dip electronic trip unit.

This model is a fixed, three-pole circuit breaker with horizontal rear terminals equipped with an Ekip Dip LSI solid-state electronic release. Its LSI protection functions provide long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, supporting effective coordination while protecting cables, busbars, transformers and connected distribution equipment.

With a rated uninterrupted current of 1000 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC, the E2.2H 1000 is engineered for networks with very high prospective fault currents. Four auxiliary change-over contacts, open/closed position indication and optional motorised operation further support integration into sophisticated industrial and infrastructure switchboards.

Key Advantages

  • High-performance ABB SACE Emax 2 E2.2H air circuit breaker.
  • 1000 A rated uninterrupted current for high-current low-voltage distribution.
  • Ekip Dip LSI electronic trip unit provides configurable electronic overcurrent protection.
  • LSI functionality combines long-time, short-time delayed and instantaneous short-circuit protection.
  • 100 kA Icu at 400 V AC provides robust interruption of very high prospective fault currents.
  • 400–1000 A adjustable overload setting range supports circuit protection coordination.
  • Fixed three-pole construction with horizontal rear terminals suits switchboard busbar integration.
  • Four auxiliary change-over contacts support signalling, monitoring and control integration.

Key Features

  • ABB SACE Emax 2 E2.2H series.
  • 1000 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed version.
  • Horizontal rear terminals.
  • Ekip Dip LSI solid-state electronic release.
  • Long-time L overload protection.
  • Short-time delayed S short-circuit protection.
  • Instantaneous I short-circuit protection.
  • 400–1000 A overload release setting range.
  • 600–10000 A short-time delayed short-circuit setting range.
  • 1500–15000 A instantaneous short-circuit setting range.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 100 kA Icu at 400 V AC.
  • Four auxiliary change-over contacts.
  • Circuit-breaker open/closed position indication.

Advanced Selective Protection for High-Fault Power Distribution

Air circuit breakers such as the ABB Emax 2 E2.2H protect low-voltage electrical networks by automatically interrupting current when hazardous overload or short-circuit conditions occur. The Ekip Dip LSI electronic release provides separate long-time, short-time delayed and instantaneous protection functions, enabling the breaker to protect against different overcurrent conditions while supporting coordination with other protective devices in the distribution system.

The E2.2H performance class combines a 100 kA ultimate short-circuit breaking capacity at 400 V AC with a 85 kA 1-second short-time withstand capability, making it particularly suitable for systems with substantial prospective fault currents. Horizontal rear terminals facilitate switchboard busbar connections, while the fixed construction and auxiliary signalling features provide a robust solution for main incomers and high-current feeders.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Main incomer and high-current feeder protection.
  • Selective electrical distribution systems.
  • Installations with high prospective short-circuit currents.
  • Transformer secondary distribution switchboards.
  • Manufacturing and process plant switchgear.
  • Commercial and critical infrastructure power distribution.
  • OEM switchboards requiring horizontal rear busbar connections.

Technical Specifications

Series SACE Emax 2 E2.2
ABB order code 1SDA070942R1
EAN 8015644747923
Product type Air circuit breaker
Frame / performance class E2.2H
Rated current (In) 1000 A
Rated uninterrupted current (Iu) 1000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 3
Version Fixed
Terminal arrangement Horizontal rear terminals
Main-circuit connection Bolt connection
Trip unit Ekip Dip LSI electronic release
Protection functions L (long-time overload), S (short-time short circuit), I (instantaneous short circuit)
Integrated earth-fault protection No
Overload release setting 400–1000 A
Short-time delayed short-circuit setting 600–10000 A
Instantaneous short-circuit setting 1500–15000 A
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz 100 kA
Rated short-time withstand current (Icw), 1 s 85 kA
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Control element Push button
Complete device with protection unit Yes
Integrated motor drive No
Optional motor drive Yes
Integrated undervoltage release No
DIN rail mounting No
Degree of protection IP30
Connecting capacity 600 mm²
Electrical durability at Ue ≤ 440 V 15000 cycles
Electrical durability at 500–690 V 15000 cycles
Mechanical durability 25000 cycles
Power loss 53 W
Dimensions (H × W × D) 371 × 276 × 270 mm
Net weight 41 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA070942R1 used for?

The ABB 1SDA070942R1 is an Emax 2 E2.2H air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, particularly where high short-circuit performance and selective electronic protection are required.

What is the rated current of the E2.2H 1000 Ekip Dip LSI?

The circuit breaker has a rated uninterrupted current of 1000 A and a rated operational voltage of up to 690 V AC.

What protection does the Ekip Dip LSI trip unit provide?

The Ekip Dip LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection. This configuration does not include integrated G earth-fault protection.

What is the breaking capacity of the ABB E2.2H 1000?

The E2.2H 1000 has a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC, 50 Hz and a rated short-time withstand current of 85 kA for 1 s.

What does FHR mean on the ABB 1SDA070942R1?

The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with busbars inside low-voltage switchboards.

Trusted ABB Protection for Critical Power Systems

ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high short-circuit performance and flexible switchboard integration to provide dependable protection and selective control for demanding low-voltage power distribution systems.