Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070928R1 Emax 2 E2.2N 1000 air circuit breaker, a fixed three-pole 1000 A ACB with horizontal rear terminals and Ekip Hi-Touch LSI electronic overload, short-time and instantaneous short-circuit protection.
£7,410.95
The ABB E2.2N 1000 Ekip Hi-Touch LSI 3p FHR, order code 1SDA070928R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection and switching in demanding low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, this configuration combines a 1000 A rating with the E2.2N performance class and the sophisticated Ekip Hi-Touch electronic trip unit.
This model is a fixed, three-pole circuit breaker with horizontal rear terminals and an Ekip Hi-Touch LSI solid-state electronic release. Its LSI protection functions provide long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, allowing precise coordination of cables, busbars, transformers and downstream distribution equipment.
With a rated uninterrupted current of 1000 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, the E2.2N 1000 provides robust protection for high-current distribution systems. Four auxiliary change-over contacts, open/closed position indication and optional motorised operation support integration into modern switchboard control and automation systems.
Air circuit breakers such as the ABB Emax 2 E2.2N protect low-voltage electrical networks by automatically interrupting current when hazardous overload or short-circuit conditions occur. The Ekip Hi-Touch LSI electronic release provides independently configurable long-time, short-time delayed and instantaneous protection functions, supporting selective coordination while protecting conductors, busbars and connected equipment.
The E2.2N platform combines 66 kA short-circuit performance with advanced electronic protection and a robust Emax 2 construction. Horizontal rear terminals facilitate connection to switchboard busbars, while auxiliary contacts, status indication and optional motor operation make the 1SDA070928R1 well suited to sophisticated industrial and infrastructure distribution systems.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070928R1 |
| EAN | 8015644747787 |
| Product type | Air circuit breaker |
| Frame / performance class | E2.2N |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Horizontal rear terminals |
| Main-circuit connection | Bolt connection |
| Trip unit | Ekip Hi-Touch LSI electronic release |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit) |
| Integrated earth-fault protection | No |
| Overload release setting | 400–1000 A |
| Short-time delayed short-circuit setting | 600–10000 A |
| Instantaneous short-circuit setting | 1500–15000 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 66 kA |
| Rated service short-circuit breaking capacity (Ics) at 400 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) at 440 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) at 500 V AC | 66 kA |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Control element | Push button |
| Protection unit | Integrated |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Integrated undervoltage release | No |
| DIN rail mounting | No |
| Degree of protection | IP30 |
| Electrical durability at Ue ≤ 440 V | 15000 cycles |
| Electrical durability at 500–690 V | 15000 cycles |
| Mechanical durability | 25000 cycles |
| Power loss | 53 W |
| Dimensions (W × H × D) | 371 × 276 × 270 mm |
| Standard / approval | IEC |
The ABB 1SDA070928R1 is an Emax 2 E2.2N air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, including main incomers, feeders and industrial distribution systems requiring selective electronic protection.
The circuit breaker has a rated uninterrupted current of 1000 A and a rated operational voltage of up to 690 V AC.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection. This model does not include integrated G earth-fault protection.
The E2.2N 1000 has a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, 50 Hz, providing robust fault interruption for demanding low-voltage distribution systems.
The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with switchboard busbar systems.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, robust short-circuit performance and flexible switchboard integration to provide dependable protection and selective control for modern low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.