1SDA070910R1 ABB E2.2S 800 Ekip G Hi-Touch LSIG 3p FHR Air Circuit Breaker

1SDA070910R1 ABB E2.2S 800 Ekip G Hi-Touch LSIG 3p FHR Air Circuit Breaker

ABB 1SDA070910R1 E2.2S 800 Ekip G Hi-Touch LSIG is a fixed three-pole SACE Emax 2 air circuit breaker rated at 800 A and 690 V AC with advanced generator-oriented LSIG electronic protection.

SKU: 1SDA070910R1MPN: 1SDA070910R1
Price
List Price £11,440.42 ex VAT
Your Price (ex VAT) Save 25%
£8,580.32 25% OFF
You save £2,860.11 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,580.32
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,580.32

Why Choose the ABB E2.2S 800 Ekip G Hi-Touch LSIG 3p FHR Air Circuit Breaker?

The ABB E2.2S 800 Ekip G Hi-Touch LSIG 3p FHR is an advanced SACE Emax 2 air circuit breaker (ACB) designed for generator protection, switching and intelligent monitoring in low-voltage electrical distribution systems. Identified by ABB order code 1SDA070910R1, this fixed three-pole circuit breaker combines an 800 A rated current with the high-performance Ekip G Hi-Touch LSIG electronic protection release. :chatgpt-content-reference{index="0"}

As part of the ABB SACE Emax 2 E2.2S series, this breaker is engineered for demanding generator and industrial applications. The Ekip G Hi-Touch LSIG release provides comprehensive long-time, short-time, instantaneous and ground-fault protection together with advanced generator-oriented measurement, monitoring and protection functionality.

The E2.2S 800 features a fixed three-pole construction with rear horizontal terminals and is rated for operation up to 690 V AC. Its S performance level provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, delivering high fault-interruption capability for critical low-voltage power systems. :chatgpt-content-reference{index="1"}

Key Advantages

  • Advanced SACE Emax 2 air circuit breaker for generator and power-distribution applications.
  • 800 A rated current for industrial and generator systems.
  • Ekip G Hi-Touch LSIG electronic trip unit with generator-focused protection and monitoring.
  • 85 kA ultimate breaking capacity at 400–440 V AC.
  • 66 kA ultimate breaking capacity at 500–690 V AC.
  • Integrated long-time, short-time, instantaneous and ground-fault protection.
  • Fixed three-pole design with rear horizontal terminals.

Key Features

  • ABB SACE Emax 2 E2.2S series.
  • 800 A rated uninterrupted current (Iu).
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Three-pole configuration.
  • Fixed-mounted construction.
  • Rear horizontal terminals.
  • Ekip G Hi-Touch LSIG solid-state electronic release.
  • Generator protection and advanced measurement functionality.
  • 85 kA Icu at 400–440 V AC.
  • 66 kA Icu at 500–690 V AC.
  • 66 kA short-time withstand current for 1 s.
  • Four auxiliary contacts and breaker open/closed indication included.

Advanced Generator Protection with Ekip G Hi-Touch

Generator applications require sophisticated protection because fault behaviour differs from conventional utility-fed systems. The Ekip G Hi-Touch LSIG release combines standard circuit-breaker protection with generator-focused protection, measurement and monitoring functions to support dependable operation and selective protection coordination.

The E2.2S 800 provides configurable LSIG protection together with high-performance switching capability. Its SACE Emax 2 architecture allows integration into modern automation and energy-management systems, making it suitable for generator switchboards, distributed generation installations and critical-power applications.

Typical Applications

  • Generator output circuit protection.
  • Industrial generator switchboards.
  • Standby and emergency power systems.
  • Distributed generation installations.
  • Microgrid and energy-management applications.
  • Critical infrastructure power systems.
  • Industrial low-voltage distribution networks.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA070910R1
EAN 8015644747602
Product type Air circuit breaker (ACB)
Frame E2.2
Performance level S
Rated current (In) 800 A
Rated uninterrupted current (Iu) 800 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) 85 kA at 400–440 V AC
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw) 66 kA for 1 s
Number of poles 3
Trip unit Ekip G Hi-Touch LSIG
Trip unit type Electronic / solid-state
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Primary application Generator protection
Release type EL
Mounting Fixed
Terminal arrangement Rear horizontal terminals
Terminal connection type Rear flat horizontal
Terminal type Bolt
Main terminal screw M12
Tightening torque 70 N·m
Auxiliary contacts 4
Power loss 34 W
Mechanical durability 25,000 cycles
Electrical durability 15,000 cycles
Dimensions (W × H × D) 276 × 371 × 270 mm
Net weight 41 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA070910R1 used for?

The ABB 1SDA070910R1 is a SACE Emax 2 generator air circuit breaker designed for switching, protection and monitoring of low-voltage generator and power-distribution circuits.

What is the current rating of the E2.2S 800?

The E2.2S 800 has a rated uninterrupted current of 800 A and a rated operational voltage of 690 V AC. :chatgpt-content-reference{index="2"}

What protection functions does the Ekip G Hi-Touch LSIG provide?

The Ekip G Hi-Touch LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection with generator-oriented monitoring capabilities.

What is the breaking capacity of this circuit breaker?

The E2.2S 800 provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC. :chatgpt-content-reference{index="3"}

Is the ABB 1SDA070910R1 fixed or withdrawable?

The ABB 1SDA070910R1 is a fixed three-pole circuit breaker with rear horizontal terminals, designed for installation in suitable low-voltage switchboards and generator panels. :chatgpt-content-reference{index="4"}

Trusted Generator Protection from ABB

ABB SACE Emax 2 air circuit breakers with Ekip G Hi-Touch LSIG protection deliver advanced generator protection, reliable fault interruption and intelligent monitoring for modern power-generation and low-voltage distribution systems.