ABB 1SDA070908R1 E2.2S 800 Ekip Hi-Touch LSI three-pole fixed SACE Emax 2 air circuit breaker rated at 800 A for advanced protection and switching of low-voltage power distribution systems.
£7,703.27
The ABB E2.2S 800 Ekip Hi-Touch LSI 3P, order code 1SDA070908R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection and switching of low-voltage electrical distribution systems. As part of the ABB Emax 2 E2.2 series, this fixed three-pole circuit breaker combines an 800 A current rating with the advanced Ekip Hi-Touch LSI electronic trip unit.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, with advanced measurement and protection capabilities for demanding electrical networks. Its electronic architecture supports accurate protection coordination and selectivity, helping safeguard cables, busbars, transformers and connected equipment while maintaining continuity of service.
With a rated current of 800 A, an operating voltage of up to 690 V AC and the high short-circuit performance associated with the E2.2S frame, this breaker is suited to demanding industrial and commercial power systems. The fixed three-pole configuration with rear flat horizontal terminals enables efficient integration into low-voltage switchboards and busbar assemblies.
ABB SACE Emax 2 air circuit breakers are engineered to provide reliable switching and protection for demanding low-voltage power networks. The E2.2S frame combines substantial short-circuit performance with flexible installation characteristics, making it suitable for main switchboards, industrial distribution systems and critical high-current feeders.
The Ekip Hi-Touch LSI release extends conventional electronic circuit protection with advanced measurement and protection capabilities. Its long-time, short-time and instantaneous functions allow the breaker to be coordinated with other protective devices, helping improve selectivity, equipment protection and continuity of electrical service.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070908R1 |
| Product type | Air circuit breaker (ACB) |
| Performance level | S |
| Rated current | 800 A |
| Rated operational voltage | up to 690 V AC |
| Number of poles | 3 |
| Trip unit | Ekip Hi-Touch LSI |
| Release type | Electronic |
| Protection functions | LSI (Long-time, Short-time, Instantaneous) |
| Long-time protection adjustment range | 320–800 A |
| Short-circuit protection adjustment range | 1200–12000 A |
| Breaking capacity | up to 85 kA |
| Rated short-time withstand current | 66 kA |
| Mounting | Fixed |
| Main terminals | Rear flat horizontal |
| Terminal connection | Bolted |
| Standard | IEC 60947-2 |
The ABB 1SDA070908R1 is an Emax 2 air circuit breaker designed for switching and advanced protection of low-voltage electrical distribution circuits in industrial, commercial and infrastructure installations.
The circuit breaker has a rated current of 800 A.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The breaker is designed for low-voltage electrical distribution systems with an operating voltage of up to 690 V AC.
This fixed three-pole breaker uses rear flat horizontal terminals for connection to the switchboard busbar system.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, measurement and robust switching performance to safeguard modern industrial, commercial and infrastructure low-voltage power distribution systems.