1SDA070893R1 ABB E2.2N 800 Ekip Dip LSIG 3p F HR Air Circuit Breaker 800 A

1SDA070893R1 ABB E2.2N 800 Ekip Dip LSIG 3p F HR Air Circuit Breaker 800 A

ABB 1SDA070893R1 E2.2N 800 Ekip Dip LSIG three-pole fixed air circuit breaker with rear horizontal terminals, 800 A rated current and 66 kA short-circuit breaking capacity for comprehensive low-voltage power distribution protection.

SKU: 1SDA070893R1MPN: 1SDA070893R1
Price
List Price £6,606.99 ex VAT
Your Price (ex VAT) Save 25%
£4,955.24 25% OFF
You save £1,651.75 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,955.24
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,955.24

Why Choose the ABB E2.2N 800 Ekip Dip LSIG 3p F HR Air Circuit Breaker?

The ABB E2.2N 800 Ekip Dip LSIG 3p F HR, order code 1SDA070893R1, is a high-performance air circuit breaker (ACB) designed for protection and switching in low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 series, this E2.2 frame circuit breaker combines high short-circuit performance with comprehensive electronic protection for industrial, commercial and infrastructure electrical installations.

The breaker is equipped with an Ekip Dip LSIG solid-state electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. This comprehensive protection package helps safeguard electrical equipment and distribution networks against a broad range of fault conditions while supporting selective and reliable operation within modern low-voltage switchboards.

With a rated uninterrupted current of 800 A, a rated operational voltage up to 690 V AC and a rated ultimate short-circuit breaking capacity of 66 kA at 440 V AC, the E2.2N 800 is suitable for demanding power distribution applications. This model is a three-pole fixed circuit breaker with rear horizontal terminals, providing a robust connection arrangement for integration into compatible switchgear assemblies.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for low-voltage power distribution.
  • 800 A rated uninterrupted current for industrial and commercial electrical systems.
  • 66 kA ultimate short-circuit breaking capacity at 440 V AC.
  • Integrated Ekip Dip LSIG electronic trip unit for comprehensive circuit protection.
  • Provides long-time, short-time, instantaneous and ground-fault protection.
  • Three-pole fixed configuration with rear horizontal terminals.
  • 66 kA short-time withstand current for 1 s for robust fault-current performance.
  • Ground-fault protection provides additional protection for low-voltage distribution networks.

Key Features

  • ABB SACE Emax 2 E2.2N series.
  • 800 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed mounting design.
  • Rear horizontal terminals.
  • Ekip Dip LSIG solid-state electronic release.
  • Long-time overload (L), short-time short-circuit (S), instantaneous (I) and ground-fault (G) protection functions.
  • 66 kA Icu at 440 V AC.
  • 66 kA rated short-time withstand current for 1 s.
  • Rated operational voltage up to 690 V AC.
  • Four auxiliary contacts fitted.
  • Circuit-breaker open/closed position indication.
  • Rear horizontal connection arrangement for switchboard integration.

Comprehensive LSIG Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E2.2N protect high-current electrical distribution circuits against overloads, short circuits and ground faults while also providing dependable switching and isolation. The E2.2N frame combines substantial short-circuit capability with flexible installation options, making it suitable for main distribution boards, industrial switchgear and other installations where high prospective fault currents can occur.

The Ekip Dip LSIG trip unit provides electronic long-time, short-time, instantaneous and ground-fault protection functions. The additional ground-fault function distinguishes the LSIG configuration from LSI versions and provides enhanced protection for electrical distribution systems where earth and ground faults must be detected and cleared reliably.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Transformer secondary protection.
  • Manufacturing and process plant switchgear.
  • Power distribution panels and switchgear assemblies.
  • High-current feeder and incomer protection.
  • Electrical distribution systems requiring LSIG and ground-fault protection.

Technical Specifications

Series SACE Emax 2
Frame / sub-type E2.2N
Order code / MPN 1SDA070893R1
Product type Air circuit breaker (ACB)
Current type AC
Rated current 800 A
Rated uninterrupted current (Iu) 800 A
Rated operational voltage up to 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) 66 kA at 440 V AC
Rated short-time withstand current (Icw) 66 kA for 1 s
Number of poles 3
Protection release Ekip Dip LSIG
Release type Solid-state electronic
Protection functions L (long-time), S (short-time), I (instantaneous) and G (ground fault)
Short-circuit performance level N
Mounting configuration Fixed
Terminal arrangement Rear horizontal
Auxiliary contacts 4
Circuit-breaker position indication Open / closed
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA070893R1 used for?

The ABB 1SDA070893R1 is an Emax 2 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications.

What is the rated current of the ABB E2.2N 800?

The E2.2N 800 has a rated uninterrupted current of 800 A, making it suitable for demanding low-voltage power distribution systems.

What breaking capacity does the 1SDA070893R1 provide?

The breaker provides a rated ultimate short-circuit breaking capacity of 66 kA at 440 V AC and a rated short-time withstand current of 66 kA for 1 s.

What protection unit is fitted to this circuit breaker?

The 1SDA070893R1 is fitted with an Ekip Dip LSIG solid-state electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.

What does F HR mean on the ABB E2.2N 800?

The F HR configuration identifies this model as a fixed circuit breaker with rear horizontal terminals, intended for permanent installation and rear connection within compatible low-voltage switchgear.

Trusted Power Distribution Technology from ABB

ABB SACE Emax 2 air circuit breakers are engineered for reliable protection, switching and management of modern low-voltage electrical distribution systems, combining high short-circuit performance with advanced electronic protection and flexible switchboard integration.