Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070890R1 Emax 2 E1.2N 1600 fixed three-pole air circuit breaker with Ekip G Hi-Touch LSIG electronic protection, 1600 A rated uninterrupted current, up to 690 V AC operational voltage and 66 kA breaking capacity at 400 V AC.
£8,456.50
The ABB 1SDA070890R1, designated E1.2N 1600 Ekip G Hi-Touch LSIG 3p F F, is a high-performance three-pole air circuit breaker (ACB) designed for protection, monitoring and control in low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 series, it combines a 1600 A rated uninterrupted current with the sophisticated Ekip G Hi-Touch LSIG electronic trip unit for comprehensive electrical protection and power system management.
The E1.2N is engineered for demanding industrial, commercial and infrastructure installations where high breaking performance, selectivity and advanced protection are required. Its Ekip G Hi-Touch LSIG solid-state release provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, while the advanced Ekip platform supports sophisticated measurement, monitoring and system integration capabilities.
With a rated uninterrupted current of 1600 A, rated operational voltage up to 690 V AC and rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, the 1SDA070890R1 provides robust protection for high-current distribution systems. This version is a fixed, three-pole circuit breaker with front terminals and is supplied with four auxiliary change-over contacts and circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax 2 E1.2N protect high-current low-voltage distribution systems against overloads, short circuits and earth faults while providing controlled switching and isolation. The E1.2N frame combines compact dimensions with high breaking performance, making it suitable for switchboards where dependable protection and efficient use of installation space are important.
The Ekip G Hi-Touch LSIG trip unit extends the capabilities of conventional circuit protection with advanced electronic protection, measurement and monitoring functions. Its LSIG protection functions allow the breaker to be coordinated with other protective devices throughout the electrical network, helping achieve selective fault isolation while maintaining continuity of supply to unaffected circuits.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA070890R1 |
| Product type | Air circuit breaker (ACB) |
| Frame | E1.2N |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational voltage (Ue) | up to 690 V AC |
| Number of poles | 3 |
| Installation | Fixed |
| Terminal configuration | Front terminals |
| Trip unit | Ekip G Hi-Touch LSIG |
| Trip unit type | Solid-state electronic release |
| Protection functions | L, S, I, G |
| Overload release setting | 640–1600 A |
| Short-time delayed short-circuit setting | 960–16000 A |
| Instantaneous short-circuit setting | 2400–24000 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Earth-fault protection | Integrated |
| Auxiliary contacts | 4 change-over contacts |
| Motor operator | Optional |
| Product net width | 214 mm |
| Product net height | 295 mm |
| Product net depth | 184 mm |
| Product net weight | 11 kg |
| EAN | 8015644747404 |
The ABB 1SDA070890R1 is an Emax 2 air circuit breaker designed for switching, protecting and monitoring high-current low-voltage electrical distribution systems against overloads, short circuits and earth faults.
The circuit breaker has a rated uninterrupted current of 1600 A, with its overload release setting adjustable from 640–1600 A.
The Ekip G Hi-Touch LSIG electronic trip unit provides advanced protection and monitoring, including long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The E1.2N 1600 has a rated ultimate short-circuit breaking capacity (Icu) of 66 kA at 400 V AC.
This version is a fixed three-pole air circuit breaker with front terminals, designed for permanent installation within a suitable low-voltage switchboard or switchgear assembly.
ABB SACE Emax 2 air circuit breakers combine high breaking performance, advanced electronic protection, measurement and connectivity capabilities to provide dependable protection and power management for modern low-voltage electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.