1SDA070877R1 ABB E1.2C 1600 Ekip G Touch LSIG 3p F F Air Circuit Breaker

1SDA070877R1 ABB E1.2C 1600 Ekip G Touch LSIG 3p F F Air Circuit Breaker

ABB 1SDA070877R1 E1.2C 1600 Ekip G Touch LSIG is a fixed three-pole SACE Emax 2 air circuit breaker rated at 1600 A and 690 V AC with generator-oriented electronic protection and LSIG protection functions.

SKU: 1SDA070877R1MPN: 1SDA070877R1
Price
List Price £9,650.25 ex VAT
Your Price (ex VAT) Save 25%
£7,237.69 25% OFF
You save £2,412.56 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,237.69
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,237.69

Why Choose the ABB E1.2C 1600 Ekip G Touch LSIG 3p F F Air Circuit Breaker?

The ABB E1.2C 1600 Ekip G Touch LSIG 3p F F is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for generator protection, switching and monitoring in low-voltage electrical systems. Identified by ABB order code 1SDA070877R1, this fixed three-pole circuit breaker combines a 1600 A rated current with the specialised Ekip G Touch LSIG solid-state electronic protection release.

The Ekip G Touch platform is engineered for generator applications and combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection with generator-oriented protection and monitoring functions. Its touchscreen interface provides intuitive configuration and supervision while supporting the wider SACE Emax 2 ecosystem for communication, automation and intelligent power-management applications.

The E1.2C 1600 uses a fixed three-pole configuration with front terminals and is rated for operation up to 690 V AC. Its E1.2C performance class provides a rated ultimate short-circuit breaking capacity of 50 kA at 400 V AC, making it a robust solution for generator-fed switchboards and demanding industrial, commercial and infrastructure power systems.

Key Advantages

  • Specialised SACE Emax 2 air circuit breaker for generator and low-voltage power-distribution systems.
  • 1600 A rated current for high-current generator and distribution applications.
  • Ekip G Touch LSIG electronic trip unit with generator-oriented protection and monitoring capabilities.
  • Long-time, short-time, instantaneous and ground-fault protection.
  • 50 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Fixed three-pole construction with front main terminals.
  • Touchscreen-based configuration with support for communication, automation and intelligent power-management integration.

Key Features

  • ABB SACE Emax 2 E1.2C series.
  • 1600 A rated uninterrupted current (Iu).
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Three-pole configuration.
  • Fixed-mounted construction.
  • Front terminals for the main circuit.
  • Ekip G Touch LSIG solid-state electronic release.
  • Generator-oriented protection and monitoring functionality.
  • Long-time, short-time, instantaneous and ground-fault protection functions.
  • 50 kA rated ultimate short-circuit breaking capacity at 400 V AC.
  • Fitted with four auxiliary contacts and circuit-breaker open/closed position indication.

Advanced Generator Protection with Ekip G Touch

Generator-fed electrical systems require protection capable of responding to operating conditions that differ from conventional utility-fed networks. The Ekip G Touch release is designed for generator applications, combining the core LSIG functions required for circuit protection with additional generator-oriented protection, measurement and monitoring capabilities.

The LSIG functions provide long-time overload, short-time selective, instantaneous short-circuit and ground-fault protection. Combined with the touchscreen-based Ekip G Touch interface and flexible SACE Emax 2 architecture, the E1.2C 1600 is well suited to generator switchboards, distributed generation installations and other systems requiring coordinated generator and distribution protection.

Typical Applications

  • Generator output circuit protection.
  • Low-voltage generator switchboards.
  • Standby and emergency generation systems.
  • Industrial power-generation installations.
  • Combined heat and power generation systems.
  • Distributed generation and microgrid applications.
  • Critical infrastructure and mission-critical power systems.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA070877R1
EAN / GTIN 8015644747275
Product type Air circuit breaker (ACB)
Frame E1.2
Short-circuit performance level C
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) 50 kA at 400 V AC
Number of poles 3
Trip unit Ekip G Touch LSIG
Trip unit type Electronic / solid-state
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Ground-fault protection Integrated
Primary application Generator and power-distribution protection
User interface Touchscreen
Mounting Fixed
Main terminal arrangement Front terminals
Auxiliary contacts 4
Open/closed indication Included
Power loss 201 W
Maximum operating frequency 60 cycles per hour
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA070877R1 used for?

The ABB 1SDA070877R1 is a SACE Emax 2 air circuit breaker designed for switching, protection and monitoring of low-voltage generator circuits and associated electrical distribution systems.

What is the current rating of the E1.2C 1600?

The E1.2C 1600 has a rated current and rated uninterrupted current of 1600 A, with a rated operational voltage of up to 690 V AC.

What protection functions does the Ekip G Touch LSIG release provide?

The Ekip G Touch LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection together with generator-oriented protection and monitoring capabilities.

What is the breaking capacity of the ABB E1.2C 1600?

The E1.2C 1600 has a rated ultimate short-circuit breaking capacity of 50 kA at 400 V AC, providing robust fault interruption for demanding generator and low-voltage distribution applications.

Is the ABB 1SDA070877R1 fixed or withdrawable?

The ABB 1SDA070877R1 is a fixed three-pole circuit breaker with front terminals, designed for permanent installation within a suitable generator or low-voltage power-distribution switchboard.

Trusted Generator Protection from ABB

ABB SACE Emax 2 circuit breakers with Ekip G protection combine generator-focused electronic protection, dependable short-circuit performance and advanced monitoring capabilities for industrial generation, critical-power and low-voltage distribution systems.