ABB 1SDA070871R1 Emax 2 E1.2C 1600 air circuit breaker, a fixed three-pole 1600 A ACB with front terminals and Ekip Dip LI electronic overload and instantaneous short-circuit protection.
£4,062.76
The ABB E1.2C 1600 Ekip Dip LI 3p F F, order code 1SDA070871R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for reliable protection and switching of low-voltage AC power distribution systems. Part of the advanced ABB Emax 2 E1.2 series, this configuration combines a compact 1600 A frame with electronic overcurrent protection for demanding industrial, commercial and infrastructure switchboards.
This circuit breaker is a fixed, three-pole version with front terminals and an Ekip Dip LI solid-state electronic trip unit. The LI protection functions provide long-time overload and instantaneous short-circuit protection, helping protect cables, busbars and downstream equipment against sustained overcurrents and severe electrical faults.
With a rated uninterrupted current of 1600 A, an E1.2C short-circuit performance class of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s, the E1.2C 1600 is engineered for substantial low-voltage distribution duties. The breaker is also fitted with four auxiliary contacts and circuit-breaker open/closed position indication for integration into switchboard control and signalling systems.
Air circuit breakers such as the ABB Emax 2 E1.2C protect low-voltage electrical distribution systems by interrupting current when hazardous overcurrent conditions occur. The Ekip Dip LI electronic release provides long-time protection against sustained overloads together with instantaneous protection against severe short circuits, helping limit damage to conductors, busbars and connected electrical equipment.
The E1.2C platform combines a compact physical format with high current-carrying and fault-interruption capability. Its fixed three-pole construction, front terminals, electronic protection and auxiliary signalling make the 1SDA070871R1 particularly suitable for main incomers and distribution feeders in industrial and commercial low-voltage switchboards.
| Series | SACE Emax 2 E1.2 |
|---|---|
| ABB order code | 1SDA070871R1 |
| Product type | Air circuit breaker |
| Frame / performance class | E1.2C |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Front terminals |
| Trip unit | Ekip Dip LI solid-state electronic release |
| Protection functions | L (long-time overload), I (instantaneous short circuit) |
| Short-circuit breaking performance at 440 V AC | 50 kA |
| Rated short-time withstand current (Icw), 1 s | 42 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Current type | AC |
| Product net weight | 14 kg |
The ABB 1SDA070871R1 is an Emax 2 E1.2C air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits in industrial, commercial and infrastructure switchboards.
The circuit breaker has a rated uninterrupted current of 1600 A, making it suitable for substantial low-voltage power distribution loads.
The Ekip Dip LI electronic trip unit provides long-time overload protection (L) and instantaneous short-circuit protection (I).
The E1.2C 1600 has 50 kA short-circuit breaking performance at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.
The 1SDA070871R1 is a fixed three-pole air circuit breaker with front terminals, designed for permanent installation within a suitable low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine compact construction, electronic overcurrent protection and robust short-circuit performance to provide dependable protection for modern low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.