1SDA070841R1 ABB E1.2N 1250 Ekip Dip LI 3P Fixed Air Circuit Breaker

1SDA070841R1 ABB E1.2N 1250 Ekip Dip LI 3P Fixed Air Circuit Breaker

ABB 1SDA070841R1 is a SACE Emax 2 E1.2N 1250 A three-pole fixed air circuit breaker with front terminals and an Ekip Dip LI electronic trip unit for reliable low-voltage power distribution protection.

SKU: 1SDA070841R1MPN: 1SDA070841R1
Price
List Price £5,717.91 ex VAT
Your Price (ex VAT) Save 25%
£4,288.43 25% OFF
You save £1,429.48 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,288.43
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,288.43

Why Choose the ABB E1.2N 1250 Ekip Dip LI 3P Fixed Air Circuit Breaker?

The ABB 1SDA070841R1 is a high-performance SACE Emax 2 E1.2N air circuit breaker (ACB) designed for dependable protection and switching in low-voltage power distribution systems. Rated at 1250 A, this three-pole breaker incorporates an Ekip Dip LI solid-state electronic trip unit providing long-time overload and instantaneous short-circuit protection.

As part of the ABB SACE Emax 2 range, the E1.2N combines compact construction with high short-circuit performance and straightforward electronic protection. The Ekip Dip LI release uses DIP-switch adjustment for simple protection configuration, with long-time overload protection adjustable from 500–1250 A and instantaneous short-circuit protection adjustable from 1875–18750 A.

This configuration is a three-pole fixed air circuit breaker with front terminals. The E1.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC, together with a short-time withstand current of 50 kA for 1 second.

Key Advantages

  • High-performance ABB SACE Emax 2 E1.2N air circuit breaker.
  • 1250 A rated current for demanding low-voltage distribution systems.
  • Ekip Dip LI electronic trip unit for overload and instantaneous short-circuit protection.
  • DIP-switch configuration for straightforward protection adjustment.
  • 66 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 50 kA short-time withstand current for 1 second.
  • Rated operational voltage up to 690 V AC.
  • Fixed three-pole construction with front terminals for switchboard integration.

Key Features

  • ABB SACE Emax 2 E1.2N air circuit breaker.
  • 1250 A rated uninterrupted current.
  • 3-pole configuration.
  • Fixed circuit-breaker execution.
  • Front terminal connection arrangement.
  • Ekip Dip LI solid-state electronic release.
  • Long-time overload (L) protection.
  • Instantaneous short-circuit (I) protection.
  • Overload setting range of 500–1250 A.
  • Instantaneous setting range of 1875–18750 A.
  • Four auxiliary contacts for breaker status signalling.
  • Designed and tested for low-voltage power distribution applications.

Reliable LI Protection for Power Distribution

The Ekip Dip LI trip unit provides the essential protection functions required for many low-voltage distribution circuits. Long-time protection responds to sustained overload conditions, while instantaneous protection provides rapid interruption of high-level short-circuit faults.

Combined with the E1.2N frame's 66 kA ultimate breaking capacity at 400–440 V AC and 50 kA one-second withstand rating, the 1SDA070841R1 provides a robust solution for main distribution boards and industrial switchgear where dependable overcurrent protection and high fault-handling capability are required.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process facilities.
  • Infrastructure and utility installations.
  • Protection of busbars, feeders and distribution circuits.
  • OEM switchboards and electrical distribution assemblies.

Technical Specifications

Series SACE Emax 2
Order code 1SDA070841R1
EAN / GTIN 8015644746919
Product type Air circuit breaker
Frame E1.2N
Short-circuit performance level N
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 3
Current type AC
Installation Fixed
Terminal arrangement Front terminals
Terminal type Bolt
Trip unit Ekip Dip LI
Release type Solid-state electronic
Protection functions L (long-time overload), I (instantaneous short circuit)
Long-time overload adjustment range 500–1250 A
Instantaneous short-circuit adjustment range 1875–18750 A
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 66 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 66 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 50 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 50 kA
Service short-circuit breaking capacity (Ics) at 400–690 V AC 50 kA
Short-time withstand current (Icw), 1 s 50 kA
Short-time withstand current (Icw), 3 s 30 kA
Power loss 122 W
Electrical durability at Ue ≤ 440 V 8000 cycles
Electrical durability at Ue 500–690 V 6500 cycles
Mechanical durability 20000 cycles
Dimensions (W × H × D) 210 × 296 × 183 mm
Net weight 14 kg
Standard IEC 60947-2
ABB product group Emax2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA070841R1?

The ABB 1SDA070841R1 is a SACE Emax 2 E1.2N 1250 A three-pole fixed air circuit breaker with front terminals and an Ekip Dip LI solid-state electronic trip unit.

What protection functions does the Ekip Dip LI provide?

The Ekip Dip LI provides long-time overload and instantaneous short-circuit protection, with protection thresholds configured using DIP switches.

What is the breaking capacity of the ABB E1.2N 1250?

The E1.2N 1250 provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC.

Is the ABB 1SDA070841R1 fixed or withdrawable?

The 1SDA070841R1 is a fixed three-pole air circuit breaker with front terminals.

What are the protection adjustment ranges of the ABB 1SDA070841R1?

The long-time overload protection is adjustable from 500–1250 A, while the instantaneous short-circuit protection is adjustable from 1875–18750 A.

Trusted by Power Distribution Professionals Worldwide

ABB SACE Emax 2 air circuit breakers combine dependable switching performance, high short-circuit capability and configurable electronic protection for modern low-voltage power distribution applications.