Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070826R1 is a SACE Emax 2 E1.2B 1250 A three-pole fixed air circuit breaker with front terminals and an Ekip Touch LSIG electronic trip unit for comprehensive low-voltage power distribution protection.
£4,604.44
The ABB 1SDA070826R1 is a SACE Emax 2 E1.2B air circuit breaker (ACB) designed for comprehensive protection, switching and monitoring in low-voltage power distribution systems. Rated at 1250 A, this three-pole breaker incorporates an Ekip Touch LSIG electronic trip unit providing long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection.
As part of the ABB SACE Emax 2 family, the E1.2B combines compact construction with advanced electronic protection and digital functionality. The Ekip Touch release features an intuitive colour touchscreen interface for configuring protection functions and accessing operating information, helping simplify commissioning, monitoring and maintenance in modern electrical installations.
This configuration is a three-pole fixed air circuit breaker with front terminals. The E1.2B performance level provides an ultimate short-circuit breaking capacity of 42 kA at 415 V AC, while its rated operational voltage extends to 690 V AC, making it suitable for demanding industrial and commercial distribution applications.
Air circuit breakers provide switching, isolation and fault protection at critical points in low-voltage distribution systems. The ABB SACE Emax 2 platform combines robust short-circuit performance with advanced electronic protection and digital functionality for dependable protection of switchboards, busbars, cables and connected electrical equipment.
The Ekip Touch LSIG trip unit fitted to this E1.2B configuration provides four complementary protection functions covering overload, delayed short-circuit, instantaneous short-circuit and earth-fault conditions. Its touchscreen interface makes protection configuration and operating-data access more intuitive, while the short-time function supports selective coordination within multi-level distribution networks.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA070826R1 |
| EAN / GTIN | 8015644746766 |
| Product type | Air circuit breaker |
| Frame | E1.2B |
| Short-circuit performance level | B |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Number of poles | 3 |
| Installation | Fixed |
| Terminal arrangement | Front terminals |
| Trip unit | Ekip Touch LSIG |
| Release type | Electronic |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit), G (earth fault) |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 42 kA |
| Power loss | 122 W |
| Standard | IEC |
| ABB product group | Emax2 Air Circuit Breaker |
The ABB 1SDA070826R1 is a SACE Emax 2 E1.2B 1250 A three-pole fixed air circuit breaker with front terminals and an Ekip Touch LSIG electronic trip unit.
The Ekip Touch LSIG provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection, with a touchscreen interface for configuration and operating information.
This E1.2B configuration provides an ultimate short-circuit breaking capacity of 42 kA at 415 V AC.
The 1SDA070826R1 is a fixed three-pole air circuit breaker with front terminals.
Yes. Its Ekip Touch LSIG electronic trip unit includes integrated earth-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
ABB SACE Emax 2 air circuit breakers combine dependable switching performance, advanced electronic protection and flexible digital functionality for modern low-voltage power distribution applications.