Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070822R1 is a SACE Emax 2 E1.2B three-pole fixed 1250 A air circuit breaker rated at 690 V AC with front terminals, an Ekip Dip LSI electronic trip unit and 42 kA ultimate short-circuit breaking capacity at 400–690 V AC.
£4,077.79
The ABB 1SDA070822R1, designated E1.2B 1250 Ekip Dip LSI 3p F F, is a SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in low-voltage AC power distribution systems. Built on the compact ABB SACE Emax 2 E1.2 frame, this fixed three-pole breaker combines a 1250 A rated uninterrupted current with an Ekip Dip LSI solid-state electronic trip unit.
The Ekip Dip LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. Its DIP-switch-based adjustment provides a straightforward method of configuring protection thresholds, making the breaker well suited to installations requiring dependable electronic protection and selective coordination without a touchscreen-based trip unit.
Rated for operation up to 690 V AC, the E1.2B 1250 provides a rated ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC and a rated short-time withstand current of 42 kA for 1 s. Its fixed three-pole construction and front terminals make it suitable for industrial, commercial and infrastructure switchboards requiring reliable high-current circuit protection.
The Ekip Dip LSI electronic trip unit provides three essential protection functions for low-voltage distribution systems. Long-time protection responds to sustained overload conditions, short-time protection introduces a configurable response to short-circuit currents for improved selectivity, and instantaneous protection enables rapid interruption when severe fault currents occur.
The E1.2B 1250 also provides a 42 kA short-time withstand capability for 1 s, allowing appropriately coordinated downstream protective devices time to clear applicable faults before the main breaker operates. Combined with straightforward DIP-switch configuration, this makes the 1SDA070822R1 a practical solution for distribution systems requiring dependable electronic protection and selective coordination.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2 |
| Performance level | B |
| Order code / Product ID | 1SDA070822R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Execution | Fixed |
| Number of poles | 3 |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | LSI |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Overload protection adjustment range | 500–1250 A |
| Short-time protection adjustment range | 750–12500 A |
| Integrated earth-fault protection | No |
| Short-circuit performance level | B |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated service short-circuit breaking capacity (Ics) at 400–440 V AC | 42 kA |
| Rated short-time withstand current (Icw) | 42 kA for 1 s; 24 kA for 3 s |
| Terminal connection type | Front |
| Main circuit connection | Bolted |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Power loss | 122 W |
| Electrical durability at ≤440 V | 8000 cycles |
| Electrical durability at 500–690 V | 6500 cycles |
| Mechanical durability | 20000 cycles |
| Degree of protection | IP30 |
| EAN | 8015644746728 |
| Customs tariff number | 85362090 |
| Standard | IEC |
The ABB 1SDA070822R1 is an Emax 2 air circuit breaker designed for switching and protecting low-voltage AC distribution systems, including transformer, generator and installation protection applications.
The 1SDA070822R1 has a rated uninterrupted current of 1250 A.
The breaker uses an Ekip Dip LSI solid-state electronic trip unit, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection with DIP-switch-adjustable settings.
The E1.2B 1250 has a rated ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC and a rated short-time withstand current of 42 kA for 1 s.
The 1SDA070822R1 is a three-pole fixed air circuit breaker with front terminal connections.
ABB SACE Emax 2 air circuit breakers combine dependable fault interruption with configurable Ekip electronic protection for industrial, commercial and infrastructure low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.