ABB 1SDA070821R1 Emax 2 E1.2B 1250 air circuit breaker, a fixed three-pole 1250 A ACB with front terminals and Ekip Dip LI electronic overload and instantaneous short-circuit protection.
£3,791.90
The ABB E1.2B 1250 Ekip Dip LI 3p F F, order code 1SDA070821R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for reliable protection and switching of low-voltage AC power distribution systems. Part of the advanced ABB Emax 2 E1.2 series, this model combines a compact frame with electronic protection for demanding industrial and commercial electrical installations.
This configuration is a fixed, three-pole circuit breaker with front terminals and an Ekip Dip LI solid-state electronic trip unit. The LI protection functions provide long-time overload and instantaneous short-circuit protection, helping safeguard cables, busbars and downstream electrical equipment against damaging overcurrent conditions.
With a rated current of 1250 A, rated operational voltage up to 690 V AC and a rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC, the E1.2B 1250 is engineered for robust power distribution. This version is also supplied with four auxiliary contacts and circuit-breaker open/closed position indication for integration into switchboards and control systems.
Air circuit breakers such as the ABB Emax 2 E1.2B protect low-voltage distribution systems by automatically interrupting current when abnormal electrical conditions occur. The electronic Ekip Dip LI release continuously supports protection against sustained overloads and high-level short circuits, helping reduce the risk of damage to conductors, busbars and connected equipment.
The E1.2B platform combines high current-carrying capability with a compact architecture suitable for modern low-voltage switchboards. Its fixed three-pole construction, front terminals, auxiliary signalling contacts and electronic protection make the 1SDA070821R1 particularly suitable for incomer, feeder and distribution duties where dependable circuit protection and straightforward system integration are required.
| Series | SACE Emax 2 E1.2 |
|---|---|
| ABB order code | 1SDA070821R1 |
| Product type | Air circuit breaker |
| Frame / subtype | E1.2B |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Version | Fixed |
| Terminal connection | Front |
| Trip unit | Ekip Dip LI electronic release |
| Protection functions | L (overload), I (instantaneous short circuit) |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 42 kA |
| Rated service short-circuit breaking capacity (Ics) at 400 V AC | 42 kA |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw), 1 s | 42 kA |
| Rated short-time withstand current (Icw), 3 s | 24 kA |
| Auxiliary contacts | 4 |
| Current type | AC |
| Standard | IEC 60947-2 |
| Product net width | 210 mm |
| Product net height | 296 mm |
| Product net depth | 183 mm |
| Product net weight | 14 kg |
| EAN | 8015644746711 |
The ABB 1SDA070821R1 is an Emax 2 air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits in industrial, commercial and infrastructure installations.
This circuit breaker has a rated current of 1250 A, making it suitable for substantial low-voltage distribution loads.
The Ekip Dip LI electronic trip unit provides long-time overload protection (L) and instantaneous short-circuit protection (I).
This E1.2B version has a rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC, with a rated service short-circuit breaking capacity of 42 kA.
The 1SDA070821R1 is a fixed three-pole circuit breaker with front terminal connections and is intended for permanent installation within a suitable low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high breaking performance and flexible switchboard integration to provide dependable protection for modern low-voltage power distribution systems.