1SDA070809R1 ABB E1.2N 1000 Ekip Hi-Touch LSIG 3-Pole Fixed Air Circuit Breaker

1SDA070809R1 ABB E1.2N 1000 Ekip Hi-Touch LSIG 3-Pole Fixed Air Circuit Breaker

ABB 1SDA070809R1 is an Emax 2 E1.2N 1000 A three-pole fixed air circuit breaker with front terminals and an Ekip Hi-Touch LSIG solid-state electronic trip unit for advanced overload, selective short-circuit, instantaneous short-circuit and earth-fault protection.

SKU: 1SDA070809R1MPN: 1SDA070809R1
Price
List Price £10,272.22 ex VAT
Your Price (ex VAT) Save 25%
£7,704.17 25% OFF
You save £2,568.06 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,704.17
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,704.17

Why Choose the ABB 1SDA070809R1 E1.2N 1000 Ekip Hi-Touch LSIG Air Circuit Breaker?

The ABB 1SDA070809R1 is a SACE Emax 2 E1.2N 1000 three-pole fixed air circuit breaker equipped with an advanced Ekip Hi-Touch LSIG solid-state electronic trip unit. Designed for demanding low-voltage AC power-distribution systems, it combines a 1000 A rated uninterrupted current with comprehensive overload, short-circuit and earth-fault protection.

This configuration features front terminals and the E1.2N short-circuit performance level, providing an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC. Its rated short-time withstand current is 50 kA for 1 second and 30 kA for 3 seconds, supporting robust performance in high-demand distribution systems.

The Ekip Hi-Touch LSIG release provides long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection. The Hi-Touch platform combines advanced protection with measurement and power-system supervision capabilities, while four auxiliary change-over contacts and open/closed indication support integration with compatible switchboard control and monitoring systems.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for demanding low-voltage distribution.
  • 1000 A rated uninterrupted current in the compact E1.2 frame.
  • Ekip Hi-Touch LSIG electronic trip unit with integrated earth-fault protection.
  • 66 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 50 kA short-time withstand current for 1 second.
  • Three-pole fixed construction with front terminals for professional switchboard integration.

Key Features

  • ABB SACE Emax 2 air circuit breaker.
  • E1.2N 1000 configuration.
  • 1000 A rated uninterrupted current.
  • 690 V AC rated operational voltage.
  • Three-pole construction.
  • Fixed execution.
  • Front terminals with bolted main-circuit connection.
  • Ekip Hi-Touch LSIG solid-state electronic trip unit.
  • LSIG protection: long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection.
  • Four auxiliary change-over contacts and switched-off indication.

Advanced LSIG Protection and Power-System Supervision

The Ekip Hi-Touch LSIG electronic trip unit provides comprehensive protection for sophisticated low-voltage distribution systems. Long-time protection responds to sustained overloads, selective short-circuit protection supports coordinated fault clearing, instantaneous protection rapidly disconnects severe short circuits, and integrated earth-fault protection provides additional protection against ground-fault conditions.

Combined with the E1.2N air circuit-breaker platform, the ABB 1SDA070809R1 delivers high fault-interruption performance in a compact fixed configuration. Front terminals support efficient switchboard integration, while the Hi-Touch electronic platform, auxiliary contacts and status indication make the breaker suitable for installations requiring advanced protection, measurement, supervision and automation.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power-distribution systems.
  • Commercial building electrical distribution.
  • Transformer, generator and installation protection.
  • Critical power and infrastructure installations.
  • OEM switchboards requiring advanced LSIG protection and power-system supervision.

Technical Specifications

Product family SACE Emax 2
ABB order code 1SDA070809R1
Product type Air circuit breaker
Frame E1.2
Short-circuit performance level N
Rated uninterrupted current 1000 A
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V AC
Rated impulse withstand voltage 12 kV
Current type AC
Number of poles 3
Execution Fixed
Terminal connection Front
Main-circuit connection Bolt connection
Trip unit Ekip Hi-Touch LSIG
Release type Electronic
Protection functions LSIG
Integrated earth-fault protection Yes
Ultimate short-circuit breaking capacity at 400 V AC 66 kA
Ultimate short-circuit breaking capacity at 415 V AC 66 kA
Ultimate short-circuit breaking capacity at 440 V AC 66 kA
Ultimate short-circuit breaking capacity at 500 V AC 50 kA
Ultimate short-circuit breaking capacity at 690 V AC 50 kA
Rated service short-circuit breaking capacity 100% of Icu
Short-time withstand current, 1 s 50 kA
Short-time withstand current, 3 s 30 kA
Auxiliary contacts 4 change-over contacts
Switched-off indication Yes
Degree of protection IP30
Power loss 78 W
Product net dimensions (W × H × D) 210 × 296 × 183 mm
Product net weight 14 kg
Electrical durability 8000 cycles
Mechanical durability 20000 cycles
Standard IEC
EAN 8015644746599
ABB product group Emax2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA070809R1?

The ABB 1SDA070809R1 is a SACE Emax 2 E1.2N 1000 three-pole fixed air circuit breaker with front terminals and an Ekip Hi-Touch LSIG solid-state electronic trip unit.

What is the current rating of ABB 1SDA070809R1?

The E1.2N 1000 configuration has a rated uninterrupted current of 1000 A.

What protection functions does the Ekip Hi-Touch LSIG trip unit provide?

The LSIG configuration provides long-time overload protection, selective short-circuit protection, instantaneous short-circuit protection and integrated earth-fault protection.

What is the breaking capacity of the E1.2N 1000?

The E1.2N 1000 provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC.

What is the short-time withstand current of ABB 1SDA070809R1?

The breaker has a rated short-time withstand current of 50 kA for 1 second and 30 kA for 3 seconds.

Does ABB 1SDA070809R1 provide earth-fault protection?

Yes. The Ekip Hi-Touch LSIG trip unit includes integrated earth-fault protection as part of its LSIG protection functions.

Is ABB 1SDA070809R1 fixed or withdrawable?

The ABB 1SDA070809R1 is a fixed Emax 2 air circuit breaker with front terminals.

Does ABB 1SDA070809R1 include auxiliary contacts?

Yes. The breaker provides four auxiliary change-over contacts together with switched-off indication for compatible monitoring and control arrangements.

Trusted by Electrical Professionals Worldwide

ABB SACE Emax 2 air circuit breakers are used in demanding industrial, commercial and infrastructure power systems where dependable overload, short-circuit and earth-fault protection, selective coordination and advanced electronic supervision are essential.