ABB 1SDA070782R1 is a SACE Emax 2 E1.2B three-pole fixed 1000 A air circuit breaker rated at 690 V AC with front terminals, an Ekip Dip LSI electronic trip unit and a 42 kA ultimate breaking capacity at 400–690 V AC.

SKU: 1SDA070782R1MPN: 1SDA070782R1
Price
List Price £5,136.09 ex VAT
Your Price (ex VAT) Save 25%
£3,852.07 25% OFF
You save £1,284.02 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £3,852.07
Trade pricing is personalised to your account

Manufacturer Lead Time

£3,852.07

Why Choose the ABB E1.2B 1000 Ekip Dip LSI 3p F F Air Circuit Breaker?

The ABB 1SDA070782R1, designated E1.2B 1000 Ekip Dip LSI 3p F F, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for protection and switching in low-voltage AC power distribution systems. Part of the ABB SACE Emax 2 E1.2 series, this fixed three-pole circuit breaker combines a 1000 A rated uninterrupted current with the reliable Ekip Dip LSI electronic trip unit.

The Ekip Dip LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. Adjustable protection thresholds allow the breaker to be configured using DIP switches, providing a straightforward and dependable method of adapting protection characteristics to the requirements of the electrical installation.

With a rated operational voltage of up to 690 V AC and a B short-circuit performance level, the E1.2B 1000 provides a rated ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC. Its compact E1.2 frame, fixed construction and front terminal arrangement make it suitable for industrial, commercial and infrastructure switchboards requiring reliable high-current circuit protection.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for low-voltage power distribution.
  • 1000 A rated uninterrupted current for high-current electrical distribution applications.
  • Ekip Dip LSI electronic trip unit providing long-time, short-time and instantaneous protection.
  • 42 kA ultimate and service short-circuit breaking capacity across key AC operating voltages up to 690 V.
  • Protection settings adjustable through accessible DIP switches.
  • Three-pole fixed configuration with front terminals for permanent switchboard installation.

Key Features

  • ABB SACE Emax 2 E1.2 series.
  • 1000 A rated uninterrupted current.
  • 690 V AC rated operational voltage.
  • Three-pole configuration.
  • Fixed circuit breaker execution.
  • Front bolted terminal connections.
  • Ekip Dip LSI electronic release.
  • LSI functions provide long-time, short-time and instantaneous overcurrent protection.
  • B short-circuit performance level.
  • 42 kA Icu at 400–690 V AC.
  • 42 kA Ics at 400–690 V AC.
  • 42 kA short-time withstand current for 1 s.
  • Suitable for IT networks up to 690 V.
  • Designed to IEC standards for low-voltage circuit breakers.

Reliable Circuit Protection with Ekip Dip LSI

The Ekip Dip LSI electronic trip unit provides three essential protection functions for low-voltage distribution systems. Long-time protection responds to sustained overload conditions, short-time protection allows selective coordination during short-circuit events, and instantaneous protection provides rapid interruption when severe fault currents occur.

Combined with the ABB SACE Emax 2 platform, the Ekip Dip release provides dependable electronic protection with straightforward DIP-switch configuration. The 1SDA070782R1 also offers a 42 kA short-time withstand capability for 1 s, supporting selective protection strategies in switchboards where downstream protective devices should be given an opportunity to clear faults before the main breaker operates.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main electrical switchboards.
  • Transformer, generator and installation protection.
  • Commercial building power distribution.
  • Manufacturing and process facilities.
  • Infrastructure and critical-power installations.
  • Electrical systems requiring adjustable LSI protection and selective fault coordination.

Technical Specifications

Series SACE Emax 2
Frame E1.2
Order code / Product ID 1SDA070782R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Execution Fixed
Number of poles 3
Rated current (In) 1000 A
Rated uninterrupted current (Iu) 1000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Frequency 50 / 60 Hz
Trip unit Ekip Dip LSI
Release type Electronic
Protection functions LSI
Overload protection setting 0.4–1 × In
Short-time protection setting 0.6–10 × In
Instantaneous protection setting 1.5–15 × In
Short-circuit performance level B
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 42 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 42 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 42 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 42 kA
Rated service short-circuit breaking capacity (Ics) 42 kA
Ics as percentage of Icu 100%
Rated short-time withstand current (Icw) 42 kA for 1 s; 24 kA for 3 s
Terminal connection type Front
Terminal type Bolt
Main circuit screw M10
Tightening torque 45 N·m
Power loss 78 W
Electrical durability 8000 cycles
Mechanical durability 20000 cycles
Suitable for IT networks Yes, up to 690 V
Dimensions (W × H × D) 210 × 296 × 183 mm
Net weight 14 kg
EAN 8015644746322
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA070782R1 used for?

The ABB 1SDA070782R1 is an Emax 2 air circuit breaker designed for switching and protecting low-voltage AC distribution systems, including transformer, generator and installation protection applications.

What is the rated current of the ABB E1.2B 1000?

The 1SDA070782R1 has a rated uninterrupted current of 1000 A.

What protection unit does the ABB 1SDA070782R1 use?

The breaker uses an Ekip Dip LSI electronic trip unit, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection with DIP-switch-adjustable settings.

What is the breaking capacity of the ABB 1SDA070782R1?

The E1.2B 1000 has a rated ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC, with a rated service breaking capacity equal to 100% of Icu.

Is the ABB 1SDA070782R1 fixed or withdrawable?

The 1SDA070782R1 is a three-pole fixed air circuit breaker with front bolted terminal connections.

ABB Emax 2 Power Distribution Protection

ABB SACE Emax 2 air circuit breakers combine high-performance fault interruption with configurable Ekip electronic protection for dependable industrial, commercial and infrastructure low-voltage power distribution systems.