ABB 1SDA070763R1 E1.2N 800 is an 800 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals and an Ekip Dip LSIG electronic trip unit for overload, selective short-circuit, instantaneous and ground-fault protection.
£4,845.20
The ABB E1.2N 800 Ekip Dip LSIG 3P F F, order code 1SDA070763R1, is an 800 A three-pole fixed air circuit breaker from the ABB SACE Emax 2 range. It combines the compact E1.2 frame with an Ekip Dip LSIG solid-state electronic trip unit, providing comprehensive overload, selective short-circuit, instantaneous short-circuit and ground-fault protection for low-voltage AC distribution systems.
The E1.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC. The breaker also provides a rated short-time withstand current of 50 kA for 1 s, supporting demanding distribution applications where both fault interruption and selective coordination are important.
Rated at 800 A with an operational voltage up to 690 V AC, this model uses a fixed three-pole construction with front bolt terminals. ABB specifies the complete breaker with four auxiliary contacts and open/closed breaker position indication, making it suitable for main distribution, feeder and industrial switchboard applications requiring integrated LSIG protection.
The Ekip Dip LSIG release combines four principal protection functions. Long-time protection responds to sustained overload currents, short-time selective protection enables controlled response to short-circuit conditions, instantaneous protection provides rapid interruption of severe faults, and ground-fault protection detects fault current flowing to earth.
Combined with the E1.2N frame's 66 kA ultimate breaking capacity at 400–440 V AC and 50 kA short-time withstand current for 1 s, the 1SDA070763R1 provides a robust solution for demanding distribution networks. Its 800 A rating, fixed construction and front terminals make it particularly suitable for permanent installation in industrial, commercial and infrastructure switchboards.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA070763R1 |
| Product type | Air circuit breaker |
| Frame | E1.2 |
| Short-circuit performance level | N |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LSIG |
| Release type | Electronic / solid-state |
| Protection functions | Long-time (L), short-time selective (S), instantaneous (I), ground fault (G) |
| Overload protection setting range | 320–800 A |
| Instantaneous short-circuit setting range | 1200–12000 A |
| Installation version | Fixed |
| Terminal connection | Front |
| Terminal type | Bolt |
| Recommended main-circuit screw | M10 |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 50 kA |
| Rated service short-circuit breaking capacity (Ics) at 400–690 V AC | 50 kA |
| Rated short-time withstand current (Icw) | 50 kA for 1 s; 30 kA for 3 s |
| Power loss | 50 W |
| Auxiliary contacts | 4 |
| Breaker position indication | Open/closed |
| Suitable for IT networks | Yes, up to 690 V |
| Net weight | 14 kg |
| Standard | IEC |
| EAN | 8015644746131 |
| ABB product group | Emax2 Air Circuit Breaker |
The ABB 1SDA070763R1 is an E1.2N 800 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals and an Ekip Dip LSIG solid-state electronic trip unit.
The Ekip Dip LSIG provides long-time (L) overload, short-time selective (S), instantaneous (I) and ground-fault (G) protection.
The breaker has an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC.
The breaker has a rated short-time withstand current of 50 kA for 1 s and 30 kA for 3 s.
Both releases provide long-time, short-time selective and instantaneous protection, while the LSIG version additionally provides ground-fault (G) protection for earth-fault conditions.