1SDA070763R1 ABB E1.2N 800 Ekip Dip LSIG 3P F F Air Circuit Breaker

1SDA070763R1 ABB E1.2N 800 Ekip Dip LSIG 3P F F Air Circuit Breaker

ABB 1SDA070763R1 E1.2N 800 is an 800 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals and an Ekip Dip LSIG electronic trip unit for overload, selective short-circuit, instantaneous and ground-fault protection.

SKU: 1SDA070763R1MPN: 1SDA070763R1
Price
List Price £6,460.26 ex VAT
Your Price (ex VAT) Save 25%
£4,845.20 25% OFF
You save £1,615.07 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,845.20
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,845.20

Why Choose the ABB E1.2N 800 Ekip Dip LSIG 3P F F Air Circuit Breaker?

The ABB E1.2N 800 Ekip Dip LSIG 3P F F, order code 1SDA070763R1, is an 800 A three-pole fixed air circuit breaker from the ABB SACE Emax 2 range. It combines the compact E1.2 frame with an Ekip Dip LSIG solid-state electronic trip unit, providing comprehensive overload, selective short-circuit, instantaneous short-circuit and ground-fault protection for low-voltage AC distribution systems.

The E1.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC. The breaker also provides a rated short-time withstand current of 50 kA for 1 s, supporting demanding distribution applications where both fault interruption and selective coordination are important.

Rated at 800 A with an operational voltage up to 690 V AC, this model uses a fixed three-pole construction with front bolt terminals. ABB specifies the complete breaker with four auxiliary contacts and open/closed breaker position indication, making it suitable for main distribution, feeder and industrial switchboard applications requiring integrated LSIG protection.

Key Advantages

  • Genuine ABB SACE Emax 2 air circuit breaker.
  • 800 A rated uninterrupted current for substantial low-voltage loads.
  • 66 kA ultimate breaking capacity at 400–440 V AC.
  • 50 kA ultimate breaking capacity at 500–690 V AC.
  • 50 kA short-time withstand current for 1 s.
  • Ekip Dip LSIG electronic release provides comprehensive circuit protection.
  • Short-time selective protection supports coordinated protection strategies.
  • Ground-fault protection provides additional protection against earth-fault conditions.
  • Three-pole fixed construction with front terminals.

Key Features

  • ABB SACE Emax 2 E1.2N series.
  • 800 A rated current.
  • Ekip Dip LSIG solid-state electronic trip unit.
  • Long-time (L) overload protection.
  • Short-time selective (S) short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • Ground-fault (G) protection.
  • Three-pole construction.
  • Fixed (F) execution.
  • Front (F) terminal connection.
  • Bolt-type main terminals.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Suitable for 690 V IT networks.

Comprehensive LSIG Protection for Low-Voltage Distribution

The Ekip Dip LSIG release combines four principal protection functions. Long-time protection responds to sustained overload currents, short-time selective protection enables controlled response to short-circuit conditions, instantaneous protection provides rapid interruption of severe faults, and ground-fault protection detects fault current flowing to earth.

Combined with the E1.2N frame's 66 kA ultimate breaking capacity at 400–440 V AC and 50 kA short-time withstand current for 1 s, the 1SDA070763R1 provides a robust solution for demanding distribution networks. Its 800 A rating, fixed construction and front terminals make it particularly suitable for permanent installation in industrial, commercial and infrastructure switchboards.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Main incomer and feeder protection.
  • Selective and coordinated distribution networks.
  • Systems requiring integrated ground-fault protection.
  • Manufacturing and process plant switchgear.
  • Compatible 690 V IT distribution networks.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA070763R1
Product type Air circuit breaker
Frame E1.2
Short-circuit performance level N
Rated current (In) 800 A
Rated uninterrupted current (Iu) 800 A
Number of poles 3
Current type AC
Trip unit Ekip Dip LSIG
Release type Electronic / solid-state
Protection functions Long-time (L), short-time selective (S), instantaneous (I), ground fault (G)
Overload protection setting range 320–800 A
Instantaneous short-circuit setting range 1200–12000 A
Installation version Fixed
Terminal connection Front
Terminal type Bolt
Recommended main-circuit screw M10
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400–440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 50 kA
Rated service short-circuit breaking capacity (Ics) at 400–690 V AC 50 kA
Rated short-time withstand current (Icw) 50 kA for 1 s; 30 kA for 3 s
Power loss 50 W
Auxiliary contacts 4
Breaker position indication Open/closed
Suitable for IT networks Yes, up to 690 V
Net weight 14 kg
Standard IEC
EAN 8015644746131
ABB product group Emax2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA070763R1?

The ABB 1SDA070763R1 is an E1.2N 800 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals and an Ekip Dip LSIG solid-state electronic trip unit.

What protection functions does the Ekip Dip LSIG provide?

The Ekip Dip LSIG provides long-time (L) overload, short-time selective (S), instantaneous (I) and ground-fault (G) protection.

What is the breaking capacity of the ABB E1.2N 800?

The breaker has an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC.

What is the short-time withstand rating of the ABB 1SDA070763R1?

The breaker has a rated short-time withstand current of 50 kA for 1 s and 30 kA for 3 s.

What is the difference between Ekip Dip LSI and Ekip Dip LSIG?

Both releases provide long-time, short-time selective and instantaneous protection, while the LSIG version additionally provides ground-fault (G) protection for earth-fault conditions.

Trusted ABB Power Distribution Technology

ABB SACE Emax 2 air circuit breakers combine high fault-interruption capability, compact construction and proven Ekip electronic protection to provide selective and dependable protection for modern low-voltage power distribution systems.