1SDA070758R1 ABB E1.2C 800 Ekip Hi-Touch LSI 800 A 3-Pole Fixed Air Circuit Breaker

1SDA070758R1 ABB E1.2C 800 Ekip Hi-Touch LSI 800 A 3-Pole Fixed Air Circuit Breaker

ABB 1SDA070758R1 E1.2C 800 is an 800 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals, an R800 rating plug and an Ekip Hi-Touch LSI solid-state trip unit providing long-time, short-time and instantaneous protection.

SKU: 1SDA070758R1MPN: 1SDA070758R1
Price
List Price £8,506.66 ex VAT
Your Price (ex VAT) Save 25%
£6,380.00 25% OFF
You save £2,126.67 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,380.00
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,380.00

Why Choose the ABB E1.2C 800 Ekip Hi-Touch LSI 3-Pole Air Circuit Breaker?

The ABB 1SDA070758R1 is a SACE Emax 2 E1.2C air circuit breaker designed for advanced protection, switching and isolation in demanding low-voltage AC power distribution systems. Rated at 800 A, this three-pole circuit breaker combines the compact E1.2 frame with ABB's advanced Ekip Hi-Touch LSI solid-state electronic trip unit.

The integrated Ekip Hi-Touch LSI trip unit provides long-time (L), short-time (S) and instantaneous (I) protection functions. The Hi-Touch platform extends conventional overcurrent protection with advanced measurement and power-quality functionality, making it suitable for sophisticated electrical distribution systems requiring detailed monitoring and protection capabilities.

The 1SDA070758R1 features a three-pole fixed (F) construction with front terminals (F) and an R800 rating plug. The E1.2C platform provides an ultimate short-circuit breaking capacity of 50 kA at 400 V AC and a short-time withstand current of 42 kA for 1 s, providing robust performance for industrial, commercial and infrastructure switchboards.

Key Advantages

  • Advanced ABB SACE Emax 2 E1.2C air circuit breaker for demanding low-voltage systems.
  • 800 A rated current for high-current feeder and distribution applications.
  • Ekip Hi-Touch LSI solid-state trip unit with advanced protection and measurement capabilities.
  • Long-time, short-time and instantaneous protection against overload and short-circuit conditions.
  • 50 kA ultimate short-circuit breaking capacity at 400 V AC.
  • 42 kA short-time withstand current for 1 s.
  • Three-pole fixed construction for permanent switchboard integration.
  • Front terminals provide an accessible main-circuit connection arrangement.

Key Features

  • ABB SACE Emax 2 E1.2C 800 air circuit breaker.
  • 800 A rated current.
  • 690 V rated voltage.
  • Three-pole construction.
  • Fixed (F) installation.
  • Front (F) terminals.
  • Ekip Hi-Touch LSI solid-state electronic trip unit.
  • R800 rating plug.
  • L protection: long-time overload protection.
  • S protection: short-time short-circuit protection.
  • I protection: instantaneous short-circuit protection.
  • No integrated ground-fault protection in this LSI configuration.
  • Fitted with four auxiliary change-over contacts.
  • Includes circuit-breaker open/closed position indication.
  • Designed for advanced monitoring and power-quality applications.

Advanced Ekip Hi-Touch LSI Protection and Monitoring

The ABB Ekip Hi-Touch LSI trip unit combines advanced electronic monitoring with three fundamental overcurrent protection functions. Long-time protection responds to sustained overload conditions, short-time protection enables controlled and selective response to short circuits, and instantaneous protection provides rapid interruption of severe short-circuit faults.

The Hi-Touch platform is intended for sophisticated electrical installations where enhanced measurement, monitoring and power-quality capabilities are valuable. Combined with the E1.2C 800 circuit-breaker platform, the 1SDA070758R1 provides an 800 A fixed protection solution with strong short-circuit performance for modern low-voltage distribution switchboards.

Typical Applications

  • Low-voltage main and sub-distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process plant switchgear.
  • High-current feeder circuit protection.
  • Infrastructure and critical-power installations.
  • Systems requiring advanced electrical monitoring and protection.
  • Three-phase systems requiring LSI overcurrent protection.

Technical Specifications

Series SACE Emax 2
Order code 1SDA070758R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Frame E1.2
Performance level C
Rated current 800 A
Rated voltage 690 V
Number of poles 3
Current type AC
Installation Fixed (F)
Terminal type Front (F)
Main circuit connection Bolt connection
Trip unit Ekip Hi-Touch LSI
Release type Solid-state electronic
Rating plug R800
Protection functions Long-time, short-time and instantaneous (LSI)
Ultimate short-circuit breaking capacity at 400 V AC 50 kA
Short-time withstand current 42 kA for 1 s
Overload release setting 320 A minimum setting
Short-time short-circuit release setting 480 A minimum setting
Instantaneous short-circuit release setting 1200 A minimum setting
Integrated ground-fault protection No
Auxiliary contacts 4 change-over contacts
Open/closed indication Yes
Motor drive Optional
Degree of protection IP30
Power loss 50 W
Electrical durability 8000 cycles
Mechanical durability 20,000 cycles
Rated impulse withstand voltage 12 kV
EAN 8015644746087

Frequently Asked Questions

What is the ABB 1SDA070758R1?

The ABB 1SDA070758R1 is a SACE Emax 2 E1.2C 800 three-pole fixed air circuit breaker with front terminals and an Ekip Hi-Touch LSI solid-state electronic trip unit.

What is the rated current of the ABB E1.2C 800?

The ABB E1.2C 800 is rated at 800 A and is designed for demanding low-voltage feeder and power distribution applications.

What protection functions does the Ekip Hi-Touch LSI provide?

The Ekip Hi-Touch LSI trip unit provides long-time (L), short-time (S) and instantaneous (I) overcurrent protection. This LSI configuration does not include integrated ground-fault protection.

What is the short-circuit performance of the ABB E1.2C 800?

The E1.2C 800 has an ultimate short-circuit breaking capacity of 50 kA at 400 V AC and a short-time withstand current of 42 kA for 1 s.

What mounting and terminal configuration does the ABB 1SDA070758R1 use?

The 1SDA070758R1 has a fixed (F) three-pole construction with front (F) terminals for permanent integration into compatible low-voltage switchgear.

Advanced Emax 2 Protection from ABB

ABB SACE Emax 2 air circuit breakers with Ekip Hi-Touch protection combine robust short-circuit performance, advanced electronic protection and sophisticated monitoring capabilities for demanding low-voltage power distribution systems.