ABB 1SDA070753R1 E1.2C 800 is an 800 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals, Ekip Dip LSIG electronic protection, integrated ground-fault protection and 50 kA ultimate breaking capacity at 400–440 V AC.
£4,198.16
The ABB E1.2C 800 Ekip Dip LSIG, order code 1SDA070753R1, is a SACE Emax 2 air circuit breaker engineered for dependable protection and control of low-voltage power distribution systems. This configuration combines an 800 A rated current, three-pole construction, fixed installation and front terminals with ABB's Ekip Dip LSIG solid-state electronic protection release.
The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC. Its rated short-time withstand current is 42 kA for 1 s and 24 kA for 3 s, supporting selective protection strategies in industrial, commercial and infrastructure distribution systems.
The fitted Ekip Dip LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection. This comprehensive protection package makes the 1SDA070753R1 particularly suitable for distribution systems requiring both selective overcurrent protection and integrated earth-fault protection in a compact fixed air circuit breaker.
The Ekip Dip LSIG release combines four complementary protection functions. Long-time protection responds to sustained overload conditions, short-time protection provides a controlled response to short circuits for selective coordination, instantaneous protection rapidly clears severe high-current faults, and the ground-fault function detects potentially damaging current flowing to earth.
The E1.2C's 42 kA one-second short-time withstand capability complements its selective short-time protection function, allowing properly coordinated downstream devices time to clear appropriate faults. Integrated ground-fault protection extends this protection strategy to earth-fault conditions, making the 1SDA070753R1 a versatile solution for distribution systems where comprehensive electronic protection and continuity of unaffected circuits are important.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA070753R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 3 |
| Short-circuit performance level | C |
| Icu at 400/415/440 V AC | 50 kA |
| Icu at 500/525/690 V AC | 42 kA |
| Ics at 380–440 V AC | 50 kA |
| Ics at 500–690 V AC | 42 kA |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw) | 42 kA for 1 s; 24 kA for 3 s |
| Protection release | Ekip Dip LSIG |
| Release type | Electronic (EL) |
| Protection functions | Long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) |
| Integrated earth-fault protection | Yes |
| Execution | Fixed |
| Terminal connection | Front |
| Main-circuit connection | Bolted |
| Connecting capacity | 500 mm² |
| Recommended terminal screw | M12 |
| Terminal tightening torque | 45 N·m |
| Auxiliary change-over contacts | 4 |
| Open/closed indication | Yes |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Power loss | 50 W |
| Electrical durability | 8,000 operations |
| Mechanical durability | 20,000 operations |
| Standard | IEC 60947-2 |
| EAN | 8015644746032 |
The ABB 1SDA070753R1 is an 800 A three-pole SACE Emax 2 E1.2C air circuit breaker with fixed construction, front terminals and an Ekip Dip LSIG electronic protection release.
The LSIG release provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection for comprehensive low-voltage distribution-system protection.
The E1.2C 800 provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC, with rated service breaking capacity equal to 100% of Icu.
Yes. The G function in the Ekip Dip LSIG release provides integrated ground-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
The 1SDA070753R1 is a fixed three-pole air circuit breaker equipped with front main terminals for permanent installation within a compatible low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine compact construction, dependable short-circuit performance, selective coordination and integrated ground-fault protection in a versatile platform engineered for industrial, commercial and infrastructure power distribution systems.