1SDA070753R1 ABB E1.2C 800 Ekip Dip LSIG 3-Pole Fixed Air Circuit Breaker

1SDA070753R1 ABB E1.2C 800 Ekip Dip LSIG 3-Pole Fixed Air Circuit Breaker

ABB 1SDA070753R1 E1.2C 800 is an 800 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals, Ekip Dip LSIG electronic protection, integrated ground-fault protection and 50 kA ultimate breaking capacity at 400–440 V AC.

SKU: 1SDA070753R1MPN: 1SDA070753R1
Price
List Price £5,597.55 ex VAT
Your Price (ex VAT) Save 25%
£4,198.16 25% OFF
You save £1,399.39 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,198.16
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,198.16

Why Choose the ABB E1.2C 800 Ekip Dip LSIG Air Circuit Breaker?

The ABB E1.2C 800 Ekip Dip LSIG, order code 1SDA070753R1, is a SACE Emax 2 air circuit breaker engineered for dependable protection and control of low-voltage power distribution systems. This configuration combines an 800 A rated current, three-pole construction, fixed installation and front terminals with ABB's Ekip Dip LSIG solid-state electronic protection release.

The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC. Its rated short-time withstand current is 42 kA for 1 s and 24 kA for 3 s, supporting selective protection strategies in industrial, commercial and infrastructure distribution systems.

The fitted Ekip Dip LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection. This comprehensive protection package makes the 1SDA070753R1 particularly suitable for distribution systems requiring both selective overcurrent protection and integrated earth-fault protection in a compact fixed air circuit breaker.

Key Advantages

  • 800 A rated current for substantial low-voltage distribution circuits.
  • 50 kA ultimate breaking capacity at 400–440 V AC.
  • 42 kA ultimate breaking capacity at 500–690 V AC.
  • 42 kA short-time withstand current for 1 s supports selective coordination.
  • Comprehensive Ekip Dip LSIG electronic protection.
  • Integrated ground-fault protection in addition to overload and short-circuit protection.
  • Ics equal to 100% of Icu across the specified operating-voltage range.
  • 690 V AC rated operational voltage for broad low-voltage system compatibility.
  • Three-pole fixed construction with front terminals simplifies switchboard integration.

Key Features

  • ABB SACE Emax 2 E1.2C air circuit breaker.
  • Rated current (In): 800 A.
  • Rated uninterrupted current (Iu): 800 A.
  • Three-pole configuration.
  • Fixed (F) execution.
  • Front (F) main terminals.
  • Ekip Dip LSIG electronic release.
  • LSIG protection: long-time, short-time, instantaneous and ground-fault functions.
  • C short-circuit performance level.
  • 50 kA Icu at 400–440 V AC.
  • 42 kA Icu at 500–690 V AC.
  • Integrated earth-fault protection.
  • Four auxiliary change-over contacts.
  • Open/closed circuit-breaker position indication.
  • Optional motor-drive capability for enhanced automation.

Comprehensive Ekip Dip LSIG Protection

The Ekip Dip LSIG release combines four complementary protection functions. Long-time protection responds to sustained overload conditions, short-time protection provides a controlled response to short circuits for selective coordination, instantaneous protection rapidly clears severe high-current faults, and the ground-fault function detects potentially damaging current flowing to earth.

The E1.2C's 42 kA one-second short-time withstand capability complements its selective short-time protection function, allowing properly coordinated downstream devices time to clear appropriate faults. Integrated ground-fault protection extends this protection strategy to earth-fault conditions, making the 1SDA070753R1 a versatile solution for distribution systems where comprehensive electronic protection and continuity of unaffected circuits are important.

Typical Applications

  • Low-voltage main and sub-distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plant electrical systems.
  • Commercial building power distribution.
  • Infrastructure and utility installations.
  • Generator and transformer distribution assemblies.
  • Applications requiring comprehensive LSIG electronic protection.
  • Systems requiring integrated ground-fault protection.
  • Fixed switchboard installations requiring an 800 A three-pole air circuit breaker.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA070753R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Rated current (In) 800 A
Rated uninterrupted current (Iu) 800 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Current type AC
Number of poles 3
Short-circuit performance level C
Icu at 400/415/440 V AC 50 kA
Icu at 500/525/690 V AC 42 kA
Ics at 380–440 V AC 50 kA
Ics at 500–690 V AC 42 kA
Ics as percentage of Icu 100%
Rated short-time withstand current (Icw) 42 kA for 1 s; 24 kA for 3 s
Protection release Ekip Dip LSIG
Release type Electronic (EL)
Protection functions Long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G)
Integrated earth-fault protection Yes
Execution Fixed
Terminal connection Front
Main-circuit connection Bolted
Connecting capacity 500 mm²
Recommended terminal screw M12
Terminal tightening torque 45 N·m
Auxiliary change-over contacts 4
Open/closed indication Yes
Motor drive Optional
Degree of protection IP30
Power loss 50 W
Electrical durability 8,000 operations
Mechanical durability 20,000 operations
Standard IEC 60947-2
EAN 8015644746032

Frequently Asked Questions

What is the ABB 1SDA070753R1?

The ABB 1SDA070753R1 is an 800 A three-pole SACE Emax 2 E1.2C air circuit breaker with fixed construction, front terminals and an Ekip Dip LSIG electronic protection release.

What protection functions does the Ekip Dip LSIG release provide?

The LSIG release provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection for comprehensive low-voltage distribution-system protection.

What is the breaking capacity of the ABB E1.2C 800?

The E1.2C 800 provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC, with rated service breaking capacity equal to 100% of Icu.

Does the ABB 1SDA070753R1 provide ground-fault protection?

Yes. The G function in the Ekip Dip LSIG release provides integrated ground-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.

Is the ABB 1SDA070753R1 fixed or withdrawable?

The 1SDA070753R1 is a fixed three-pole air circuit breaker equipped with front main terminals for permanent installation within a compatible low-voltage switchboard.

Trusted for Comprehensive Low-Voltage Protection

ABB SACE Emax 2 air circuit breakers combine compact construction, dependable short-circuit performance, selective coordination and integrated ground-fault protection in a versatile platform engineered for industrial, commercial and infrastructure power distribution systems.