Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA070752R1 E1.2C 800 is an 800 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals, Ekip Dip LSI electronic protection, 50 kA ultimate breaking capacity at 400–440 V AC and 42 kA short-time withstand capability for 1 s.
£3,731.70
The ABB E1.2C 800 Ekip Dip LSI, order code 1SDA070752R1, is a SACE Emax 2 air circuit breaker engineered for dependable protection and control in low-voltage power distribution systems. This configuration combines an 800 A rated current, three-pole construction, fixed installation and front terminals with ABB's Ekip Dip LSI solid-state electronic protection release.
The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC. Its rated short-time withstand current is 42 kA for 1 s, supporting coordinated protection in industrial, commercial and infrastructure distribution systems.
The fitted Ekip Dip LSI release provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. Together with the compact E1.2 frame, fixed construction and front-terminal arrangement, this makes the 1SDA070752R1 a practical solution for switchboards requiring reliable electronic protection and selective coordination without the advanced touchscreen functions of higher-tier Ekip releases.
The Ekip Dip LSI release combines three complementary protection functions. Long-time protection responds to sustained overload conditions, short-time protection provides a controlled response to short circuits to support selective coordination with downstream devices, and instantaneous protection rapidly disconnects severe high-current faults.
The E1.2C's 42 kA one-second short-time withstand capability complements the selective short-time protection function by allowing properly coordinated downstream protective devices time to clear appropriate faults. This combination makes the 1SDA070752R1 well suited to multi-level distribution systems where both dependable fault interruption and continuity of unaffected circuits are important.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA070752R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Short-circuit performance level | C |
| Icu at 400/415/440 V AC | 50 kA |
| Icu at 500/525/690 V AC | 42 kA |
| Ics at 380–440 V AC | 50 kA |
| Ics at 500–690 V AC | 42 kA |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw) | 42 kA for 1 s; 24 kA for 3 s |
| Protection release | Ekip Dip LSI |
| Release type | Electronic (EL) |
| Protection functions | Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) |
| Execution | Fixed |
| Terminal connection | Front |
| Terminal type | Bolted |
| Power loss | 50 W |
| Electrical durability | 8,000 operations |
| Mechanical durability | 20,000 operations |
| Product width | 210 mm |
| Product height | 296 mm |
| Product depth | 183 mm |
| Net weight | 14 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644746025 |
The ABB 1SDA070752R1 is an 800 A three-pole SACE Emax 2 E1.2C air circuit breaker with fixed construction, front terminals and an Ekip Dip LSI electronic protection release.
The LSI release provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection for coordinated low-voltage power distribution.
The E1.2C 800 provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC, with Ics equal to 100% of Icu.
The 1SDA070752R1 is a fixed three-pole air circuit breaker equipped with front main terminals for permanent installation within a compatible low-voltage switchboard.
The breaker has a rated short-time withstand current of 42 kA for 1 s and 24 kA for 3 s, supporting selective coordination in appropriately engineered distribution systems.
ABB SACE Emax 2 air circuit breakers combine compact construction, dependable short-circuit performance and electronic protection in a versatile platform engineered for industrial, commercial and infrastructure low-voltage distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.