1SDA070717R1 ABB E1.2C 630 Ekip G Touch LSIG 3-Pole Fixed Air Circuit Breaker

1SDA070717R1 ABB E1.2C 630 Ekip G Touch LSIG 3-Pole Fixed Air Circuit Breaker

ABB 1SDA070717R1 is an Emax 2 E1.2C 630 A three-pole fixed air circuit breaker with front terminals and an Ekip G Touch LSIG electronic trip unit for advanced generator and low-voltage power-system protection.

SKU: 1SDA070717R1MPN: 1SDA070717R1
Price
List Price £8,566.88 ex VAT
Your Price (ex VAT) Save 25%
£6,425.16 25% OFF
You save £2,141.72 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,425.16
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,425.16

Why Choose the ABB 1SDA070717R1 E1.2C 630 Ekip G Touch LSIG Air Circuit Breaker?

The ABB 1SDA070717R1 is an Emax 2 E1.2C 630 three-pole fixed air circuit breaker equipped with an Ekip G Touch LSIG electronic trip unit. Designed for generator protection and demanding low-voltage power-distribution applications, it combines the compact E1.2 frame with advanced electronic protection, measurement and monitoring functionality.

This configuration has a 630 A rated uninterrupted current, three-pole construction, fixed execution and front terminals. The E1.2C performance level provides a 50 kA ultimate short-circuit breaking capacity at 440 V and a 42 kA short-time withstand current for 1 second, supporting demanding generator and distribution switchboards.

The Ekip G Touch LSIG trip unit combines generator-oriented functionality with long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection. Its Touch interface provides an advanced platform for configuring protection and accessing electrical information in professional power-system applications.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for generator and power-distribution applications.
  • 630 A rated uninterrupted current on the compact E1.2 frame.
  • Ekip G Touch LSIG electronic trip unit with generator-oriented protection functionality.
  • 50 kA ultimate short-circuit breaking capacity at 440 V.
  • 42 kA short-time withstand current for 1 second.
  • Three-pole fixed construction with front terminals for professional switchboard integration.

Key Features

  • ABB SACE Emax 2 air circuit breaker.
  • E1.2C 630 configuration.
  • 630 A rated uninterrupted current.
  • 690 V rated voltage.
  • Three-pole construction.
  • Fixed execution.
  • Front terminals.
  • Ekip G Touch electronic trip unit.
  • LSIG protection: long-time overload, selective short-circuit, instantaneous short-circuit and earth-fault protection.
  • Integrated earth-fault protection and generator-oriented electronic protection functionality.

Advanced Generator and Power-System Protection

The Ekip G Touch LSIG electronic trip unit is designed for applications requiring advanced generator and distribution-system protection. Its LSIG functions provide long-time overload protection, selective short-circuit protection, instantaneous short-circuit protection and earth-fault protection, helping safeguard generators, conductors and connected electrical equipment against a broad range of abnormal conditions.

Combined with the E1.2C air circuit-breaker platform, the ABB 1SDA070717R1 provides substantial short-circuit performance in a compact fixed format. Front terminals support straightforward switchboard integration, while the Ekip G Touch platform makes this configuration particularly suitable for generator switchboards and sophisticated low-voltage power-distribution systems.

Typical Applications

  • Generator protection and generator switchboards.
  • Low-voltage main distribution switchboards.
  • Industrial power-distribution systems.
  • Critical and standby power installations.
  • Commercial and infrastructure electrical distribution.
  • OEM switchboards requiring advanced LSIG generator protection.

Technical Specifications

Product family SACE Emax 2
ABB order code 1SDA070717R1
Product type Air circuit breaker
Frame E1.2
Performance level C
Rated uninterrupted current 630 A
Rated voltage 690 V
Number of poles 3
Execution Fixed
Terminals Front
Trip unit Ekip G Touch
Protection functions LSIG
Integrated earth-fault protection Yes
Ultimate short-circuit breaking capacity at 440 V 50 kA
Short-time withstand current, 1 s 42 kA
Overload release adjustment range 252–630 A
Short-time delayed short-circuit adjustment range 378–6300 A
Instantaneous short-circuit adjustment range 945–9450 A
Degree of protection IP30
Standard IEC
ABB product group Emax2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA070717R1?

The ABB 1SDA070717R1 is an Emax 2 E1.2C 630 three-pole fixed air circuit breaker with front terminals and an Ekip G Touch LSIG electronic trip unit.

What is the current rating of ABB 1SDA070717R1?

The E1.2C 630 configuration has a 630 A rated uninterrupted current.

What protection functions does the Ekip G Touch LSIG trip unit provide?

The LSIG configuration provides long-time overload protection, selective short-circuit protection, instantaneous short-circuit protection and earth-fault protection.

Is ABB 1SDA070717R1 suitable for generator protection?

Yes. The Ekip G Touch trip unit provides generator-oriented protection functionality and is designed for applications such as generator switchboards and associated low-voltage distribution systems.

What is the breaking capacity of the E1.2C 630?

The E1.2C configuration provides an ultimate short-circuit breaking capacity of 50 kA at 440 V.

What is the short-time withstand current of ABB 1SDA070717R1?

The E1.2C configuration has a 42 kA short-time withstand current for 1 second.

Is ABB 1SDA070717R1 fixed or withdrawable?

The 1SDA070717R1 is a fixed Emax 2 air circuit breaker with front terminals.